Description
The BECKHOFF KL5121 is an incremental encoder interface with programmable outputs, operating as a Bus Terminal within the BECKHOFF K-bus system. It is designed for the direct connection of an incremental encoder with 24 V DC signals (including A, B, latch, and gate inputs) and features four integrated 24 V DC digital outputs. This combination allows the terminal to function as an electronic camshaft controller, executing high-speed switching operations based on the encoder position directly in the hardware, bypassing fieldbus cycle delays.
The terminal features a 16-bit binary counter and supports a limit frequency of up to 1,000,000 increments per second with 4-fold evaluation. The four fast programmable outputs supply up to 0.5 A of output current each, with response times under 100 microseconds. This configuration makes it highly suitable for applications requiring rapid position-based actions without relying on controller-level scan cycles.
Features
- 1-channel incremental encoder interface for 24 V DC signals (A, B, latch, and gate inputs).
- Four integrated fast programmable digital outputs (24 V DC, 0.5 A) acting as an electronic camshaft controller.
- High-speed hardware-level switching under 100 microseconds, independent of the K-bus cycle time.
- 16-bit binary counter with up to 1,000,000 increments/s limit frequency using 4-fold evaluation.
- Standard K-bus system integration for compatibility with BECKHOFF Bus Couplers.
- Compact, DIN-rail-mountable housing with IP20 protection.
Applications
- Electronic camshaft control in packaging and high-speed processing machinery.
- Fast position-based switching and sorting systems.
- Rotary axis position monitoring and boundary limit detection.
- Synchronized material cutting and dispensing systems.
Technical Specifications
| Parameter |
Specification |
| Manufacturer |
BECKHOFF |
| Model |
KL5121 |
| Product Type |
Bus Terminal (K-Bus) |
| Number of Channels |
1 incremental encoder channel, 4 digital outputs |
| Encoder Connection |
A, B, latch, gate |
| Encoder Operating Voltage |
24 V DC |
| Counter |
16-bit binary |
| Limit Frequency |
1,000,000 increments/s (with 4-fold evaluation) |
| Output Voltage |
24 V DC |
| Output Current |
0.5 A per channel |
| Switching Times |
< 100 microseconds |
| Power Supply |
24 V DC (-15% / +20%) |
| Current Consumption (Power Contacts) |
typ. 30 mA + load |
| Current Consumption (K-Bus) |
typ. 60 mA |
| Bit Width in Process Image |
2 x 16-bit data, 2 x 8-bit control/status |
| Special Features |
Electronic camshaft controller |
| Weight |
approx. 60 g |
| Operating Temperature |
0 to +55 degC |
| Storage Temperature |
-25 to +85 degC |
| Relative Humidity |
95%, non-condensing |
| Vibration/Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Protection Rating |
IP20 |
| Ex Markings |
ATEX: II 3 G Ex nA IIC T4 Gc; IECEx: Ex ec IIC T4 Gc |
| Approvals |
CE, UL, ATEX, IECEx |
Installation Guidelines
- Ensure the system is completely de-energized before mounting, wiring, or removing the KL5121 terminal to prevent electrical damage or personal injury.
- Verify that the terminal model matches your system specification and configuration requirements.
- Fit the terminal onto a standard 35 mm DIN rail (EN 60715) by snapping it firmly into position alongside other K-bus terminals.
- Establish reliable power-contact connections by aligning the terminal side contacts with neighboring units.
- Wire the 24 V DC incremental encoder inputs (A, B, latch, gate) and the four programmable outputs using appropriate conductor sizes, implementing shielding where necessary to minimize high-frequency interference.
- Perform a commissioning check to verify process image mapped inputs and test output switching times within your PLC or control software.
Replacement Recommendations
When replacing a BECKHOFF KL5121, record the physical wiring assignments and power connections. Since configuration settings for the electronic camshaft thresholds and encoder parameters are typically handled via the master controller (K-bus coupler and PLC program), ensure that the replacement unit matches the existing process image mapping. Keep the system completely powered down during the hardware swap.