1 of 3

General Electric Mark VIe IS420UCSBH1A UCSB Controller Module

General Electric Mark VIe IS420UCSBH1A UCSB Controller Module

Only 7 item(s) left in stock
  • Manufacturer: General Electric

  • Product No.: IS420UCSBH1A

  • Country of origin:United States

  • Product Type: UCSB Controller Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 1520g

  • Dimensions: 5.5cm x 12.3cm x 20.3cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The IS420UCSBH1A is a single-module industrial control processor developed by General Electric for the Mark VIe Control Safety System Series. Operating with the functional abbreviation UCSB, this hardware acts as the first generation of UCSB-type standalone control units executing real-world application logic for infrastructure and power plant applications. The IS420UCSBH1A is dynamically engineered with native configuration maps that allow it to function interchangeably as a primary controller within Mark VIe, EX2100e excitation control, and LS2100e static starter systems. Built around an embedded 600 MHz Intel EP80579 microprocessor, the module processes complex turbine application logic and controls communication interfaces without requiring a system backup battery or an integrated mechanical cooling fan assembly. It runs an operating software platform nearly identical to the subsequent UCSC series to maintain firmware compliance and configuration consistency across multi-generation system lifecycles.

Features

  • Integrated 600 MHz EP80579 Intel industrial microprocessor for consistent, deterministic processing loop execution.
  • Solid-state hardware design completely eliminates internal cooling fans and volatile backup battery requirements.
  • Multi-platform multi-purpose identity certified for Mark VIe, EX2100e, and LS2100e control architectures.
  • Compatible operating system structure delivering nearly identical application logic execution as the UCSC system controllers.
  • Certified for secure installation in both standard non-hazardous operating environments and Class I, Division 2 locations.

Applications

  • Gas, steam, and hydro turbine control systems within the Speedtronic product family.
  • EX2100e generator excitation control loop management.
  • LS2100e Static Starter control system logic execution.
  • Hazardous area process automation requiring Class I, Zone 2 or Division 2 safety standards.

Technical Specifications

Parameter Specification Value
Manufacturer General Electric (GE)
Model/Part Number IS420UCSBH1A
Functional Abbreviation UCSB
System Series Compatibility Mark VIe Control Safety System, EX2100e, LS2100e
Microprocessor Type Intel EP80579 (600 MHz clock speed)
Minimum Control Voltage 18 VDC
Nominal Power Supply Ratings 24 VDC / 28 VDC
Maximum Control Voltage 30 VDC
Maximum Current Rating 1.5 ADC
Ambient Operating Temperature Range -22 to 149 degF (-30 to 65 Celsius)
Cooling Mechanism Natural Convection (Fanless Architecture)
Manual Reference Guide GEH-6725 / GEH-6721
Country of Origin United States

Compliance and Certifications

Location Type Certification / Listing Agency Codes
ATEX Zone 2, Group IIC UL DEMKO 12 ATEX 1114875X
Class I, Zone 2, Group IIC UL E207685
Class I, Division 2, Groups A, B, C, D UL E207685
Non-Hazardous Locations UL E207685

Installation Guidelines

CRITICAL WARNING:

De-energize all secondary power distribution networks before inserting or disconnecting this module. Live maintenance in ATEX Zone 2 environments can trigger volatile ignition or cause permanent circuit damage to the processor base board.

1

Ensure proper cabinet clearance for passive vertical convection cooling. Air passage lanes around the chassis must remain unblocked by adjacent hardware assemblies.

2

Confirm the primary control voltage supply lines are conditioned within the structural operational envelope of 18 VDC to 30 VDC.

3

Verify structural grounding pads comply strictly with hazardous deployment guidelines detailed inside GEH-6725 documentation before starting system initialization sequences.

What is the recommended input voltage window for the controller?

The module requires a minimum control potential of 18 VDC and can accept up to a maximum of 30 VDC, with standard nominal ratings placed at 24 VDC and 28 VDC.

Does this controller model require an external cooling fan or internal battery?

No. The hardware is completely fanless and utilizes a battery-less design, depending entirely on natural convection through vertical cabinet orientation for thermal dissipation.

Is the controller compatible with system lines other than the Mark VIe?

Yes. This universal single module is labeled and fully authorized for deployment across Mark VIe, EX2100e excitation control, and LS2100e static starter control loops.

What specific safety classification numbers apply to its hazardous area usage?

It holds UL DEMKO 12 ATEX 1114875X for ATEX Zone 2 (Group IIC) environments, alongside UL E207685 covering Class I, Zone 2, Group IIC, and Class I, Division 2 (Groups A, B, C, D).

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Black
Country of origin
United States
Power source
DC Power

Recently Viewed Products

Technical knowledge

OpenVMS Alpha жүйесінде жұмыс істейтін Bailey INFI 90 Symphony HMI-лерін жаңарту

OpenVMS Alpha жүйесінде жұмыс істейтін ескірген Bailey Symphony операторлық станцияларын ауыстыруға арналған практикалық нұсқаулық. Ол Alpha эмуляциясын, OpenVMS x86-ға көшіруді, OPC қайта...

Өнеркәсіптік сенімділік үшін техникалық қызмет көрсету деректері неге маңызды

Техникалық қызмет көрсету деректері жұмыс тапсырыстарын, сенсор сигналдарын, активтердің тарихын, шығындарды және техник мамандардың білімін байланыстырады. Оны дұрыс қолдану жоспарлауды,...

Сұйықтық қуат жүйелерін ауыстыруға арналған электрлік актуаторлар: Практикалық өнеркәсіптік автоматтандыру нұсқаулығы

Бұл мақала SMC компаниясының e-Actuator сериясы сияқты біріктірілген электрлік актюаторлардың дәстүрлі пневматикалық және гидравликалық жүйелерді ауыстыра отырып, өнеркәсіптік қозғалысты басқаруды...

Өнеркәсіптік автоматтандыру қолданбалары үшін OpenPLC көмегімен математикалық операциялар

Бұл мақалада PLC жүйелерінің өнеркәсіптік автоматтандыруда қосу, алу, көбейту, бөлу, модуль және дәрежелеу сияқты негізгі математикалық операцияларды қалай орындайтыны түсіндіріледі. Онда осы функция...

FBD PLC бағдарламалауындағы жетілдірілген булев логика: Негізгі логикадан тыс практикалық өнеркәсіптік қолданбалар

Мақалада PLC бағдарламалауында негізгі AND, OR және NOT операцияларынан тыс қолданылатын бірнеше күрделі Булев логика функциялары түсіндіріледі. Онда шындық кестелері, мультиплексорлар, импульс...

PLC бағдарламалаудағы логикалық операторлар: FBD логикалық қақпаларын түсіну

Булев логика әрбір ПЛК бағдарламасының негізі болып табылады. Қарапайым машина басқару жүйелерінен күрделі өнеркәсіптік автоматтандыру жүйелеріне дейін, логикалық қақпалар контроллерлердің өзгеретін...