General Electric

GE Fanuc VersaMax IC200ALG320 Analog Output Module

SKU IC200ALG320

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: General Electric

  • Product No.: IC200ALG320

  • Country of origin:United States

  • Product Type: Analog Output Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 160g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Overview

The IC200ALG320 (IC200-ALG-320) is a high-precision, 4-channel analog output module from the GE VersaMax family. It is designed to provide unipolar voltage signals ranging from 0 to +10 VDC to control proportional valves, variable speed drives, and other actuators in industrial automation systems. Known for its compact footprint and ease of integration, the IC200ALG320 converts digital data from the CPU or Network Interface Unit (NIU) into stable, low-noise analog signals. Its modular design allows for "Hot-Swapping" and easy DIN-rail mounting, making it a reliable choice for decentralized control in HVAC, water treatment, and light manufacturing applications.

Technical Configuration

The module features a 12-bit resolution, ensuring granular control over the output signal. Each of the four channels is independent, although they share a common ground. The VersaMax architecture separates the module electronics from the field wiring via a terminal base (sold separately), which allows for permanent wiring and simplified maintenance. The module includes internal diagnostics to monitor the health of the D/A converters and provides LED status indicators for "OK" and "User Power" to facilitate rapid on-site troubleshooting.

Technical Specifications

Attribute Specification
Model IC200ALG320
Brand GE Fanuc / Emerson
Series VersaMax Analog I/O
Output Type Voltage (Unipolar)
Number of Channels 4
Output Voltage Range 0 to +10 VDC
Resolution 12-bit (0 to 4095 counts)
Accuracy +/- 0.5% of full scale (at 25 deg C)
Update Rate Approx. 4 ms for all 4 channels
External Power Supply 24 VDC (+/- 15%)
Weight Approx. 0.13 kg
Dimensions 11.0 x 6.68 x 2.63 cm

Technical FAQs

Does this module require external power to operate?

Yes. The IC200ALG320 requires an external +24 VDC power supply to drive the analog output circuits. This power is usually supplied through the terminal base. If the "User Power" LED is off, the analog outputs will not function even if the PLC is in Run mode.

What is the "Default" behavior if the PLC stops communicating?

During configuration in Proficy Machine Edition, you can set the "Hold Last State" or "Output Default" behavior. This ensures that if communication is lost, the 0-10V signal either stays at its current value or drops to a safe predefined voltage (usually 0V).

Can I use this module for 4-20mA current loops?

No. The IC200ALG320 is a voltage-only module (0-10V). For current loop applications, you would need the IC200ALG321 (which is the 0-20mA/4-20mA equivalent).


Engineering & Installation Guide

  • Signal Shielding: Analog signals are highly susceptible to electromagnetic interference (EMI). Always use shielded twisted-pair (STP) cabling. The shield should be grounded at the PLC end (the terminal base) and left floating at the actuator end to prevent ground loops.

  • Terminal Base Selection: This module is compatible with several terminal bases, such as the IC200TBT001 (Barrier style) or IC200TBP001 (Spring style). Ensure the base is correctly keyed to the "Analog Output" position to prevent the insertion of a different module type.

  • Load Impedance: Ensure the input impedance of the receiving device (e.g., a VFD) is at least 2 kOhms. Connecting a load with too low an impedance will cause the voltage to drop and may trigger a thermal overload within the module's output stage.

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 3 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Black
Country of origin
United States
Power source
DC Power

Technical knowledge

IC693CPU313 Memory Retention and Expansion Limits Before Replacement

A practical replacement guide for the GE Fanuc IC693CPU313, covering its embedded five-slot architecture, memory backup, firmware-dependent capacity and why it cannot use Series 90-30 expansion racks.

Bently Nevada 3500/40M vs 3500/42M: I/O and Channel Checks Before Replacement

A field-focused comparison of Bently Nevada 3500/40M and 3500/42M monitor inputs, channel-pair configuration, rear I/O options, external termination hardware and firmware checks before replacement.

Allen-Bradley 1746-NR4 RTD Faults: Wiring, Excitation, and Filter Checks

A field checklist for diagnosing Allen-Bradley 1746-NR4 RTD and resistance inputs, including sensor curves, lead compensation, excitation current, filter timing and channel diagnostics.

Replacing an Allen-Bradley 1785-L40B: PLC-5/40 Checks Before Migration

A field-focused checklist for replacing an Allen-Bradley 1785-L40B or planning a PLC-5/40 migration, covering backups, 1771 I/O mapping, DH+/RIO channels, revision risks and commissioning.

Allen-Bradley 1747-SN: RIO Mapping and Link Fault Checks

Replacing an Allen-Bradley 1747-SN scanner? Check SLC 500 logical rack and G-file mapping, link speed, cable termination, COMM/FAULT LEDs and hardware series before blaming the module or changing the...

Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks

Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.