The 330101-00-63-10-02-00 is a standard 3300 XL 8 mm proximity probe configured with 0.0 in unthreaded length (Option 00), 6.3 in case length (Option 63), and a 1.0 m total system length (Option 10). This 3/8-24 UNF threaded probe uses a miniature coaxial ClickLoc connector and standard cabling (Option 02) without hazardous area approvals (Option 00), making it suitable for general machinery protection environments where advanced agency certifications are not required.
As a core element of the 3300 XL 8 mm proximity transducer system, this probe provides non-contacting eddy-current displacement measurement for critical rotating machinery. It is designed to interface with 3300 XL Proximitor sensors and extension cables, ensuring linear signal transmission for shaft vibration and axial position monitoring applications.
| Option | Code | Description |
| Orderable Part Number | 330101-00-63-10-02-00 | 3300 XL 8 mm Proximity Probe, 3/8-24 UNF |
| A - Unthreaded Length | 00 | 0.0 in |
| B - Case Length | 63 | 6.3 in |
| C - Total Length | 10 | 1.0 meter |
| D - Connector/Cable | 02 | Miniature coaxial ClickLoc connector, standard cable |
| E - Agency Approval | 00 | Not required |
| Manufacturer | Bently Nevada |
| Part Number | 330101-00-63-10-02-00 |
| System Type | 3300 XL 8 mm Proximity Transducer System |
| Probe Diameter | 8 mm (0.31 in) |
| Thread Size | 3/8-24 UNF-2A |
| Case Length | 6.3 in |
| Unthreaded Length | 0.0 in |
| Total System Length | 1.0 meter |
| Connector Type | Miniature coaxial ClickLoc |
| Cable Type | Standard |
| Hazardous Area Approval | Not required |
Proper installation of the 3300 XL probe requires careful attention to the mounting bracket orientation and probe gap setting. Ensure the probe is mounted securely using the appropriate bracket to prevent vibration-induced signal interference. When routing the coaxial cable, avoid sharp bends and protect the connector from moisture and contaminants. This model does not include armor; use appropriate conduit if the installation environment presents a risk of mechanical damage or abrasion.