Beckhoff EL1918-2200 TwinSAFE EtherCAT Terminal 8-channel Digital Input

Beckhoff EL1918-2200 TwinSAFE EtherCAT Terminal 8-channel Digital Input

Hanya 10 item tersisa di stok
  • Produsen: BECKHOFF

  • Nomor Produk: EL1918-2200

  • Negara asal:Jerman

  • Jenis Produk: TwinSAFE Safety Terminals

  • Pembayaran: T/T, Western Union

  • Berat: 2000g

  • Dimensi: 12 mm x 100 mm x 68 mm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

Designed to integrate directly into the EtherCAT I/O system, the Beckhoff EL1918-2200 is an ultra-compact TwinSAFE terminal engineered for the decentralized connection of safety-related sensors. This 8-channel digital input module transmits safe signals via Safety over EtherCAT (FSoE) to a TwinSAFE Logic-capable component, enabling reliable execution of safety functions in complex industrial automation architectures. Featuring 1-wire or 2-wire connection technology, the module combines high-density packaging with robust processing diagnostics to meet strict global safety metrics.

Key Features

  • 8 Fail-Safe Digital Inputs: Supports direct connection of safe sensors and contacts.
  • FSoE Protocol Integration: Operates seamlessly via TwinSAFE / Safety over EtherCAT communication.
  • Flexible Wiring: Compatible with both 1-wire and 2-wire termination schemes.
  • High-Density Housing: 12 mm width optimizes valuable DIN rail footprint.
  • Status Diagnostics: Dedicated LED status indicators on the front panel for bus communication and error tracking.

Applications

  • Automotive Assembly Lines: Interlocking safety gates, light curtains, and emergency stop circuits.
  • Robotic Cells: Processing safe position feedback and functional safety signals.
  • Material Handling Systems: Distributed emergency-off systems over extended physical networks.
  • Packaging Machinery: Multi-axis safety zone management and guard monitoring.

Technical Specifications

Parameter Value / Specification
Manufacturer Beckhoff
Model Number EL1918-2200
Safety Standards EN ISO 13849-1:2015 (Cat. 4, PL e), EN 61508:2010 (SIL 3)
Protocol TwinSAFE / Safety over EtherCAT (FSoE)
Number of Safe Inputs 8
Connection Technology 1-/2-wire
Fault Response Time ≤ watchdog time (parameterizable)
E-bus Current Consumption typ. 165 mA
Power Contacts Current Load max. 10 A
IP Protection Rating IP20
Housing Material Polycarbonate (HD housing)
Solid Wire Cross-Section 0.08 to 1.5 mm² (AWG 28 to 16)
Stranded Wire Cross-Section 0.25 to 1.5 mm² (AWG 22 to 16)
Ferrule Wire Cross-Section 0.14 to 0.75 mm² (AWG 26 to 19)
Stripping Length 8 to 9 mm
Net Weight approx. 50 g
Shipping Weight (Calculated) 0.15 kg (single unit packaging)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm

Empirical Engineering Insights

Alternative Models & Compatibility

While the standard EL1908 offers 8 digital inputs, the EL1918-2200 variant utilizes high-density termination for complex safety mapping and features optimized processing logic parameters. Note that this terminal requires a valid TwinSAFE Logic master (such as an EL6910 or a TwinCAT safety PLC configuration) to execute safe logic functions. Compatibility requires TwinCAT 3.1 or higher for optimal parameter configuration and FSoE protocol handling.

Application Pitfalls & Engineering Notes

A major deployment hazard involves E-bus power budgeting. The EL1918-2200 consumes typically 165 mA from the E-bus. In large nodes populated with multiple safety or analog slices, the internal 5V supply line can quickly saturate. Always recalculate your E-bus current draw in TwinCAT System Manager; insert an EL9410 power supply terminal if the total current exceeds the couplers capacity (typically 2A for standard EtherCAT couplers).

Commissioning & Wiring Tips

When wiring the High Density (HD) spring connections, ensure that ferrules are crimped square and do not exceed 0.75 mm². Use a specialized flat-blade screwdriver to actuate the spring contacts for stranded conductors without pre-crimped ferrules. Keep the stripping length strictly between 8 and 9 mm to avoid exposing bare copper or preventing full contact seating, which can cause intermittent safety channel faults.

Installation Guidelines

CRITICAL WARNING: De-energize the entire control cabinet before inserting or removing the terminal. Failure to do so can cause permanent damage to the internal E-bus transceiver and could initiate unintended safety-system activations or system faults.
1
Mount the terminal onto a standard 35 mm DIN rail (conforming to EN 60715). Align the integrated double slot-and-key connection with adjacent terminals and press down until you hear a secure click.
2
Secure the terminal assembly horizontally using an end bracket to prevent lateral shifting during operation under high vibration.
3
Connect safe sensors using either 1-wire or 2-wire architectures. Standard solid-core wires can be pushed directly into the contact terminal without tool actuation.
4
Power up the system and verify the status LEDs. Configure safety addresses, watchdog parameters, and input mapping via TwinCAT Safety Editor before operational commissioning.
Loading product navigation…

What is the primary function of the Beckhoff EL1918-2200 terminal?

The terminal is an 8-channel digital fail-safe input module designed for decentralized sensor evaluation. It transfers safety-relevant digital signals via FSoE (Safety over EtherCAT) to a TwinSAFE logic controller.

Does the EL1918-2200 require external logic to execute safety functions?

Yes. The module acts purely as an input terminal. It must communicate with a safety logic master, such as an EL6910 TwinSAFE Logic terminal or a software-based safety PLC, to process safety logic.

What are the E-bus current consumption requirements for this safety module?

The module typically consumes 165 mA from the E-bus. Ensure your EtherCAT coupler or auxiliary power terminal (such as an EL9410) has sufficient current headroom.

Which safety standards are supported by this digital input terminal?

It is certified for applications requiring safety performance levels up to Category 4, PL e according to EN ISO 13849-1:2015, and SIL 3 in compliance with EN 61508:2010.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...

Kilasan Masa Lalu: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...