1 dari 6

ABB ACS550-01-08A8-4 ACS550 Variable Frequency Drive

ABB ACS550-01-08A8-4 ACS550 Variable Frequency Drive

Hanya 5 item tersisa di stok
  • Produsen: ABB

  • Nomor Produk: ACS550-01-08A8-4

  • Negara asal:Swedia

  • Jenis Produk: Variable Frequency Drives

  • Kode batang: 85044095

  • Pembayaran: T/T, Western Union

  • Berat: 6500g

  • Dimensi: 12.50 x 36.90 x 21.20 cm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Kuantitas
Lihat detail lengkap

Description

Engineered to deliver precise speed and torque control for three-phase induction motors, the ABB ACS550-01-08A8-4 variable frequency drive integrates seamlessly into low-voltage industrial power systems. This highly reliable motor controller supports an output power rating of 4 kW (5 HP) under normal duty conditions and operates across a standard supply voltage range of 380 to 480 V AC. As part of the established ACS550 series, this drive features an integrated swinging choke that significantly lowers harmonic distortion compared to standard line reactors, enhancing the operational lifespan of connected electrical infrastructure. The unit is housed in a robust IP21 protection enclosure, making it ideal for standard wall-mounted industrial installations requiring dependable thermal dissipation and compact spatial footprints.

Features

  • Patented Swinging Choke: Reduces line harmonics up to 25% at partial loads without the bulk of external line reactors.
  • Flexible Control Modes: Supports scalar (V/Hz) and sensorless vector control for adaptable torque profiles.
  • Integrated EMC Filter: Built-in RFI/EMC filter ensures compliance with European and domestic high-frequency interference standards.
  • Native Fieldbus Interface: Standard Modbus RTU interface on RS-485 terminals simplifies integration into distributed SCADA architectures.
  • FlashDrop Compatibility: Enables parameter uploading and drive programming in seconds without applying main power.

Applications

  • Centrifugal pumps requiring energy-efficient flow control and quadratic torque profiles.
  • Industrial supply and exhaust fans utilizing speed-regulated HVAC air distribution.
  • Material handling conveyors demanding controlled acceleration and deceleration ramps to prevent mechanical stress.
  • Mixers, agitators, and dosing systems requiring constant low-speed torque stability.

Technical Specifications Table

Parameter Specification
Manufacturer ABB
Model Number ACS550-01-08A8-4
Series ACS550 Standard Drive
Input Voltage Range 380 to 480 V AC (+10% / -15%)
Number of Phases 3-Phase Input / 3-Phase Output
Normal Duty Output Power 4 kW (5 HP)
Normal Duty Output Current 8.8 A
Heavy Duty Output Power 3 kW (4 HP)
Heavy Duty Output Current 6.9 A
Input Frequency Range 48 to 63 Hz
Enclosure Rating IP21 (UL Type 1)
Control Connections 2 Analog Inputs, 2 Analog Outputs, 6 Digital Inputs, 3 Relay Outputs
Communications Modbus RTU (Embedded)
Product Dimension (W x H x D) 12.50 x 36.90 x 21.20 cm
Net Shipping Weight 6.50 kg
Commodity Code 85044095

Connections and Interfaces

Terminal Designation Function / Assignment
U1, V1, W1 3-Phase AC Power Input Terminals
U2, V2, W2 3-Phase AC Variable Frequency Output to Motor
BRK+, BRK- Dynamic Braking Resistor External Connections
AI1 / AI2 Analog Inputs (Voltage 0...10V / Current 0/4...20mA)
AO1 / AO2 Analog Outputs (Programmable, standard 0/4...20mA)
DI1...DI6 Digital Inputs (Configurable, 12...24V DC PNP/NPN logic)
RO1, RO2, RO3 Relay Outputs (Form C, programmable, max 250V AC / 30V DC)

Alternative Models & Compatibility

The ACS550-01-08A8-4 directly replaces legacy Frame R1 ACS400 drives with minimal mechanical adaptation. When retrofitting, note that digital I/O macros may default to "ABB Standard"; ensure your existing control wire maps match the programmed macro. For network upgrades, this VFD is fully compatible with optional fieldbus modules including the RPBA-01 (Profibus-DP), RCAN-08 (CANopen), and RETA-01 (EtherNet/IP / Modbus TCP).

Application Pitfalls & Engineering Notes

For high-elevation installations exceeding 1000 meters above sea level, the output current must be derated by 1% for every additional 100 meters. Additionally, when using motor cables longer than 100 meters (328 feet), parasitic capacitance to earth can cause false "F0016" (Earth Fault) trips. In these configurations, an external du/dt filter or output reactor must be installed to protect the drive's output IGBT bridge and prevent winding degradation on older motors.

Commissioning & Wiring Tips

To configure analog input signals, ensure the onboard DIP switches (located behind the Assistant Control Panel assembly on the control board) match the desired input signal type: Switch J1 controls AI1 (Voltage/Current) and Switch J2 controls AI2 (Voltage/Current). Ensure control wiring is run in separate conduits from high-power motor and input cables to prevent high-frequency noise coupling. Always ground the motor cable shield 360 degrees at both the VFD clamp and the motor terminal box.

Installation Guidelines

CRITICAL WARNING: ELECTRICAL HAZARD

Before beginning any installation, maintenance, or terminal wiring, disconnect all input power sources and lock out all disconnects. Wait a minimum of 5 minutes after de-energizing the drive to allow the internal DC bus capacitors to discharge fully. Verify zero voltage across terminals U1/V1/W1 and the DC bus terminals prior to handling internal components.

1

Mount the drive vertically on a flat, non-flammable surface, ensuring at least 200 mm of clearance above and below the cooling fan assembly for unimpeded vertical airflow.

2

Connect the input power conductors to terminals U1, V1, and W1, and the protective earth (PE) grounding conductor to the drive's primary chassis ground terminal.

3

Terminate the motor cables to U2, V2, and W2 using symmetrically shielded motor cables to minimize electromagnetic radiation and bearing currents.

4

Wire control, interlock, and emergency stop circuits to the I/O terminals, separating them by at least 200 mm from the high-voltage power lines.

Loading product navigation…

What does the 'F0016' earth fault indicate on this VFD?

An F0016 fault indicates an asymmetrical earth/ground leakage current in the motor or motor cable. Check the insulation resistance of both the motor windings and the motor cabling using a megohmmeter after disconnecting the drive completely.

Can this drive run on single-phase utility power?

This model is rated for three-phase input power. Operating it on a single-phase supply is not recommended unless substantial current derating (typically 50%) is applied, and parameter 3007 (Input Phase Loss) is configured to prevent automatic tripping.

How do I switch the analog input signals between voltage and current modes?

Locate the J1 jumper block on the control board directly below the keypad mounting cradle. Change the jumper placement for AI1 or AI2 to 'I' for 0/4-20mA current loops, or 'V' for 0-10V voltage signals, and align parameter 1301/1304 accordingly.

What is the function of the built-in swinging choke?

The swinging choke matches drive inductance to the load state. It reduces input line current harmonics up to 25% under partial load conditions and improves the line voltage THD (Total Harmonic Distortion) profile compared to standard input reactors.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian kembali, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Swedia

Produk yang Baru Dilihat

Pengetahuan teknis

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Dari sistem perekat yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga AI,...

Throwback: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...

Factory I/O: Alat Simulasi PLC Modern untuk Pelatihan Otomasi Industri

Factory I/O mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang imersif untuk siswa, insinyur, dan tim pemeliharaan. Platform ini menjembatani kesenjangan antara teori dan praktik...