Bently Nevada

Bently Nevada 126599-01 3500/44M Aero GT I/O Module

SKU 126599-01

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Bently Nevada

  • Product No.: 126599-01

  • Country of origin:United States

  • Product Type: Aero GT I/O Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 2.3cm x 11cm x 24.1cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The 126599-01 is an Aero GT I/O module with internal terminations manufactured by Bently Nevada for the 3500/44M Aeroderivitive GT Vibration Monitor. Installed in a full-height rear slot of a 3500 rack, the 126599-01 accepts input signals from interface modules (part numbers 86517 and 86497), Velomitors, and accelerometers to monitor aeroderivative gas turbine machinery. The module operates in conjunction with the 3500/44M main monitor module, accepting inputs from two separate Keyphasor signals and routing signals for 1X vibration tracking, band-pass vibration, and signal integration. It includes internal termination connections for transducer inputs, recorder outputs, and inhibit controls.

Features

  • Full-height rear I/O module with internal termination wiring headers
  • Interfaces with interface modules (PN 86517 and 86497), Velomitors, and accelerometers
  • Routes input signals for aeroderivative gas turbine monitoring applications
  • Supports dual Keyphasor signal inputs across channel pairs
  • Connects directly to the 3500/44M Aeroderivitive GT Vibration Monitor main board via the rack backplane

Applications

  • Aeroderivative gas turbine vibration monitoring
  • Machinery protection and automated alarm trip systems
  • Industrial gas turbine condition monitoring loops

Ordering Information

Part Number / Option Description
3500/44-AA-BB Aeroderivative Monitor
A: I/O Module Type  
01 Aero GT I/O Module with Internal Terminations
02 Aero GT I/O Module with External Terminations
05 Prox/Velom I/O Module with Internal Terminations
06 Prox/Velom I/O Module with External Terminations
07 Multimode Prox/Velom I/O Module with Internal Terminations
08 Multimode Prox/Velom I/O Module with External Terminations
B: Hazardous Area Approval Option  
00 None
01 cNRTLus (Class 1, Division 2)
02 ATEX/IECEx/CSA (Class 1, Zone 2)
Spares & Components  
126599-01 Aero GT I/O Module Internal Terminations
143490-01 3500/44M Aeroderivitive GT Vibration Monitor
143491-01 3500/44M Aeroderivitive GT Vibration Monitor User Guide
140471-01 Prox/Velom I/O Module with Internal Terminations
140482-01 Prox/Velom I/O Module with External Terminations
169459-01 Multimode Prox/Velom I/O Module with Internal Terminations
169459-02 Multimode Prox/Velom I/O Module with External Terminations
00580434 Euro Style connector header, 8 pin, Green
00580432 Euro Style connector header, 10 pin, Green
00561941 Prox/Velom and Multimode Prox/Velom I/O Module ten-pin connector shunt
166M2389 Connector Header Push-in-Spring Type (Alternative for PN 00580434)
166M2388 Connector Header Push-in-Spring Type (Alternative for PN 00580432)

Technical Specifications

Parameter Specification
Manufacturer Bently Nevada
Product Type Aero GT I/O Module with Internal Terminations
Input Signal Capacity Accepts 1 to 4 signals from interface modules (86517, 86497), Velomitors, and accelerometers
Input Impedance Greater than 95 kOhm (Proximitor and acceleration inputs)
Transducer Power Supply -23 Vdc nominal at 43 mA max
Recorder Voltage Compliance +4 to +20 mA (Output proportional to monitor full-scale; load resistance 0 to 600 Ohm, +12 Vdc range across load)
Rack Space Requirement 1 full-height rear slot
I/O Module Dimensions (H x W x D) 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
I/O Module Weight 0.45 kg (1.0 lb)

Connections/Interfaces

Connector Pin Function
PWR + Transducer Power Positive
PWR - Transducer Power Negative
SHLD Transducer Shield
COM Common
CH1 - CH4 Channel 1 through Channel 4 Transducer Inputs
INHB Inhibit Input
RET Return
REC1 - REC4 Recorder Outputs 1 through 4
SHIELD System Ground / Shield Connection

Installation Guidelines

  • Install the module into the full-height rear slot directly behind the 3500/44M main monitor board.
  • Secure field transducer and recorder wiring using compatible Euro-style connector headers or push-in spring terminal connectors.
  • Connect channel shield wires to the designated SHLD terminals on the I/O block.
  • Ensure proper insertion and torque on rear panel retaining screws to secure backplane ground connection.

