Description

Designed for comprehensive and precise electrical network analysis, the Beckhoff EL3443-0013 serves as a high-performance 3-channel power measurement EtherCAT terminal. This module is engineered to evaluate non-sinusoidal AC and DC distribution systems directly, accommodating voltages up to 480 V AC. Utilizing 24-bit resolution analog inputs, it processes signals from low-voltage current transformers with a nominal output of 333 mV. This makes it an ideal instrument for integration into space-constrained control cabinets where detailed monitoring of effective, reactive, and apparent power, along with harmonic analysis up to the 40th harmonic, is required for preventative maintenance and active energy management.

Features

  • 3-Phase Power Measurement: Features three independent current and three independent voltage measurement channels for complete grid diagnostics.
  • Low-Voltage Sensor Interface: Designed for safe and efficient interfacing with external 333 mV voltage-output current transformers.
  • Advanced Grid Analysis: Measures current, voltage, active/reactive/apparent power, energy values, cos phi, frequency, THD, and harmonics up to the 40th order.
  • Mains Synchronization: Provides net-synchronous updates with an interval of one mains period (20 ms at 50 Hz).
  • Compact Form Factor: Standard 12 mm EtherCAT terminal housing simplifies integration onto standard 35 mm DIN rails.
  • Zero Voltage Crossing Detection: Enables high-accuracy synchronization and phase order detection.

Applications

  • Industrial Energy Monitoring: Deployment in manufacturing facilities to trace, log, and optimize machinery power consumption.
  • Power Quality Auditing: Localized harmonic distortion and voltage anomaly analysis within busy automation networks.
  • Sub-Metering Infrastructures: Integration into distributed control systems to monitor individual assembly lines or plant zones.

Technical Specifications

Parameter Value / Specification
Manufacturer Beckhoff Automation GmbH & Co. KG
Model Number EL3443-0013
Number of Inputs 3 x current, 3 x voltage
Measuring Technology 3-phase power measurement
Max. Measuring Voltage 480 V AC 3~ (ULX-N: max. 277 V AC/240 V DC)
Measuring Current Input 333 mV (AC/DC) via external measurement transformers
Resolution 24 bit
Measuring Error 0.3% relative to full-scale value (U/I), 0.6% calculated value
Electrical Isolation 2500 V
E-bus Current Consumption Typical 120 mA
Update Interval One mains period (20 ms at 50 Hz)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Permissible Relative Humidity 95%, non-condensing
Housing Material Polycarbonate
Connection Technology CAGE CLAMP spring actuation
Conductor Cross-Section Solid/Stranded: 0.08 to 2.5 mm2 (AWG 28...14)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Country of Origin Germany
Shipping Weight (Calculated) 0.15 kg

Connections and Interfaces

Terminal Connection Signal Assignment Description
L1 (1) Voltage Phase 1 Voltage input channel for phase 1 (L1)
L2 (2) Voltage Phase 2 Voltage input channel for phase 2 (L2)
L3 (3) Voltage Phase 3 Voltage input channel for phase 3 (L3)
N (5) Neutral Conductor Neutral connection for reference voltage
I1+ / I1- (9, 10) Current Channel 1 (333 mV) Differential low-voltage input for phase 1 current transformer
I2+ / I2- (11, 12) Current Channel 2 (333 mV) Differential low-voltage input for phase 2 current transformer
I3+ / I3- (13, 14) Current Channel 3 (333 mV) Differential low-voltage input for phase 3 current transformer

Empirical Engineering Insights

Alternative Models & Compatibility

It is critical to distinguish the EL3443-0013 from the standard EL3443-0000. The standard model is configured for direct current measurements of up to 1 A or 5 A AC/DC. In contrast, the EL3443-0013 relies on low-power, voltage-output external sensors (333 mV). Interchanging these terminal types without matching the corresponding field current transformers will cause measurement saturation or catastrophic thermal failure of the inputs.

Application Pitfalls & Engineering Notes

When monitoring networks with significant variable frequency drive (VFD) loading, thermal load within the terminal housing can escalate due to harmonic current peaks. Ensure appropriate lateral space or active heat dissipation within the enclosure if the continuous phase-to-phase voltage remains consistently above 440 V AC. Never connect standard, current-output (x A / 1 A or x A / 5 A) current transformers directly to this module, as the low-voltage inputs cannot clamp the inductive surge of high-current secondary loops.

Commissioning & Wiring Tips

To ensure high-fidelity measurements, always implement shielded twisted pair (STP) wiring for the 333 mV transformer signal lines. The shielding should terminate directly to the functional ground (FE) of the DIN rail closest to the point of entry. In TwinCAT 3, configuration offsets must be applied via the CoE (CanOverEthernet) online parameterization menu to correlate the 333 mV signal range directly to the primary scaling values of the field sensors.

Installation Guidelines

CRITICAL WARNING: Prior to mounting, wiring, or maintenance on the terminal, de-energize the entire distribution network. Verify that the bus system and voltage inputs are fully isolated. Residual charges must be bled from the primary circuit to avoid fatal electric shock or damage to the internal analog converters.
1

Snap the terminal onto the grounded 35 mm DIN rail (conforming to EN 60715) using the integrated locking mechanism.

2

Connect the physical E-Bus logic path by sliding adjacent terminals together using the dual slot and key system.

3

Perform tool-actuated CAGE CLAMP spring wiring. Strip wire insulation to 8-9 mm before inserting conductors into terminal ports.

4

Verify signal routing: establish phase voltage inputs on connections 1, 2, and 3, and terminate current transformer inputs on connections 9 through 14.

Loading product navigation…

What is the main difference between the EL3443-0013 and standard power terminals?

The EL3443-0013 is optimized for 333 mV low-voltage current transformer inputs rather than high-amperage direct AC/DC inputs. This allows for safer and more flexible connections with low-power sensors.

Does the EL3443-0013 require external power supplies?

The control logic and primary operations are powered directly through the EtherCAT E-bus, consuming approximately 120 mA. The voltage and current inputs are strictly passive measurement interfaces.

How are current values scaled inside TwinCAT for this terminal?

Scaling is parameterized in the CoE (CAN over EtherCAT) directory of the terminal within the TwinCAT software. Field engineers must input the primary-to-secondary ratio of the 333 mV current transformer to scale physical values.

Can this unit measure direct current (DC) power networks?

Yes, the EL3443-0013 supports DC power measurements. The voltage inputs accommodate up to 240 V DC, and the current inputs are capable of reading DC shunt outputs calibrated to 333 mV.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian kembali, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Dari sistem perekat yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga AI,...

Throwback: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...

Factory I/O: Alat Simulasi PLC Modern untuk Pelatihan Otomasi Industri

Factory I/O mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang imersif untuk siswa, insinyur, dan tim pemeliharaan. Platform ini menjembatani kesenjangan antara teori dan praktik...