1 dari 1

Honeywell 51304638-175 MU-T Series Nonredundant Analog Output Module

Honeywell 51304638-175 MU-T Series Nonredundant Analog Output Module

Hanya 7 item tersisa di stok
  • Produsen: Honeywell

  • Nomor Produk: 51304638-175

  • Negara asal:Amerika Serikat

  • Jenis Produk: Analog Output Modules

  • Pembayaran: T/T, Western Union

  • Berat: 2000g

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Kuantitas
Lihat detail lengkap

Description

Interfacing control system processing electronics with field-level loop devices, the Honeywell 51304638-175 functions as a reliable, nonredundant Analog Output FTA (Field Termination Assembly). Also identified under model code MC-GAOX02, this unit facilitates the distribution of analog control signals from the controller to final control elements such as valves, actuators, and positioners in industrial process environments.

This Field Termination Assembly features 8 individual, galvanically isolated channels designed to prevent electrical interference between loops. The module integrates compression terminal connections, allowing for direct-wire terminations without the need for additional terminal strips. To ensure reliability in corrosive or damp processing environments, the assembly's printed circuit board is conformally coated, offering standard protection against dust, humidity, and chemical contaminants.

Features

  • Provides 8 nonredundant, galvanically isolated analog output channels.
  • Supports standard 4-20mA current loop configurations.
  • Equipped with high-reliability compression terminals for secure field connections.
  • Conformally coated PCB protection for enhanced resistance to harsh environmental conditions.
  • Compatible with standard Honeywell Size B mounting footprint requirements.
  • Designed for simplex loop applications where redundancy is not required.

Applications

  • Process control loop integration in oil and gas refineries.
  • Modulating control valve and actuator positioning in chemical plants.
  • Utility and boiler feed control loops in power generation facilities.
  • Water and wastewater plant dosing and flow control distribution.

Technical Specifications

Manufacturer Honeywell
Part Number/Model 51304638-175 / MC-GAOX02
Series MU-T Series / TDC 3000 Experion Compatibility
Module Type Analog Output Field Termination Assembly (FTA)
Redundancy Support Nonredundant (Simplex)
Output Channels 8 Channels
Signal Range 4-20mA (Galvanically Isolated)
Maximum Load Resistance Less than 750 ohms
Terminal Connection Type Compression Terminals
Conformal Coating Yes
Module Size Size B (307 mm / 12.1 in)
Shipping Weight 2.0 kg

Connections and Interfaces

Field wiring connections are terminated directly on the board via the integrated compression screw terminal blocks. Each of the 8 loop channels occupies dedicated positive and negative terminals to support isolated loop-powered or externally powered 4-20mA control loops.

Installation Guidelines

  • Mounting: Mount the module securely onto compatible Size B mounting channels or standoffs inside an industrial enclosure.
  • Wiring: Use shielded twisted-pair cabling for all 4-20mA loops to minimize electromagnetic interference. Terminate shields according to system engineering specifications, typically grounding at the cabinet side only.
  • Thermal Management: Maintain adequate vertical ventilation spacing between FTAs inside the termination cabinet to prevent localized heat accumulation.
  • Handling: Standard ESD precautions must be observed during handling, installation, and field wiring activities to protect internal components.

Compliance and Certifications

  • CE Compliant
Loading product navigation…

What is the primary function of the Honeywell 51304638-175 module?

The Honeywell 51304638-175 is a nonredundant Analog Output Field Termination Assembly (FTA) used to interface system controller cards with field devices such as control valves and actuators using 4-20mA signals.

How many channels does the MC-GAOX02 assembly support?

The assembly supports 8 galvanically isolated analog output channels.

Does this module support redundant control loop architectures?

No, this module is designed for nonredundant (simplex) configurations only.

What is the maximum allowed load resistance for the current loops?

The maximum loop load resistance supported by this module is less than 750 ohms.

Does the module have protection for harsh operating environments?

Yes, this model features conformal coating on the printed circuit board assembly to protect against dust, humidity, and chemical exposure.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian kembali, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Amerika Serikat

Produk yang Baru Dilihat

Pengetahuan teknis

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Dari sistem perekat yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga AI,...

Throwback: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...

Factory I/O: Alat Simulasi PLC Modern untuk Pelatihan Otomasi Industri

Factory I/O mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang imersif untuk siswa, insinyur, dan tim pemeliharaan. Platform ini menjembatani kesenjangan antara teori dan praktik...