Description
The BECKHOFF IP1502-B730 is a high-performance Fieldbus Box designed to count fast digital pulses within Modbus RTU/ASCII networks. Operating directly in harsh industrial environments without a protective control cabinet, this device integrates two 32-bit high-speed counter channels capable of processing input frequencies up to 100 kHz.
The module incorporates two counter inputs, two gate inputs, and two up/down direction switches. This configuration allows flexible pulse processing, direction detection, and counting gate control. Field signals are connected via standard M12 screw-type connectors, while the integrated sensor supply provides short-circuit protected power directly to the connected encoders or proximity sensors.
Communication with the higher-level controller is established using Modbus RTU or ASCII protocols over an RS485 physical interface. Device configuration, including address and baud rate selection, can be performed using local address selection switches or the KS2000 commissioning software. The physical design features a compact polyamide housing with IP65, IP66, and IP67 protection ratings, enabling direct on-machine mounting.
Features
- Dual-channel high-speed counting with 32-bit counter depth per channel.
- Integrated RS485 interface supporting Modbus RTU and Modbus ASCII protocols.
- Selectable baud rates ranging from 150 to 38,400 baud.
- Six total digital inputs configured as two counter inputs, two gate inputs, and two up/down switches.
- Two short-circuit-proof digital outputs/sensor supplies rated at 24 V DC, 0.5 A.
- Direct machine mounting with high protection rating (IP65/66/67).
- B-coded M12 bus interface connection for reliable RS485 communication.
- M8 connections for power feed and downstream distribution.
Applications
- High-speed pulse acquisition from rotary encoders, flow meters, and proximity sensors.
- On-machine part counting, length measurement, and speed tracking in packaging machinery.
- Decentralized signal processing in distributed manufacturing lines without electrical enclosures.
- Integration with PLC systems utilizing Modbus RTU/ASCII communication.
Technical Specifications
General
| Parameter |
Specification |
| Manufacturer |
BECKHOFF |
| Model |
IP1502-B730 |
| Product Type |
Fieldbus Box |
| Housing Material |
Polyamide (PA6) |
| Dimensions (W x H x D) |
30 mm x 175 mm x 26.5 mm |
| Weight |
Approx. 210 g |
| Mounting |
2 x 3.5 mm diameter fixing holes for M3 screws |
Counter and Digital Inputs
| Parameter |
Specification |
| Number of Counter Channels |
2 |
| Counter Depth |
32 bits per channel |
| Input Configuration |
2 counter inputs, 2 gate inputs, 2 up/down switches |
| Maximum Counting Frequency |
100 kHz (2 kHz for up/down switching) |
| Nominal Input Voltage |
24 V DC (-15% / +20%) |
| Signal Voltage "0" |
-3 to +5 V (EN 61131-2, type 2) |
| Signal Voltage "1" |
11 to 30 V (EN 61131-2, type 2) |
| Signal Connection |
M12, screw type |
Electrical and Outputs
| Parameter |
Specification |
| Number of Outputs |
2 x 24 V DC, 0.5 A |
| Sensor Supply |
Max. 0.5 A total, short-circuit proof, sourced from control voltage |
| Control Voltage Supply |
24 V DC (-15% / +20%) |
| Box Current Consumption |
45 mA (excluding sensor current) |
| Power Connection |
Feed: 1 x M8 male (4-pin); Downstream: 1 x M8 female (4-pin) |
| Electrical Isolation |
Control voltage/fieldbus: Yes; Channels/control voltage: No; Between channels: No |
Modbus Communication
| Parameter |
Specification |
| Protocol |
Modbus RTU / Modbus ASCII |
| Bus Interface |
1 x M12 socket, 5-pin, B-coded |
| Baud Rates |
150, 300, 600, 1200, 2400, 4800, 9600, 19,200, 38,400 baud |
| Max. Distance Between Stations |
1200 m (dependent on baud rate) |
| Transmission Medium |
Screened, twisted copper cable 2 x 0.25 mm² (RS485) |
| Bit Width in Process Image |
80 inputs/outputs (2 x 32-bit data, 2 x 8-bit control/status) |
| Configuration Mode |
Address selection switches or KS2000 software |
Environmental and Certifications
| Parameter |
Specification |
| Operating Temperature |
0 to +55 degC |
| Storage Temperature |
-25 to +85 degC |
| Protection Class |
IP65 / IP66 / IP67 (conforms to EN 60529) |
| Vibration/Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Approvals |
CE, UL |
Installation Guidelines
-
De-energize: Prior to starting any installation, wiring, or maintenance work, ensure all power supplies to the module and field devices are fully disconnected.
-
Mounting: Mount the module directly on a flat machine surface using the two 3.5 mm diameter fixing holes. Use M3 screws, tightening them securely to prevent vibration damage.
-
Power Supply Connection: Connect the 24 V DC control voltage feed to the 4-pin M8 male connector. If daisy-chaining power, connect the downstream M8 female connector to the next module. Verify polarity before energizing.
-
Fieldbus Wiring: Connect the Modbus RS485 communication line to the B-coded M12 5-pin socket. Ensure proper termination is applied at both ends of the bus segment.
-
Sensor and Signal Wiring: Connect the sensors to the M12 screw-type input connectors. Ensure that the total current drawn by the connected sensors does not exceed 0.5 A.
-
Configuration: Set the appropriate Modbus node address using the integrated address selection switches, or configure the communication parameters using the KS2000 software.