1 dari 3

Bently Nevada 330195-02-12-05-CN 3300 XL ETR Reverse Mount Proximity Probe

Bently Nevada 330195-02-12-05-CN 3300 XL ETR Reverse Mount Proximity Probe

Hanya 6 item tersisa di stok
  • Produsen: Bently Nevada

  • Nomor Produk: 330195-02-12-05-CN

  • Negara asal:Amerika Serikat

  • Jenis Produk: 3300 XL 8 mm ETR Reverse Mount Probe

  • Kode batang: 8537101190

  • Pembayaran: T/T, Western Union

  • Berat: 120g

  • Dimensi: 11 mm x 11 mm x 30 mm (H x W x D)

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

330195-02-12-05-CN: 3300 XL 8 mm Extended Temperature Range (ETR) reverse mount proximity probe configured with a 3/8-24 UNF-2A thread, 0.2 in unthreaded length, 1.2 in case length, 0.5 m total cable length, and NEPSI/CCC hazardous area certifications.

Unlike standard 330105 standard temperature variants rated to 177 degC, the 330195-02-12-05-CN ETR version operates at temperatures up to 218 degC (425 degF), making it suitable for high-temperature steam turbine and gas turbine bearing environments. The reverse mount configuration is threaded from the rear, allowing installation in tight internal cavities where front-access is physically restricted. This specific configuration includes a 0.5-meter total cable length and carries the local -CN NEPSI/CCC approval package required for hazardous industrial sites within China.

Features

  • Extended operating temperature rating up to 218 degC (425 degF) for high-temperature machinery environments.
  • Reverse mount design allows rear threading and installation into compact internal machine housings.
  • 3/8-24 UNF-2A thread pattern fits standard North American mechanical interfaces.
  • 0.5 meter (1.6 feet) total cable length pairs with standard 3300 XL extension cables and Proximitor sensors to form a complete 5-meter or 9-meter transducer system.
  • Standard unarmored coaxial cable configuration with high-temperature insulation.
  • Gold-plated ClickLoc connector provides secure mechanical connection with finger-tight torque.
  • China hazardous area certification (NEPSI and CCC) compliant with local regulatory requirements.

Applications

This proximity probe is used in machinery vibration and position monitoring systems across heavy industries. Typical application scenarios include:

  • Steam turbine bearing vibration and oil film monitoring.
  • Gas turbine rotor axial position and casing expansion measurement.
  • High-pressure pump shaft vibration and thrust position tracking.
  • Electric motor thrust bearing alignment monitoring.
  • Hydroelectric generator shaft runout analysis.

Ordering Information

Option / Segment Position Code Value on This SKU Description of Option Selection
Orderable Part Number 330195-02-12-05-CN 3300 XL 8 mm ETR Reverse Mount Probe, 3/8-24 UNF-2A threads
A - Unthreaded Length Option 02 0.2 in (5.0 mm) unthreaded length
B - Overall Case Length Option 12 1.2 in (30 mm) case length
C - Total Length Option 05 0.5 meter (1.6 feet) total cable length
Suffix -CN -CN China hazardous area approval package (NEPSI + CCC + applicable markings)

Technical Specifications

Parameter Specification Value
Manufacturer Bently Nevada
Part Number 330195-02-12-05-CN
Transducer Type Eddy-current proximity transducer
Probe Tip Diameter 8.0 mm (0.31 in)
Thread Type 3/8-24 UNF-2A threads
Unthreaded Length 0.2 in (5.0 mm)
Overall Case Length 1.2 in (30 mm)
Total Cable Length 0.5 meter (1.6 feet)
Cable Type 75-ohm coaxial cable, high-temperature rating, unarmored
Operating Temperature Range -51 degC to +218 degC (-60 degF to +425 degF)
System Compatibility Works with 3300 XL 8 mm Proximitor Sensor (standard 5-meter or 9-meter systems)
Vibration and Shock Limits 5 g peak, 15 to 10,000 Hz (vibration); 50 g peak, 11 ms (shock)
Weight 0.12 kg
Dimensions 11 mm x 11 mm x 30 mm (H x W x D)

Connections and Interfaces

Component Interface Connector Type Interface Role
Probe Cable Lead Miniature male coaxial ClickLoc Connects directly to standard extension cable female coaxial ClickLoc connector

Installation Guidelines

Follow standard engineering procedures for installation of reverse mount proximity probes:

  • Insert the probe from the rear of the mounting location or bracket cavity. Thread carefully to avoid cross-threading.
  • Maintain a minimum cable bend radius of 25.4 mm (1.0 in) to prevent internal shield degradation.
  • Always match total probe length + extension cable length with the specific calibration requirements of the Proximitor sensor (e.g., exactly 5.0 meters or 9.0 meters).
  • Ensure all connector mating surfaces are free of oil and dirt before clicking them closed. Tighten the ClickLoc connectors finger-tight until they click.

Compliance and Certifications

This proximity probe complies with local and international regulatory requirements for industrial machinery safety:

  • NEPSI (National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation) - Certified for hazardous environments in China.
  • CCC (China Compulsory Certification) - Certified for explosion safety.
  • CSA, ATEX, IECEx - Multi-regional approvals for explosive atmospheres (when used with an approved barrier/system).
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 330195-02-12-05-CN 3300 XL ETR Reverse Mount Proximity Probe

What does the -CN suffix represent on this Bently Nevada probe?

The -CN suffix specifies the China hazardous area approval package, certifying the probe under NEPSI and CCC regulations for installation in hazardous industrial zones in China.

How does the 330195-02-12-05-CN probe mount?

This is a reverse mount probe with 3/8-24 UNF-2A threads, meaning it is threaded from the rear of the mounting hole rather than the front, which is ideal for tight internal machinery housings.

What is the operating temperature limit for this ETR probe?

The Extended Temperature Range (ETR) rating allows this probe to operate in environments up to 218 degC (425 degF), whereas standard 3300 XL probes are limited to 177 degC (350 degF).

Which Proximitor Sensor should I use with the 330195-02-12-05-CN probe?

This probe has a 0.5-meter total length. It must be paired with an extension cable so that the combined length of the probe and cable matches the calibration of the 3300 XL Proximitor Sensor, typically 5.0 meters or 9.0 meters.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Amerika Serikat

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Elektrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan untuk Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...