1 dari 1

Beckhoff ER3184-0002 EtherCAT Box 4-channel Analog Input Module

Beckhoff ER3184-0002 EtherCAT Box 4-channel Analog Input Module

Hanya 10 item tersisa di stok
  • Produsen: BECKHOFF

  • Nomor Produk: ER3184-0002

  • Negara asal:Jerman

  • Jenis Produk: EtherCAT Box Modules

  • Pembayaran: T/T, Western Union

  • Berat: 500g

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

Designed for direct field deployment without a control cabinet, the Beckhoff ER3184-0002 EtherCAT Box provides high-precision processing of up to four analog input signals in harsh environments. This module enables software-parameterizable selection between voltage (-10/0 to +10 V) and current (0/4 to 20 mA) measurements on a per-channel basis. Housed in a robust, zinc die-cast shell with an IP67 protection rating, it processes signals with a 16-bit resolution and fast conversion times, making it ideal for distributed machinery and process loops requiring high noise immunity.

Features

  • Four single-ended, individually configurable analog inputs.
  • 16-bit analog-to-digital resolution (including sign) for high signal fidelity.
  • Robust IP65/66/67 physical encapsulation, eliminating the need for protective field enclosures.
  • High-speed conversion rate of approximately 100 microseconds per channel.
  • Support for Distributed Clocks (DC) to ensure tight synchronization across the entire EtherCAT network.
  • Configurable input filter limit frequency up to 5 kHz.
  • Standardized M12 input connections alongside reliable M8 EtherCAT communication ports.

Applications

  • Cabinet-free on-machine sensor consolidation in automotive and manufacturing assembly lines.
  • Distributed process parameters monitoring, including flow, temperature, and pressure transmitters.
  • Automated materials handling and conveyor systems operating in wet or dusty processing plants.
  • High-speed parameter recording systems utilizing TwinCAT-based distributed clocks.

Technical Specifications Table

Parameter Specification
Manufacturer Beckhoff Automation
Model Number ER3184-0002
Number of Inputs 4 (single-ended)
Signal Ranges -10 to +10 V | 0/4 to 20 mA (parameterizable per channel)
Resolution 16 bits (including sign)
Conversion Time ~ 100 microseconds
Internal Resistance > 200 kOhm (voltage) | typ. 85 Ohm + diode voltage (current)
Common-Mode Voltage (UCM) Max. 35 V
Measurement Uncertainty < ±0.3 % (relative to full scale value)
Distributed Clocks (DC) Supported, high-precision synchronization
Input Filter Configurable, limit frequency 5 kHz
Nominal Power Supply 24 V DC (-15% / +20%)
Current Consumption 120 mA from US
Electrical Isolation 500 V
IP Rating IP65 / IP66 / IP67 (conforms to EN 60529)
Operating Temperature 0 to 55 degC
Storage Temperature -25 to 85 degC
Weight Approx. 265 g
Standards & Approvals CE, UL

Connections and Interfaces

Connector / Pin Functional Assignment
M8 Bus Sockets (2 x Shielded) EtherCAT IN / EtherCAT OUT
M12 Socket Pin 1 +24 V DC sensor supply (derived from UP)
M12 Socket Pin 2 Analog input + (Voltage / Current)
M12 Socket Pin 3 GND (Sensor supply ground)
M12 Socket Pin 4 Analog input - (Signal ground)
M12 Socket Pin 5 Shield / Functional Earth (FE)

Empirical Engineering Insights

Alternative Models & Compatibility

The ER3184-0002 serves as a ruggedized, field-mounted alternative to the cabinet-based EP3184-0002 EtherCAT Box. Both modules feature identical electronic behavior and parameterization registers via TwinCAT. However, the ER3184 housing is fabricated from heavy-duty zinc die-cast, whereas EP-series modules utilize lighter plastic housings. Direct firmware drop-in compatibility is maintained from TwinCAT 2.11 Build 2040 and TwinCAT 3.x onwards.

Application Pitfalls & Engineering Notes

When configuring channels for current mode (0 to 20 mA or 4 to 20 mA), the internal input pathway pathways route through an 85 Ohm shunt in series with a protection diode. System designers must ensure that the driving sensor has sufficient compliance voltage to overcome this diode forward drop under full-scale current loops, especially when powering passive loop-powered devices.

Commissioning & Wiring Tips

To guarantee IP67 sealing and maintain shielding performance, all unused M12 and M8 connections must be sealed using authentic Beckhoff protective caps. Ground the zinc housing directly to the machine bed through a dedicated low-impedance earthing strap. This prevents ground loops and ensures high-frequency noise is successfully shunted away from the sensitive 16-bit A/D converters.

Installation Guidelines

CRITICAL WARNING: De-energize all primary field power supplies (US and UP) before mounting or connecting the EtherCAT Box. Ground potential differences between physical nodes can cause instantaneous destruction of the logic interface or damage sensor inputs if connections are hot-plugged.
1

Mount the ER3184-0002 to a flat metal surface using two M3 screws through the integral mounting holes to establish a robust mechanical and thermal interface.

2

Attach the M8 EtherCAT communication cables (IN and OUT ports) using a torque wrench calibrated to 0.4 Nm to maintain ingress protection integrity.

3

Connect the analog sensor cables to the appropriate M12 channels. Ensure you apply the proper pinout configuration for active versus passive current loop requirements.

4

Supply 24 V DC to the M8 power inlet (US and UP). Open TwinCAT, scan the EtherCAT loop, and configure the CoE (CAN over EtherCAT) variables to match the sensors' voltage or current profiles.

Loading product navigation…

How do I switch between voltage and current modes on the ER3184-0002?

Channel modes are software-configured using the TwinCAT System Manager via CoE (CAN over EtherCAT) directory parameterization. No physical wiring changes or module disassembly are needed.

What is the difference between US and UP power supply lines on this EtherCAT Box?

The US line supplies power to the internal EtherCAT module logic and bus communication, whereas UP supplies power directly to the sensor terminals on the M12 interfaces.

Does the ER3184-0002 support Distributed Clocks (DC)?

Yes, it supports high-precision Distributed Clocks, allowing highly synchronized analog input sampling across the entire EtherCAT segment down to the sub-microsecond level.

What happens if an analog input exceeds the operational range?

The module triggers overrange status bits inside the TwinCAT process image, notifying the control loop of potential sensor saturation without knocking the fieldbus connection offline.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...