1 daripada 1

Beckhoff ERI1809-0022 IO-Link Box 16-channel Digital Input Module

Beckhoff ERI1809-0022 IO-Link Box 16-channel Digital Input Module

Hanya 10 item tinggal dalam stok
  • Pengilang: BECKHOFF

  • No. Produk: ERI1809-0022

  • Negara asal:Jerman

  • Jenis Produk: IO-Link Modules

  • Pembayaran: T/T, Western Union

  • Berat: 500g

  • Dimensi: 60 mm x 126 mm x 26.5 mm

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

Directly capturing 16 digital sensor signals from the field, the Beckhoff ERI1809-0022 distributes decentralized I/O data through an integrated IO-Link interface. Built with a robust zinc die-cast housing, this module offers superior mechanical resilience and shielding compared to standard plastic housings, making it suitable for wet, high-vibration, and demanding industrial environments. The device operates as an IO-Link Class A device, transmitting input states to any compatible IO-Link master via a high-speed COM3 interface.

Features

  • 16 Digital Inputs: High-density sensor integration in a single field-mounted block.
  • Zinc Die-Cast Housing: Enhanced mechanical protection, impact resistance, and electromagnetic shielding.
  • IO-Link COM3 Interface: Supports high-speed data transfer rates up to 230.4 kbaud.
  • Adjustable Input Filter: Configurable input filtering from 0 to 20 ms (3 ms default) to prevent signal bounce.
  • Type 3 Input Characteristics: Conforms to EN 61131-2 Type 3 standards, optimizing current draw for modern electronic sensors.
  • IP67 Rated Protection: Fully sealed against dust and water immersion, designed for direct machine mounting without an enclosure.

Applications

  • Decentralized Conveyor Systems: Distributed sensor gathering across extensive logistics layouts.
  • Automotive Assembly Lines: Rugged, weld-spatter-resistant installations requiring high-density digital feedback.
  • Packaging Machinery: Compact field wiring to eliminate centralized junction boxes.
  • Machine Tooling: Wet environments where coolant and metal chips are present.

Technical Specifications

Parameter Value
Manufacturer Beckhoff
Model ERI1809-0022
Communication Protocol IO-Link V1.1, Class A
Data Transfer Rate 230.4 kbaud (COM3)
Number of Inputs 16 digital inputs
Input Voltage Range 24 V DC (-15 percent / +20 percent)
Signal Voltage "0" -3 to +5 V DC (EN 61131-2, Type 3)
Signal Voltage "1" 11 to 30 V DC (EN 61131-2, Type 3)
Input Filter Config 3.0 ms default (adjustable 0 to 20 ms)
Current Consumption Typically 100 mA from L+
Sensor Supply Max. 0.5 A from L+, short-circuit proof
Housing Material Zinc die-cast
Protection Rating IP65 / IP66 / IP67 (conforms to EN 60529)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Dimensions (W x H x D) 60 mm x 126 mm x 26.5 mm
Net Weight 450 g
Shipping Weight (Calculated) 0.65 kg
Country of Origin Germany

Connections and Interfaces

Interface / Port Connector Type Assignment / Function
IO-Link Connection 1 x M12 plug, A-coded L+ (24V DC), L- (0V), IO-Link C/Q line
Digital Inputs (1-16) 8 x M12 sockets (2 inputs per port) Pin 4: Input A, Pin 2: Input B, Pin 1: +24 V DC supply, Pin 3: 0 V GND

Empirical Engineering Insights

Alternative Models & Compatibility

The ERI1809-0022 is the direct zinc die-cast equivalent of the plastic-housed EP1809-0022. Both modules share identical electrical specifications, pin configurations, and firmware registers. If replacing an EP module, the ERI offers identical mount spacing, but features a thicker profile. Ensure adequate depth clearances within your mechanical footprint.

Application Pitfalls & Engineering Notes

Because this is an IO-Link Class A module, both the unit's internal logic and the connected sensor field power are drawn entirely from the primary L+ and L- lines of the IO-Link master port. The total available sensor supply is limited to 0.5 A. Connecting power-hungry inductive sensors or high-current photoeyes can cause the internal short-circuit protection to trip. For configurations exceeding 500 mA, consider utilizing an IO-Link Class B module or an auxiliary power supply distribution block.

Commissioning & Wiring Tips

By default, the digital inputs are configured with a 3.0 ms hardware filter. While effective for typical proximity switches, high-speed applications (such as rotary encoders or flow pulse meters) will require updating the parameter index via the TwinCAT System Manager (or other IO-Link configuration tools) to 0.0 ms. Always utilize shielded M12 cables for runs exceeding 10 meters to prevent high-frequency noise interference from adjacent variable frequency drives.

Installation Guidelines

CRITICAL WARNING: Ensure the entire IO-Link master assembly is fully de-energized before mounting or routing cabling. Never hot-plug M12 input or communication connections while field power is active to prevent transient arcs and potential damage to internal IO-Link transceiver ICs.
1

Mount the zinc die-cast housing directly onto a flat, vibration-resistant surface using two M3 screws (3.5 mm holes) or two M4 screws (4.5 mm holes).

2

Connect the primary IO-Link interface using a standard A-coded, shielded M12 cable, ensuring the lock nuts are tightened to 0.6 Nm to maintain the IP67 seal integrity.

3

Map the sensor inputs to the corresponding M12 sockets. Cap any unused sockets with IP67 protective plugs to prevent moisture intrusion.

Loading product navigation…

What is the key physical difference between the ERI1809-0022 and the EP1809-0022?

The ERI1809-0022 features a heavy-duty zinc die-cast housing for enhanced mechanical durability and shielding, whereas the EP1809-0022 uses a plastic housing.

Does this IO-Link box require an external 24V supply connection?

No. The module is a Class A device and draws both internal operating current and its 0.5 A sensor supply directly from the primary IO-Link connection (L+ and L-).

Can I connect two sensors to a single M12 input port?

Yes. Each of the 8 M12 input sockets supports up to 2 digital inputs on Pin 4 (Input A) and Pin 2 (Input B).

How do I configure the digital input filter on this module?

The input filter is adjusted from its default 3.0 ms using CoE parameters or IO-Link device configuration settings within TwinCAT or your preferred PLC engineering environment.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...