1 daripada 1

Omron 3G3MX2-A4030-ZV1 MX2 Series Multi-Function Compact Inverter

Omron 3G3MX2-A4030-ZV1 MX2 Series Multi-Function Compact Inverter

Hanya 6 item tinggal dalam stok
  • Pengilang: Omron

  • No. Produk: 3G3MX2-A4030-ZV1

  • Negara asal:Jepun

  • Jenis Produk: Variable Frequency Drives

  • Pembayaran: T/T, Western Union

  • Berat: 4000g

  • Dimensi: 230 x 180 x 200 mm

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

Designed for highly dynamic and precise motor speed control, the Omron 3G3MX2-A4030-ZV1 compact inverter provides reliable three-phase AC power regulation within the MX2 Series architecture. By integrating PM motor control options and sensorless vector performance, this variable frequency drive delivers 200% starting torque at near-zero speeds, making it highly effective for heavy-duty starting cycles. The unit features built-in safety functions conforming to ISO13849-1 Cat 3 PLd, ensuring safe torque-off (STO) without requiring external contactors. The ZV1 designation marks an enhanced functional version supporting custom program logic and seamless system integration.

Features

  • Dual Rating Support: Dual-specification support for Constant Torque (CT) at 3.0 kW and Variable Torque (VT) applications at 4.0 kW.
  • Advanced Vector Control: High starting torque of 200% at 0.5 Hz under sensorless vector control mode.
  • Integrated Safety: Double safety inputs and an external device monitor (EDM) output for direct safety circuit integration.
  • Internal Logic Engine: Built-in DriveProgramming capabilities allowing localized PLC functionality and custom flow sequences.
  • Robust Connectivity: Standard Modbus-RTU RS-485 port integrated on-board, with option cards for EtherCAT, PROFINET, and DeviceNet.

Applications

  • Material Handling: Dynamic conveyor lines, sorting tables, and high-duty cranes requiring precise position/speed profiles.
  • Pumping and Fluid Control: Centrifugal pumps and air handling systems utilizing energy-saving variable torque operations.
  • Packaging Equipment: High-speed wrapping, sealing, and labeling machinery requiring fast acceleration and deceleration response.
  • Industrial Tooling: Rotating spindle drives and auxiliary axes demanding stable torque retention across varying load states.

Technical Specifications

Parameter Specification Value
Manufacturer Omron
Model Number 3G3MX2-A4030-ZV1
Voltage Class 3-phase 400 V AC Class (380 to 480 VAC, +10% / -15%)
Input Frequency 50/60 Hz (+/- 5%)
Max Motor Capacity (Constant Torque) 3.0 kW
Max Motor Capacity (Variable Torque) 4.0 kW
Rated Output Current (CT) 7.2 A
Rated Output Current (VT) 9.2 A
Enclosure Rating IP20 (Panel-mounting / closed wall)
Control Method Phase-controlled sinusoidal PWM (V/f, Sensorless Vector)
Maximum Output Frequency 400 Hz
Cooling Method Forced-air cooling
Ambient Operating Temperature -10 to +50 degC (no derating)
Country of Origin Japan
Net Weight 1.9 kg
Shipping Weight (Calculated) 4.0 kg
Package Dimensions (Calculated) 230 x 180 x 200 mm

Connections and Interfaces

Terminal Symbol Function / Circuit Assignment
L1, L2, L3 3-Phase AC Main Power Input (380-480 V)
U, V, W 3-Phase Motor Output Connections
+1, + DC Link Reactor External Connection Terminals
B1, B2 Dynamic External Braking Resistor Terminals
S1 to S7 Multi-Function Digital Inputs (Sink/Source selectable)
H, O, OI, L Analog Input Terminals (Voltage Reference / Current Reference / Common)

Alternative Models & Compatibility

This model seamlessly replaces older non-ZV1 units (e.g., standard 3G3MX2-A4030). The ZV1 designation features updated internal firmware that expands logic functions via DriveProgramming. Parameter files are compatible and can be transferred using CX-Drive software version 2.9 or higher, though any custom internal PLC logic should be verified to confirm I/O mapping consistency.

Application Pitfalls & Engineering Notes

When operating at low output frequencies (under 10 Hz) under a high constant torque load, ensure the connected motor is auxiliary-cooled or rated for inverter duty. Standard self-cooled motors cannot dissipate heat adequately at low rotational speeds, risking thermal overload. If installing multiple units side-by-side in a control panel, follow specified spacing guidelines or apply current output derating to prevent localized heat accumulation.

Commissioning & Wiring Tips

For stable analog reference signals, connect a dedicated shielded twisted-pair (STP) cable to terminals O/OI and ground the shield at the drive's control common terminal (L) only. Do not apply external voltage to the safety input terminals GS1 and GS2; these must be routed through dry-contact safety devices. If Modbus RTU interface issues arise, verify that parameter C071 (Communication Speed) matches the master network rate and that a 120-ohm termination resistor is active at the end of the trunk.

Installation Guidelines

CRITICAL WARNING: Hazardous voltage remains stored within the internal DC bus capacitors even after AC mains power has been disconnected. Wait a minimum of 10 minutes for complete capacitor charge dissipation before removing the terminal block covers or performing physical wiring operations.
1 Mount the inverter vertically to a rigid, flat surface within an IP54-rated or appropriate industrial enclosure to prevent dust and moisture exposure.
2 Securely ground the drive's main PE terminal to the primary system ground plane using a low-impedance copper conductor.
3 Connect power cables to the L1, L2, and L3 terminals. Verify that phase voltage corresponds precisely with the nominal 400 V AC specification.
4 Route the motor connection wires from U, V, and W terminals using high-quality shielded motor cable to minimize electromagnetic interference (EMI).
Loading product navigation…

What is the difference between the standard 3G3MX2 and the ZV1 revision?

The ZV1 suffix indicates firmware-level enhancements supporting internal DriveProgramming logic and better stability with modern digital network expansion modules.

Can I use the 3G3MX2-A4030-ZV1 with a single-phase input source?

No. The 400V class MX2 drives are designed strictly for 3-phase AC input. Attempting to run on single-phase supply will trigger an input phase loss fault (E12).

What is the recommended external braking resistor resistance?

The minimum allowed resistance for an external braking resistor connected to B1 and B2 on this 3.0 kW / 400 V drive is 180 ohms. Do not connect lower resistance loads.

How do I clear persistent safety circuit faults on this unit?

Verify that both GS1 and GS2 input channels are closed simultaneously. If they are open or out of sync, the drive disables its power stage and displays safe torque-off (STO) codes.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jepun

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...