Description

Optimized for space-constrained, decentralized automation architectures, the Beckhoff EPP2817-0008 provides a high-density digital output interface directly in the field without requiring an electrical enclosure. This ruggedized EtherCAT P Box module incorporates 24 digital outputs in a single housing, utilizing a compact 25-pin D-sub interface to distribute power to actuators, contactors, and indicators. By utilizing EtherCAT P technology, the unit integrates ultra-high-speed data transmission and dual 24 V DC power supplies (US for control voltage and UP for peripheral load voltage) into a single, standardized P-coded M8 connection, dramatically reducing cabling complexity, weight, and installation footprints.

Key Features

  • High Density I/O: 24 digital outputs packed into a highly compact, IP67-rated form factor.
  • One-Cable Automation: EtherCAT P technology combines communication and system/load power into one P-coded M8 line.
  • Short-Circuit Protection: Each channel is individually protected against short circuits, limit-tested at 1.0 A maximum peak current.
  • Integrated Diagnostics: Dedicated hardware monitoring detects undervoltage conditions below 18 V DC for both US and UP supply lines.
  • Distributed Clocks: Native EtherCAT Distributed Clocks support ensures precise output synchronization with fast switching dynamics.
  • Severe Environment Protection: Fully encapsulated IP65, IP66, and IP67 protection classes make the module resistant to dust, moisture, and high-pressure washdowns.

Industrial Applications

  • Modular assembly machinery and robotic end-of-arm tooling.
  • Decentralized conveyor systems, sorting systems, and material handling lines.
  • Packaging machinery requiring distributed valve terminal and actuator controls.
  • Automotive assembly lines and tooling systems exposed to high vibration.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Reference EPP2817-0008
Communication Protocol EtherCAT P
Bus Interface 2 x M8 socket, shielded, screw type, P-coded (Upstream/Downstream)
Number of Digital Outputs 24
Output Connection Type D-sub socket, 25-pin, UNC4-40 mounting thread
Permissible Load Types Ohmic (resistive), inductive, lamp load
Nominal Output Voltage 24 V DC (-15% / +20%)
Maximum Output Current 0.5 A per channel (short-circuit proof), 3.0 A cumulative sum max
Switching Execution Speed Typical Turn-on (TON): 10 us | Typical Turn-off (TOFF): 50 us
Short-Circuit Current Limit Maximum 1.0 A peak per channel
Current Consumption (from US) Typical 100 mA
Auxiliary Power Current (from UP) Typical 20 mA + connected load current
Electrical Isolation 500 V RMS (test voltage)
Operating Temperature Range -25 to +60 degC
Storage Temperature Range -40 to +85 degC
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity and Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Environmental Protection Rating IP65 / IP66 / IP67 (conforms to EN 60529)
Standards and Approvals CE, UL
Net Weight 0.165 kg (approx. 165 g)
Shipping Weight (Calculated) 0.500 kg

Connections and Interfaces

Connector Port Physical Type Functional Assignment
EtherCAT P Input M8, 4-pin socket, P-coded Incoming EtherCAT communication, US system/sensor power, UP load/actuator power
EtherCAT P Output M8, 4-pin socket, P-coded Outgoing EtherCAT communication and power daisy-chain to downstream EPP modules
Digital Outputs (1 to 24) 25-pin D-sub socket, UNC4-40 Pin 1 to 24: Digital Output Channels | Pin 25: Common Ground (GND)

Alternative Models and Compatibility

The EPP2817-0008 represents the advanced EtherCAT P single-cable variant of the standard EP2817 multi-cable systems. Note that standard EtherCAT (EP-series, A/D-coded) and EtherCAT P (EPP-series, P-coded) cannot be interconnected directly without an EP9224 or EP9228 power injector/junction box. When planning hardware transitions from legacy layouts, confirm your TwinCAT system manager configurations are updated with the XML device description file (ESI) specifically generated for EtherCAT P modules.

Application Pitfalls and Engineering Notes

While individual outputs are capable of switching a nominal load of 0.5 A, system designers must rigorously observe the cumulative current budget. The maximum total sum current of the module is strictly capped at 3.0 A due to structural thermal constraints within the IP67 housing. Operating the module above this limit will trigger thermal protection and localized shut-downs. Additionally, because inductive loads generate inverse EMF voltage spikes, external freewheeling diodes should be used on high-inductance solenoids to preserve switching life, despite internal clamping protective circuits.

Commissioning and Wiring Tips

To maintain maximum electromagnetic compatibility (EMC) in harsh industrial environments, always use fully shielded 25-pin D-sub mating cables with the outer shield terminated to the metallic D-sub shell backshell. Ensure that the M8 P-coded locking nuts are tightened using a calibrated torque wrench (typically 0.4 Nm) to guarantee the IP67 rating and avoid continuous micro-interruptions in high-vibration applications.

Installation Guidelines

CRITICAL WARNING: Completely de-energize the entire segment of the EtherCAT P network, including both control voltage (US) and peripheral power supply (UP), prior to mating or unmating any electrical connection. Plugging or unplugging the M8 P-coded or 25-pin D-sub connectors under load can result in permanent contact degradation, electrical arcing, and internal component damage.
  1. 1 Mount the module securely on an even mounting surface using M3 bolts through the mounting holes on the top and bottom flanges. Do not exceed 0.8 Nm tightening torque on the mounting bolts.
  2. 2 Connect the shielded 25-pin D-sub actuator wiring cable. Tighten the UNC4-40 retention screws thoroughly to provide correct mechanical strain relief and ensure an IP67 seal.
  3. 3 Thread and secure the incoming EtherCAT P M8 cable (P-coded) from the master controller or previous node to the input port. Torque the M8 ring to 0.4 Nm.
  4. 4 Apply system power and verify link statuses utilizing the integrated LED indicators for EtherCAT link status (L/A) and voltage status (US/UP).
Loading product navigation…

What is the key difference between the EPP2817-0008 and standard EP2817 modules?

The EPP2817-0008 is an EtherCAT P module, which combines EtherCAT communication and power supply (US and UP) into a single M8 P-coded cable, whereas standard EP modules require separate communication and power connections.

How is the total output current restriction of 3 A managed across all 24 channels?

While each individual channel can switch up to 0.5 A, the aggregate sum current of all active channels is limited to 3 A. If all 24 outputs are energized simultaneously, the average continuous current per channel must not exceed 125 mA.

Does this module support Distributed Clocks (DC)?

Yes, the module supports highly precise EtherCAT Distributed Clocks (DC), ensuring synchronized digital outputs with low-jitter switching times down to 10 us (turn-on) and 50 us (turn-off).

What happens if the peripheral voltage drops below standard limits?

The module features dynamic undervoltage monitoring. If either the system/sensor supply voltage (US) or peripheral load voltage (UP) falls below 18 V DC, an undervoltage fault is registered and reported back to the master controller.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...