1 dari 1

Beckhoff IP1002-B810 Fieldbus Box 8-channel Digital Input Module

Beckhoff IP1002-B810 Fieldbus Box 8-channel Digital Input Module

Hanya 10 item tersisa di stok
  • Produsen: BECKHOFF

  • Nomor Produk: IP1002-B810

  • Negara asal:Jerman

  • Jenis Produk: Fieldbus Box Modules

  • Pembayaran: T/T, Western Union

  • Berat: 2000g

  • Dimensi: 30 mm x 175 mm x 26.5 mm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

Decentralized signal acquisition on machine frames and production lines is executed reliably by the Beckhoff IP1002-B810 Fieldbus Box. This device gathers binary control signals from up to eight digital sensors and transmits them over a point-to-point RS232 interface to the master controller. Housed in a robust, fully-sealed polyamide shell, the IP1002-B810 does not require a protective sub-cabinet, enabling direct machine-mount installation in heavy industrial settings. Key features include an integrated 3.0 ms input filter to prevent contact bounce and standard M12 screw-type connection points for rugged sensor field-wiring.

Features

  • 8 Digital Inputs: Supports direct connection of standard 24 V DC binary sensors.
  • RS232 Serial Interface: Peer-to-peer communication protocol with selectable data transfer rates up to 38.4 kbaud.
  • Rugged Sealed Housing: Highly durable PA6 polyamide design conforms to IP65, IP66, and IP67 protection classes.
  • Input Filtering: Integrated 3.0 ms hardware filter to suppress signal noise and contact chatter.
  • Flexible Mounting: Two pre-drilled 3.5 mm structural fixing holes for direct M3 screw attachment to machinery.

Applications

  • Distributed packaging machine automation systems.
  • Conveyor and material handling control networks.
  • Wet process areas requiring high ingress protection ratings.
  • Dedicated serial peer-to-peer data logging configurations.

Technical Specifications Table

Parameter Specification
Manufacturer Beckhoff Automation
Model Reference IP1002-B810
Product Type Fieldbus Box Digital Input Module
Number of Inputs 8 digital inputs
Interface Protocol RS232 (open, documented protocol)
Data Transfer Rates 9.6 kbaud, 19.2 kbaud, 38.4 kbaud (default)
Nominal Input Voltage 24 V DC (-15% / +20%)
"0" Signal Voltage -3 to +5 V (EN 61131-2, type 2)
"1" Signal Voltage 11 to 30 V (EN 61131-2, type 2)
Input Filter Time 3.0 ms
Box Current Consumption 45 mA + sensor current (max 0.5 A total)
Power Supply Connections Feed: 1 x M8 male, 4-pin; Downstream: 1 x M8 female, 4-pin
Bus Interface Connection 1 x M12 socket, 5-pin, B-coded
Sensor Connections M12, screw-type connection
Housing Material PA6 (Polyamide)
Ingress Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Operating Temperature Range 0 to +55 degC
Storage Temperature Range -25 to +85 degC
Approvals CE, UL
Dimensions (W x H x D) 30 mm x 175 mm x 26.5 mm
Net Weight Approx. 210 g
Shipping Weight (Calculated) 2.0 kg

Connections and Interfaces

Connector/Terminal Function / Pin Assignment
M8 Power Feed (Male) Pin 1: +24 V DC Control Voltage (US), Pin 2: +24 V DC Load Voltage (UP), Pin 3: GND (US), Pin 4: GND (UP)
M8 Downstream (Female) Daisy-chain connection to downstream modules (US, UP, GND US, GND UP)
M12 Bus Interface (B-coded) RS232 Serial communication lines (RXD, TXD, GND interface connections)

Empirical Engineering Insights

Alternative Models & Compatibility

The IP1002-B810 model relies on a standard RS232 peer-to-peer connection, which is distinct from the fieldbus-specific IP1002 network modules (such as CANopen or PROFIBUS variants). When configuring the serial link, ensure the controller's serial port parameters match the module's default baud rate of 38.4 kbaud. Standard configuration tasks can be managed directly using Beckhoff's KS2000 software interface via the specified programming adapters.

Application Pitfalls & Engineering Notes

Because RS232 is an unbalanced communication interface, the maximum length of the serial connection cable is strictly limited to 15 meters. Exceeding this distance or using low-grade unshielded cables in high-interference environments (e.g., adjacent to variable frequency drives) will lead to transmission errors and module timeouts. Ensure that the total current draw of connected sensors does not exceed the short-circuit protected limit of 0.5 A across the module.

Commissioning & Wiring Tips

When routing the control cables, use shielded copper wiring (2 x 0.25 mm²) specifically rated for RS232 transmissions. Ensure the shield is grounded properly on the host controller side. For the M8 power distribution daisy chain, verify that the cumulative control voltage (US) draw of all downstream modules does not exceed the contact rating of the feed connectors, which is typically capped at 4 A.

Installation Guidelines

CRITICAL WARNING: Prior to mounting or performing any wiring work on the Fieldbus Box, ensure all power sources—both control voltage (US) and auxiliary load voltage (UP)—are fully de-energized. Failure to isolate power can result in terminal damage, sensor damage, or unexpected system state transitions.
1
Mechanical Mounting: Secure the IP1002-B810 to a flat machine surface using two M3 screws through the 3.5 mm diameter mounting holes. Tighten to the recommended torque spec for your mounting substrate.
2
RS232 Bus Connection: Insert the B-coded 5-pin M12 bus cable into the communication port. Hand-tighten the screw coupling to secure the IP67-rated seal.
3
Power Feed Integration: Connect the incoming 24 V DC power source to the 4-pin M8 male connector. If daisy-chaining, run an M8 cable from the female downstream port to the next fieldbus module.
4
I/O Sensor Termination: Connect the 8 digital sensors to the respective M12 peripheral connections. Seal all unused ports with M12 protective caps to prevent fluid ingress and maintain the IP67 rating.
Loading product navigation…

What is the primary communication protocol used by the IP1002-B810?

This module utilizes a point-to-point RS232 serial interface with selectable baud rates of 9.6 kbaud, 19.2 kbaud, and 38.4 kbaud (default).

What is the maximum allowed cable distance for the RS232 connection?

The maximum recommended transmission cable length for the RS232 connection is 15 meters using high-quality shielded copper cable.

How do you configure the configuration parameters of this Fieldbus Box?

Configuration parameters and communication settings for the module can be adjusted through the Beckhoff KS2000 software environment.

Does the module require a separate protective electrical enclosure?

No, the IP1002-B810 features an IP65/66/67-rated polyamide housing that is fully sealed against moisture, dust, and direct liquid washdowns.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...