Derivative Action in PID Control Without Noise Problems
Learn what derivative action contributes to a PID loop, why it can amplify measurement noise and setpoint changes, and how filtering, sampling, and staged tests make D tuning safer.
Manufacturer: Bently Nevada
Product No.: 330130-080-12-RU
Country of origin:United States
Product Type: 3300 XL Standard Extension Cable
Barcode: 8537101190
Payment: T/T, Western Union
Weight: 140g
Dimensions: 45 mm x 95 mm x 95 mm (H x W x D)
Shipping port: Xiamen
Warranty: 12 months
The 330130-080-12-RU is a 3300 XL standard extension cable designed for integration within 3300 XL 8 mm proximity transducer systems. This specific configuration features an 8.0 meter cable length (Option 080) and utilizes FluidLoc cable with connector protector (Option 12), ensuring environmental protection and durability in critical rotating machinery monitoring environments. The RU suffix denotes the standard unit package for the 3300 XL system.
This extension cable serves as a key component in a complete 3300 XL transducer system, which consists of an 8 mm probe, the extension cable, and a Proximitor sensor. Proper installation requires that the combined length of the probe and extension cable equals the calibrated length of the Proximitor sensor. The ClickLoc connectors provide a secure, low-resistance connection, while the FluidLoc cable construction inhibits fluid ingress through the cable jacket, making it suitable for applications where exposure to liquids or oils may occur.
| Option | Code on This SKU | Description |
|---|---|---|
| Orderable Part Number | 330130-080-12-RU | 3300 XL Standard Extension Cable |
| A - Cable Length | 080 | 8.0 meters (26.2 feet) |
| B - Cable Type/Connector | 12 | FluidLoc cable with connector protector |
| C - Agency Approval | RU | Standard (Not required/No specific hazardous area) |
| Parameter | Specification |
|---|---|
| Manufacturer | Bently Nevada (Baker Hughes) |
| Part Number | 330130-080-12-RU |
| Cable Length | 8.0 meters (26.2 feet) |
| Cable Type | FluidLoc |
| Connector Type | ClickLoc with connector protector |
| Operating Temperature | -52 degC to +177 degC |
| Storage Temperature | -52 degC to +177 degC |
Ensure that the extension cable is routed away from high-voltage cables to prevent electromagnetic interference. When connecting the probe and extension cable, use the provided connector protectors to ensure a robust environmental seal. Tighten connectors to the recommended torque specifications to maintain signal integrity. Verify that the total length of the probe and extension cable matches the requirements of the paired Proximitor sensor before system initialization.
Complies with standard Bently Nevada 3300 XL system specifications for electromagnetic compatibility and hazardous area requirements (verify local site regulations for specific hazardous zone installations).