Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap
Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.
Manufacturer: BECKHOFF
Product No.: KS6811
Country of origin:Germany
Product Type: Bus Terminals
Payment: T/T, Western Union
Weight: 80g
Dimensions: 15 mm x 100 mm x 70 mm
Shipping port: Xiamen
Warranty: 12 months
The BECKHOFF KS6811 is a specialized single-channel DALI/DSI master Bus Terminal designed to integrate digital lighting control interfaces directly into standard Beckhoff I/O networks. This terminal serves as an intelligent bridge, enabling bidirectional communication between a central automation controller and lighting components such as electronic ballasts, dimmers, and control gears. It features a pluggable wiring design that simplifies field installation, maintenance, and system upgrades by allowing the wiring block to be removed as a single unit without disconnecting individual conductors.
The KS6811 terminal features a built-in DALI power supply capable of delivering up to 130 mA, which simplifies installation by removing the need for an external bus power source in standard layouts. With a process image of 3 bytes of input and 3 bytes of output data, the terminal provides the communication throughput required for complex lighting commands, dimming curves, and status diagnostics. It operates as a master controller, supporting up to 64 DALI slaves and up to 16 groups, ensuring flexible network layouts in professional lighting automation.
| Parameter | Specification |
| Manufacturer | BECKHOFF |
| Exact Model | KS6811 |
| Product Type | Bus Terminal (Pluggable Wiring Level) |
| Signal/Technology | DALI/DSI Master |
| Number of Channels | 1 |
| Data Transfer Rate | 1200 baud |
| Process Image Bit Width | Input: 3 bytes; Output: 3 bytes |
| Parameter | Specification |
| Nominal Voltage | 24 V DC (-15% / +20%) |
| Input Voltage | 24 V DC (-15% / +20%) |
| Current Consumption (K-bus) | Typically 55 mA |
| Current Consumption (Power Contacts) | Typically 30 mA + load |
| DALI Power Supply | Maximum 130 mA (open-circuit voltage 11.5 V to 15 V DC) |
| Electrical Isolation | 500 V (K-bus / DALI-bus) |
| Insulation Voltage (DALI-bus to K-bus) | 1,500 V DC |
| Insulation Voltage (DALI-bus to Power Contacts) | 1,500 V DC |
| Surge Voltage Resistance | Constant load 275 V AC rms |
| Current Load Power Contacts | Maximum 10 A |
| Parameter | Specification |
| Dimensions (W x H x D) | 15 mm x 100 mm x 70 mm |
| Weight | Approximately 80 g |
| Wiring Technology | Solid, flexible, or ferruled conductors; spring actuation via screwdriver |
| Connection Cross-Section (Solid/Stranded) | 0.08 mm² to 1.5 mm² (AWG 28 to 16) |
| Connection Cross-Section (Flexible) | 0.14 mm² to 1.5 mm² (AWG 26 to 16) |
| Stripping Length | 9 mm to 10 mm |
| Mounting | 35 mm DIN rail (EN 60715) with lock |
| Side-by-Side Mounting | Double slot and key connection |
| Housing Material | Polycarbonate |
| Parameter | Specification |
| Operating Temperature | 0 to +55 degC |
| Storage Temperature | -25 to +85 degC |
| Relative Humidity | 95%, no condensation |
| Vibration/Shock Resistance | Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission | Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Protection Rating | IP20 (variable installation position) |
| Approvals and Markings | CE, cULus, ATEX |
| Ex Marking | II 3 G Ex nA IIC T4 Gc |
Global Express Shipping
Returns & Warranty

Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Country of origin |