Description

The IS220PDIOH1B functions as a high-integrity Discrete Input/Output (I/O) Module configured for the Speedtronic control architecture within the GE Mark VI product family. This specialized discrete I/O pack acts as an interface layer between complex control loop logic and field-level relay hardware across multi-resource turbine environments. Unlike earlier platform generations optimized primarily for traditional fossil fuel plants, this modular architecture is deployed broadly across wind, steam, and gas turbine automated drive assemblies. The hardware layer features a dual-port Ethernet interface coupled with a local processor and a dedicated data acquisition board, enabling fast local signal parsing. To safeguard trace path reliability against continuous workplace particulate and humidity exposure, the foundational printed circuit board surface is treated with an exhaustive conformal layer.

Features

  • Dual integrated Ethernet ports providing independent network pathway drops.
  • Extensive onboard array of status LEDs for real-time connection, power, and diagnostic monitoring.
  • Full PCB protection via a thin, chemically uniform surface conformal coating.
  • Approved architecture for hazardous location categories when deployed alongside designated accessories.
  • Multi-platform utility spanning wind energy, heavy-duty gas turbine, and steam generation controls.

Applications

  • Wind turbine automated generator and pitch drive assembly loops.
  • Main discrete control interfaces for high-capacity industrial steam turbines.
  • Sequence-of-events tracking and automated safety system switching arrays.

Technical Specifications

Parameter Specification
Manufacturer General Electric Speedtronic
Model IS220PDIOH1B
Product Type Discrete I/O Module (Discrete I/O Pack)
Product Series Mark VI
Nominal Voltage Rating 28.0 VDC
Minimum Voltage Rating 27.4 VDC
Contact Voltage Outputs 32.0 Vdc
Chassis Style Vented
Internal Hardware Local Processor, Data Acquisition Board, 2 Ethernet Ports
Module Width 4.5 in
Module Height 3.5 in
Module Depth 2.25 in
Net Weight Less than 2 lbs
Shipping Weight 2.5 lb

Connections/Interfaces

Connector/Interface Type Function
Ethernet Ports (x2) Dual redundant control network communication pathways
Field Terminals (x24) 24 dedicated field contact points when mated with TDBS or TDBT accessory boards
Positive Terminals Wetting voltage input connection points
Power LED Logic and internal bus power status display
Attn LED Unit maintenance and condition flag warning status
Ethernet LEDs Real-time link verification and data packet transfer feedback

Installation Guidelines

  • Module Seating: Align the modular pack framework carefully over its terminal board pins, applying even downward seating force to ensure a clean electrical connection with accessory boards.
  • Wiring Configurations: Adhere strictly to the defined field wire gauge boundaries and specified screw head terminal torques delineated in the official loop drawings.
  • Terminal Polarities: Maintain precise separation between positive contact-wetting inputs and designated negative connection groups during line termination.
  • Hazardous Environment Verification: Confirm that the surrounding enclosure conforms to Class I, Division 2 or Zone 2 parameters prior to initializing the main 28.0 VDC bus feed.

Compliance and Certifications

  • Class I, Division 2, Groups A, B, C, D
  • Class I, Zone 2, Group IIC
  • ATEX Zone 2, Group IIC

FAQ

What primary hardware components are integrated inside this discrete I/O pack?

The module contains two separate Ethernet ports, a local signal processor, a dedicated data acquisition board, and an array of front panel diagnostic LED indicators.

Which terminal board models can be connected to the module configuration?

This module works with intrinsically safe apparatus relay contact terminal boards, such as the ISx0yTDBSH2A, ISx0yTDBSH8A, ISx0yTDBTH2A, and ISx0yTDBTH8A.

How are the terminal connections labeled for field installation loops?

The assembly features up to twenty-four field terminals when combined with TDBS or TDBT options, where all positive terminals are specifically designated as contact-wetting inputs.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 7 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Black
Country of origin
United States

Technical knowledge

Derivative Action in PID Control Without Noise Problems

Learn what derivative action contributes to a PID loop, why it can amplify measurement noise and setpoint changes, and how filtering, sampling, and staged tests make D tuning safer.

Designing Industrial Networks That Stay Troubleshootable

A practical guide to segmenting, documenting, and testing industrial Ethernet networks so plant teams can isolate faults quickly, control change, and expand without creating fragile dependencies.

Commissioning IO-Link From Master Ports to IODD Data

Commission IO-Link systematically from master addressing and port modes through IODD selection, PLC byte mapping, parameter backups, device validation, and failure-injection tests.

PowerFlex Dynamic Braking Resistor Design and Testing

A practical PowerFlex braking guide covering regenerative energy, resistor resistance and duty cycle, thermal protection, model-specific parameters, and measured commissioning tests.

Engineering Industrial Joystick Controls for Safe Motion

An industrial joystick is only the first element in a safe motion command chain. This guide covers sensing choices, wiring, signal validation, PLC logic, restart behavior, and commissioning for...

Seeing PID Behavior Before Tuning the Loop

PID tuning becomes safer when engineers can see how proportional, integral, and derivative actions reshape error, output, and response over time. This guide turns live trends into a disciplined...