Engineered for heavy-duty gas turbine combustion monitoring, the Honeywell LG1093AA44 is an industrial ultraviolet (UV) flame sensor optimized for power generation and compressor applications. Utilizing a specialized Geiger-Mueller type sensor phototube, this unit is designed to detect the UV radiation emitted by hydrocarbon flames while remaining completely solar-blind and highly tolerant to black-body radiation. Proven over decades of deployment on General Electric and GE-licensee gas turbines, this sensor interfaces seamlessly with EG1033 series amplifiers to provide critical flame status feedback to your turbine control system.

Features

  • Highly Sensitive Phototube: Specifically tuned to target the 180 to 260 nm UV spectrum for reliable flame detection.
  • Solar Blind Design: Prevents false positive readings from sunlight, infrared emissions, or surrounding high-temperature black-body radiation.
  • Integrated Shielded Cable: Includes a 16-foot (4.9 m) Teflon-shielded cable with a 1-inch external conduit thread for structural protection in harsh environments.
  • Pressure-Resistant Optics: Built-in optical viewing window rated for system pressures up to 10 bar (150 psi).
  • Explosive Atmosphere Approvals: Certified for Zone 1 and Zone 2 environments (ATEX EEx d IIC T3) and Class I, Division 1 and 2 hazard areas.

Applications

  • General Electric (GE) and GE-licensee industrial gas turbines.
  • Turbine-driven compressor stations in gas pipeline transmission.
  • Utility-scale power generation combustion monitoring systems.
  • Hazardous-area industrial burners and combustion processes.

Technical Specifications

Specification Parameter Value / Rating
Manufacturer Honeywell
Model/Part Number LG1093AA44
Sensor Type Geiger-Mueller UV Phototube
Spectral Detection Range 180 to 260 nm
Flame Present Response Time 0.1 seconds (typical)
Flame Loss Response Time 0.2 seconds (maximum)
Operating Temperature Range -40 to 176 degC
Integrated Cable Length 16 feet (4.9 meters)
Cable Shielding Type Teflon shielded with 1-inch external conduit thread
Mechanical Connection 3/4 inch internal NPT
Window Pressure Rating 10 bar (150 psi)
System Interface EG1033 Series Amplifiers (EG1033AA / AB / AC)
Maximum Loop Distance Up to 330 meters (1000 feet) from sensor to amplifier
Hazardous Approvals ATEX (EEx d IIC T3, Zone 1 & 2), FM (Class I, Div 1/2, Groups B, C, D)
Shipping Weight (Calculated) 3.0 kg

Empirical Engineering Insights

Alternative Models & Compatibility

The LG1093AA44 is designed exclusively to interface with Honeywell EG1033 amplifier modules. It is highly recommended to verify whether your specific turbine control application requires the transistor open-collector output of the EG1033AA or the SPDT relay contacts of the EG1033AB/AC units, as the sensor's baseline signal output is passive and requires active amplification to integrate with your PLCs or safety instrumented systems.

Application Pitfalls & Engineering Notes

CRITICAL APPLICATION EXCLUSION: The standard Honeywell LG1093 series, including this LG1093AA44 model, will not reliably operate on Dry Low NOx (DLE) gas turbines (such as GE/NP DLE configurations). DLE turbines require specialized, pre-selected sensors with alternative spectral thresholds. Attempting to use a standard LG1093 sensor in DLE environments will lead to frequent flame-out false alarms and operational instability.

Commissioning & Wiring Tips

When routing the integrated 16-foot Teflon-shielded cable, always run the conduit separate from high-voltage motor starters, ignition cables, or high-frequency variable speed drives (VSDs). Electromagnetic coupling on the sensor signal line can distort the high-impedance pulse signals generated by the Geiger-Mueller phototube, resulting in false flame-present signals during startup phases.

Installation Guidelines

CRITICAL WARNING: HIGH-VOLTAGE & SYSTEM COUPLING

Before removing or replacing an existing flame sensor, verify that the turbine is fully shutdown and de-energized. High voltages are present on the sensor lines when connected to active EG1033 amplifiers. Ensure the mounting sight pipe has cooled completely and that system pressure is depressurized below 10 bar before extraction.

1
Inspect the optical viewing window on the LG1093AA44 for physical scratches, oil film, or debris. Clean only with optical-grade solvent if necessary.
2
Apply high-temperature, anti-seize compound to the 3/4 inch NPT threads. Screw the sensor securely into the mounting port on the turbine casing, ensuring a gas-tight seal.
3
Route the 16-foot Teflon integrated cable through a continuous 1-inch rigid or flexible conduit. Connect the shield line to the dedicated instrumentation ground terminal inside the local junction box.
Loading product navigation…

Can the LG1093AA44 sensor be deployed on Dry Low NOx (DLE) gas turbines?

No. The standard LG1093AA44 is not compatible with DLE turbines due to alternative combustion physics. It will result in false alarms and unstable performance. DLE applications require pre-selected OEM parts.

What is the maximum cable distance allowed from the sensor to the EG1033 amplifier?

The maximum recommended distance between the Honeywell LG1093AA44 sensor and its matched EG1033 amplifier is 330 meters (1000 feet).

Is the integrated cable on the LG1093AA44 replaceable in the field?

No. The 16-foot Teflon-shielded cable is sealed into the sensor body at the factory to maintain the physical pressure seal and environmental ingress ratings.

What spectral range is this Honeywell phototube sensitive to?

The sensor uses a Geiger-Mueller tube that is highly sensitive to ultraviolet (UV) radiation in the 180 to 260 nm range, ensuring it remains blind to sunlight and black-body heat.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian kembali, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Amerika Serikat

Produk yang Baru Dilihat

Pengetahuan teknis

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Dari sistem perekat yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga AI,...

Throwback: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...

Factory I/O: Alat Simulasi PLC Modern untuk Pelatihan Otomasi Industri

Factory I/O mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang imersif untuk siswa, insinyur, dan tim pemeliharaan. Platform ini menjembatani kesenjangan antara teori dan praktik...