Beckhoff EL9222-4433 EtherCAT Terminal 2-Channel Overcurrent Protection Module

Beckhoff EL9222-4433 EtherCAT Terminal 2-Channel Overcurrent Protection Module

Hanya 10 item tersisa di stok
  • Produsen: BECKHOFF

  • Nomor Produk: EL9222-4433

  • Negara asal:Jerman

  • Jenis Produk: Overcurrent Protection Terminals

  • Pembayaran: T/T, Western Union

  • Berat: 2000g

  • Dimensi: 12 mm x 100 mm x 68 mm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Kuantitas
Lihat detail lengkap

Description

Designed to safeguard critical 24 V DC control circuits within EtherCAT industrial networks, the Beckhoff EL9222-4433 provides precise electronic overcurrent protection for dual channels rated at 3 A each. Operating directly within the standard EtherCAT terminal segment, this module dynamically monitors load currents, offering rapid electronic shutdown in the event of an overload or short circuit, thereby limiting system downtime. It features integrated status LEDs and physical push-buttons on the housing for immediate channel-level diagnostics and manual reset capability, while feeding complete diagnostic telemetry back to the controller via the E-bus interface.

Features

  • Dual-Channel Monitoring: Two independent 24 V DC distribution paths, limiting maximum current to 3 A per channel.
  • Hardware Redundancy: Integrated 4 A slow-blow fail-safe backup fuses provide hardware-level backup protection.
  • E-Bus Telemetry: Seamless configuration, current monitoring, and diagnostic reporting directly through TwinCAT.
  • Local Interactivity: Dedicated LED push-buttons on the terminal face allow for direct manual reset and instant physical status feedback.
  • High Packing Density: Compact 12 mm modular housing width minimizes DIN-rail footprint in control panels.

Applications

  • Sensor/Actuator Power Distribution: Safe current-limited supply routing for decentralized field sensors and valve terminals.
  • Control Cabinet Sub-Circuit Protection: Isolation of critical low-voltage hardware to prevent system-wide voltage collapses during single-point field faults.
  • EtherCAT Segment Protection: Protection of downstream auxiliary power contacts across I/O nodes.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff
Model / Article Number EL9222-4433
Nominal Operating Voltage 24 V DC
Number of Channels 2
Rated Current 3 A per channel
Max. Input Supply Current 10 A
Current Consumption (E-bus) 80 mA typical
Electrical Isolation 500 V (E-bus to signal voltage)
Backup Fail-Safe Element 4 A slow-blow (T) / 4 A slow-blow (T)
Overvoltage Cut-off >= 32 V DC
Hold After Trip-Out >= 10 s
Advance Load Warning Threshold 90 percent of rated channel load
Operating Temperature 0 to 55 degC
Storage Temperature -25 to 85 degC
Enclosure Protection Rating IP20
Housing Material Polycarbonate
Physical Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Net Weight 55 g
Shipping Weight (Calculated) 2.0 kg
Certifications and Approvals CE, cULus, cURus

Connections & Interface Terminal Guide

Terminal Contact Wiring Specifications & Signal Mapping
Solid Conductor Range 0.08 to 2.5 mm² (AWG 28 to 14) via screwdriver spring actuation
Stranded Conductor Range 0.08 to 2.5 mm² (AWG 28 to 14)
Conductor with Ferrule (f) 0.14 to 1.5 mm² (AWG 26 to 16)
Stripping Depth 8 to 9 mm
Power Contact Rating Imax: 10 A (Output 1 utilizes internal power contact path)

Empirical Engineering Insights

Alternative Models & Compatibility

The EL9222-4433 is optimized for 3 A fixed current limits per channel. For variable current configurations, look to the adjustable EtherCAT terminals (such as the EL9224). When inserting this module into an existing I/O stack, ensure that your TwinCAT EtherCAT XML Device Description (ESI) files are updated to match the specific firmware revision. If replacing an older EL9222-0000, verify that your E-bus current budget can handle the 80 mA load of the EL9222-4433.

Application Pitfalls & Engineering Notes

The absolute maximum capacity of the power contact rail is 10 A. Continuous heavy loads across multiple downstream modules must be calculated to prevent overload of the power contacts. If your segment exceeds 10 A total, you must insert an EL9100 or EL9110 power feed terminal directly upstream to segment the power contacts and prevent local terminal overheating.

Commissioning & Wiring Tips

To avoid intermittent faults, adhere strictly to the 8 to 9 mm stripping length. Under-stripping causes insecure mechanical tension clamp engagement, while over-stripping risks exposing bare wire to adjacent, closely-spaced terminals. When commissioning from TwinCAT, remember to map the CoE (CanOverEtherCAT) objects to read historical trip data and clear fault states remotely.

Installation Guidelines

CRITICAL WARNING:

De-energize the entire segment and isolate all 24 V DC power feeds before installing or removing the overcurrent protection terminal. Failure to do so may damage the E-bus connection pins, disrupt network communications, or lead to accidental arc discharges across adjacent contacts.

1
Align the EL9222-4433 terminal with the 35 mm DIN rail (conforming to EN 60715) alongside the existing EtherCAT segment. Ensure the slot and key guides line up correctly.
2
Press the terminal firmly onto the DIN rail until you hear the locking latch snap into position, securing the E-bus connections.
3
Using a standard terminal screwdriver, actuate the spring-actuated clamp connections to insert conductors stripped to 8-9 mm. Re-verify the wire cross-section conforms to AWG 28-14 (solid/stranded) or AWG 26-16 (ferrule).
4
Apply 24 V DC control power, boot the TwinCAT system, and verify that the front status LEDs illuminate green, indicating normal channel conditions.
Loading product navigation…

What is the primary function of the LED buttons on this terminal?

The integrated LED buttons serve a dual purpose: they physically display channel status (overload, tripped, or normal) and allow for direct local manual channel resetting during troubleshooting or maintenance.

Does this module require a separate power feed terminal?

The module uses standard 24 V DC power contacts. If the total cumulative current of your EtherCAT segment's power contacts exceeds 10 A, an upstream feed module like the EL9100 must be integrated to isolate and protect the bus.

Can I configure custom trip currents for the channels?

No, the EL9222-4433 features preset, hardware-defined tripping curves configured for a maximum of 3 A per channel. For adjustable configurations, look to programmable alternatives like the EL9224.

What is the required hold time after an overcurrent trip before resetting?

To prevent immediate thermal stress, there is a built-in thermal cooldown lockout requiring at least 10 seconds after a channel switches off before a reset can be triggered.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian kembali, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Dari sistem perekat yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga AI,...

Throwback: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...

Factory I/O: Alat Simulasi PLC Modern untuk Pelatihan Otomasi Industri

Factory I/O mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang imersif untuk siswa, insinyur, dan tim pemeliharaan. Platform ini menjembatani kesenjangan antara teori dan praktik...