1 dari 1

BECKHOFF EL3403 EtherCAT Terminal 3-Channel Power Measurement Module

BECKHOFF EL3403 EtherCAT Terminal 3-Channel Power Measurement Module

Hanya 10 item tersisa di stok
  • Produsen: BECKHOFF

  • Nomor Produk: EL3403

  • Negara asal:Jerman

  • Jenis Produk: EtherCAT Terminals

  • Pembayaran: T/T, Western Union

  • Berat: 75g

  • Dimensi: 12 mm x 100 mm x 68 mm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

To analyze three-phase AC power networks directly within the industrial fieldbus segment, the Beckhoff EL3403 provides precise, high-performance measurement values. This 3-channel analog input power measurement terminal is designed to calculate comprehensive electrical grid status parameters, including effective power, reactive power, apparent power, energy consumption, phase angle (cos phi), and frequency for each connected phase. Processing inputs up to 500 V AC directly, the module supports highly detailed diagnostics of energy distribution systems and industrial machinery. Non-intrusive current sensing up to 1 A (AC) is executed through external measuring transformers (such as x A/1 A), enabling flexible integration into existing power distribution frameworks.

Features

  • Mains-synchronous conversion with 16-bit resolution for premium signal acquisition.
  • Direct RMS value calculation for all applied voltage and current waveforms.
  • Comprehensive data calculation: delivers current, voltage, active/reactive/apparent power, energy, frequency, and phase angle values directly over the E-bus.
  • Optional single-phase operation mode for simplified monitoring on isolated lines.
  • Galvanic electrical isolation rating of 1500 V to isolate low-voltage logic from high-voltage measuring points.
  • Compact 12 mm design form factor optimizing space layout on industrial DIN rails.

Applications

  • Real-time energy management and sub-metering in industrial production facilities.
  • Dynamic load monitoring and diagnostic tracking on high-power three-phase AC motors.
  • Integration within power distribution plants and substation cabinets for utility tracking.
  • Predictive maintenance analytics based on power signature variations.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model EL3403
Technology 3-phase power measurement for alternating voltages
Number of Inputs 3 x current, 3 x voltage
Measuring Voltage Max. 500 V AC 3~ (ULX-N: max. 288 V AC)
Measuring Current Max. 1 A AC (via measuring transformers x A/1 A)
Resolution 1 uA, 0.1 mV, 10 mW (16-bit)
Measuring Error 0.5% relative to full scale value (U/I), 1% calculated values
Measuring Procedure True RMS calculation
Conversion Time Mains-synchronous
Electrical Isolation 1500 V
Current Consumption E-bus Typ. 120 mA
Process Image Bit Width 62 byte PM input, 3 byte PM output
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95%, non-condensing
Enclosure Protection Rating IP20
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Weight Approx. 75 g

Connections and Interfaces

Connection Property Specification
Wiring Method Solid conductor (e), flexible conductor (f), and ferrule (a)
Actuation Method Spring actuation by screwdriver
Connection Cross-Section (Solid/Stranded) 0.08 to 2.5 mm² (AWG 28 to 14)
Connection Cross-Section (With Ferrule) 0.14 to 1.5 mm² (AWG 26 to 16)
Stripping Length 8 to 9 mm
Current Load Power Contacts Max. 10 A

Installation Guidelines

  • Mount the terminal onto a standard 35 mm DIN rail conforming to EN 60715, locking it firmly into place.
  • Ensure double slot and key mechanical connection is completely flush with adjacent terminals.
  • Route high-voltage measurement lines separated from low-voltage E-bus and signal lines to prevent noise coupling.
  • Install appropriate external current transformer shorting blocks for safety during troubleshooting or hardware swap-outs.

Compliance and Certifications

  • CE
  • UL listed
  • EMC Immunity/Emission: Conforms to EN 61000-6-2 / EN 61000-6-4
  • Vibration/Shock Resistance: Conforms to EN 60068-2-6 / EN 60068-2-27
Loading product navigation…

What parameters can the Beckhoff EL3403 calculate and display?

The EL3403 measures voltage, current, effective power, reactive power, apparent power, energy consumption, phase angle (cos phi), and frequency for each of the three channels.

Does the EL3403 support single-phase operation?

Yes, while the terminal is optimized for 3-phase power measurement on AC networks, it also supports optional single-phase configuration.

What is the maximum voltage input direct rating of the EL3403?

The terminal is rated for a maximum measuring voltage of 500 V AC 3-phase (with ULX-N rating at a maximum of 288 V AC).

How is the current measured using this EtherCAT terminal?

The module measures AC current up to 1 A, which is typically routed via external, standard measuring transformers configured as x A / 1 A.

What is the mechanical environmental protection rating of the EL3403?

The terminal has an IP20 protection rating and is designed for cabinet installation on a 35 mm DIN rail.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Elektrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan untuk Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...