Bently Nevada

Bently Nevada 177230-01-02-00 Seismic Transmitter

SKU 177230-01-02-00

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Bently Nevada

  • Product No.: 177230-01-02-00

  • Country of origin:United States

  • Product Type: Seismic Transmitter

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 131g

  • Dimensions: 66.0 mm x 25.4 mm x 25.4 mm (H x W x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Bently Nevada 177230-01-02-00 is a simple, loop-powered seismic transmitter designed to integrate vibration monitoring directly into programmable logic controllers (PLCs), distributed control systems (DCS), or SCADA platforms. The 177230-01-02-00 measures overall casing vibration and provides a primary 4 to 20 mA loop-powered output signal proportional to peak vibration, alongside an unbuffered dynamic acceleration signal for detailed diagnostic analysis. Constructed with a 316L stainless steel housing and a ceramic shear sensing element, it delivers continuous vibration monitoring for plant asset condition monitoring and predictive maintenance.

Features

  • Loop-powered 4 to 20 mA current loop interface for direct integration with control systems.
  • Dual-output capability providing both primary 4 to 20 mA proportional signal and unbuffered dynamic voltage output for diagnostic tools.
  • Ceramic shear sensing element design.
  • Hermetically sealed 316L stainless steel body for harsh industrial environments.
  • Integrated self-test functionality and protected electrical interface.
  • Standard 3-pin MIL-C-5015 top electrical connector.

Applications

  • Casing vibration monitoring on industrial rotating machinery
  • Continuous asset protection connected to PLCs, DCS, and SCADA systems
  • Balance-of-plant machinery condition monitoring

Ordering Information

Option Code Option Description
177230 Seismic Transmitter
A: Measurement Range 01: 0-25.4 mm/s (0-1.0 in/s)
B: Frequency 02: 3 Hz to 1 kHz (180 to 60 kcps) peak
C: Approvals 00: No Approvals

Technical Specifications

Category Parameter Specification
Electrical Primary Output Signal 4 to 20 mA Current Loop (Pin A to Pin B)
  Dynamic Acceleration Output

Unbuffered Voltage (Pin C to Pin B reference), $10.2\text{ mV/m/s}^2$ ($100\text{ mV/g}$) $\pm 20\%$

 

  Excitation Voltage 12 to 30 VDC (Current limited to 40 mA)
  Dynamic Output Range $147\text{ m/s}^2$ (15 g) peak
  Dynamic Frequency Response 2.5 Hz to 10 kHz $\pm 10\%$ (150 cpm to $600\text{ kcpm} \pm 10\%$)
  Linearity 1% of Full Scale
  Dynamic Output Bias $2.5\text{ V} \pm 0.1\text{ V}$ (Referenced to Pin B)
  Settling Time Less than 15 seconds within 2% of final value
  Electrical Isolation

Greater than $10^8\text{ ohms}$

 

  Case Breakdown Voltage $600\text{ V}_{\text{rms}}$ with less than 1 mA leakage current
Dynamic Measurement Range 0-25.4 mm/s (0-1.0 in/s)
  Main Loop Frequency Response 3 Hz to 1 kHz $\pm 10\%$ (180 cpm to $60\text{ kcpm} \pm 10\%$) peak
  Mounted Resonant Frequency Greater than 12 kHz
  Transverse Sensitivity Less than 5% of sensitivity
  Sensing Element Type Ceramic / Shear
Mechanical Weight 131 g (4.62 oz), typical
  Height 66.0 mm (2.60 in)
  Hex Diameter 25.4 mm (1.00 in)
  Body Material 316L stainless steel
  Connector Material 3-pin MIL-C-5015, 316L stainless steel
  Mounting Threads 1/4-28 UNF
  Mounting Torque 4 to 7 N-m (35.4 to 62.0 in-lbf)
Environmental Operating Temperature -40 degC to +85 degC (-40 degF to +185 degF)
  Sealing Hermetically sealed
  Relative Humidity To 100% non-submerged
  Shock Survivability $9,810\text{ m/s}^2$ (1,000 g peak) maximum drop test
  Magnetic Field Sensitivity Less than $20\ \mu\text{m/s/gauss}$ peak; Less than $14.7\text{ mm/s}^2\text{/gauss}$ peak

Connections/Interfaces

Connector Pin Function
Pin A 4-20 mA Positive Loop (Positive with reference to Pin B)
Pin B 4-20 mA Loop Return (Negative Loop Return for Pin A and common for Dynamic Signal)
Pin C Dynamic Acceleration Signal (Unbuffered, referenced to Pin B)

Installation Guidelines

  • Mount transducer directly to the machine surface using the provided stud thread adapter to ensure rigid mechanical coupling.
  • Torque the mounting assembly to 4–7 N-m (35.4–62.0 in-lbf).
  • Avoid snapping magnetic bases directly onto the equipment surface, as high transient spikes can damage internal electronics.
  • Ensure the Dynamic Signal Negative (Pin B) is electrically isolated from any ground; grounding this terminal will short the 4–20 mA loop resulting in zero output.

FAQ

What is the primary measurement output of the device?

The primary output is a 4 to 20 mA current loop proportional to peak velocity over the configured range.

What function does Pin C serve on the electrical connector?

Pin C provides an unbuffered dynamic acceleration voltage signal referenced to Pin B for signal analysis.

Why must the signal return terminal remain ungrounded?

Grounding Pin B shorts the 4 to 20 mA loop circuit, causing the transmitter output to fail.

What mounting torque is specified for installation?

The recommended mounting torque is 4 to 7 N-m (35.4 to 62.0 in-lbf).

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 177230-01-02-00 Seismic Transmitter

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 5 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Silver
Country of origin
United States

Technical knowledge

Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks

Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.

AKS 33 vs AKS 3000: Checks Before Replacing a Pressure Transmitter

A field checklist for distinguishing Danfoss 060G2105, 060G1323 and 060G2109 by pressure range, fitting, loop signal and controller scaling.

Diagnosing DeltaV SE5009 Power Problems Before Replacement

A field checklist for separating 24 VDC input, carrier bus, output derating and alarm-contact faults before replacing an Emerson SE5009.

Commissioning Quantum Inputs with the 140XSM00200 Simulator

A controlled commissioning method for using the 140XSM00200 simulator to verify Modicon Quantum input mapping and interlocks before reconnecting field wiring.

Commissioning PLX32-EIP-MBTCP: Subnets, Registers, and RPI

A commissioning checklist for the ProSoft PLX32-EIP-MBTCP covering subnet separation, register contracts, EtherNet/IP timing, failure tests and replacement records.

Diagnosing IC693MDL916 Relay Outputs Before Module Replacement

A field checklist for IC693MDL916 relay commands, terminal blocks, load current, switching rate and contact-side measurements.