Compliance and Certifications

  • FCC: Complies with part 15 of the FCC Rules
  • EMC: European Community Directive 2014/30/EU; Standards EN 61000-6-2, EN 61000-6-4
  • Electrical Safety: European Community Directive LV Directive 2014/35/EU; Standard EN 61010-1
  • RoHS: European Community Directive ROHS Directive 2011/65/EU
  • Maritime: DNV GL rules for classification; ABS Rules for Condition of Classification (Part 1, Steel Vessels Rules, Offshore Units and Structures)
  • cNRTLus (Without Internal Barriers): Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc; Class I, Division 2, Groups A, B, C, and D; T4 @ Ta = -20 degC to +65 degC (-4 degF to +149 degF)
  • cNRTLus (With Internal Barriers): Class I, Zone 2: AEx/Ex nA nC ic [ia Ga] IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic [ia Ga] IIC T4 Gc; Class I, Division 2, Groups A, B, C, and D (W/ IS Output for Division 1); T4 @ Ta = -20 degC to +65 degC (-4 degF to +149 degF)
  • ATEX/IECEx (Without Internal Barriers): Ex II 3 G; Ex nA nC ic IIC T4 Gc; Ex ec nC ic IIC T4 Gc; T4 @ Ta = -20 degC to +65 degC (-4 degF to +149 degF)
  • ATEX/IECEx (With Internal Barriers): Ex II (1) G; Ex nA nC ic [ia Ga] IIC T4 Gc; Ex ec nC ic [ia Ga] IIC T4 Gc; T4 @ Ta = -20 degC to +65 degC (-4 degF to +149 degF)

FAQ

What primary main module is compatible with the device?

It is designed to work as the rear I/O card for the 3500/44M Aeroderivitive GT Vibration Monitor in a 3500 rack.

How many rack slots does the module occupy?

It occupies one full-height rear slot in the 3500 system rack.

What transducer inputs are supported by the module?

It accepts 1 to 4 signals from interface modules (part numbers 86517 and 86497), Velomitors, and accelerometers.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 126599-01 3500/44M Aero GT I/O Module

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 7 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
United States
Power source
DC Power

Technical knowledge

Commissioning AS-Interface Networks Without Guesswork

A practical AS-Interface commissioning method covering topology, power and voltage-drop checks, addressing, PLC mapping, fault tests and maintenance records for reliable actuator-sensor networks.

Selecting Line Reactors and Output Filters for VFDs

Learn how line reactors, harmonic filters, output reactors, dV/dt filters, and sine filters address different VFD power-quality and motor-cable problems—and how to select them safely.

Light-On and Dark-On Photoelectric Sensor Logic

Learn how light-on and dark-on photoelectric sensor modes interact with through-beam, retroreflective, and diffuse sensing, PNP/NPN wiring, PLC logic, commissioning, and fault detection.

Designing H-Bridge Motor Drives Without Shoot-Through

A practical guide to H-bridge motor drives covering switching states, dead time, inductive current paths, PWM choices, protection, PCB layout, PLC interfacing, and staged commissioning tests.

Designing Mitsubishi FX PLC Sequences with STL and RET

Learn how Mitsubishi FX PLC STL and RET instructions structure conveyor and pneumatic sequences, with practical state design, transition logic, timeouts, diagnostics, and safe restart boundaries.

Selecting and Troubleshooting DIN Valve Connectors

A practical guide to selecting, wiring and diagnosing DIN-style valve connectors, including form identification, coil voltage, suppression, polarity, sealing, release-time effects and commissioning...