HIMA F 6705 HIQuad X 2-Fold Converter Digital/Analog Module
SKU F6705
In stock
No reviews
12-month warranty
Free returns within 30 days
Manufacturer:
HIMA
Product No.:
F6705
Country of origin:Germany
Product Type:
Digital to Analog Converters
Payment:
T/T, Western Union
Weight:
350g
Dimensions:
20 x 130 x 180 mm
Shipping port:
Xiamen
Warranty:
12 months
Description
The HIMA F 6705 is a 2-fold digital/analog converter designed for safety-related signal conversion in source or sink mode. The module operates within safety-instrumented systems up to Requirement Class AK 1 ... 6 and receives data via the internal VO bus. The F 6705 provides two individually galvanically isolated analog outputs capable of delivering 0/4 ... 20 mA current signals with integrated safety shutdown isolation. During continuous operation, automated internal testing routines continuously verify the linearity of the onboard 12-bit D/A converter, cross-talk between individual output channels, and safety shutdown capabilities.
Features
Two individually galvanically isolated analog output channels with safety isolation
Configurable operation for either source mode or sink mode per channel
Continuous automated testing of D/A converter linearity, channel cross-talk, and safety shutdown
Support for parallel redundant output configurations and bipolar current mode (-20 mA to +20 mA)
Integrated safety shutdown mechanism for fail-safe system operation
Applications
Safety-instrumented systems (SIS) requiring Requirement Class AK 1 ... 6 compliance
Fail-safe process control loops using 0/4 ... 20 mA analog outputs
Redundant and bipolar current output control configurations
Ordering Information
Part Number / Model
Description
F 6705
2-fold Converter Digital/Analog Module, Safety Related
Flat pin plug 6.3 x 0.8 mm for cable screen (ge-gn / Yellow-Green)
Installation Guidelines
Unused Channels: Connect a jumper between terminals b6 and b8 for Channel 1, or between b22 and b24 for Channel 2, to avoid module error messages.
Shielding: Connect the 6.3 x 0.8 mm flat pin plug of the cable screen directly to the earth bar located beneath the module slot.
Redundant Operation: Paralleled channels must operate in the same mode (source or sink). Total burden resistance must be halved, and current generation should be balanced across both channels to minimize thermal drift.
Bipolar Operation: When generating -20 mA to +20 mA outputs using two modules, configure Module 1 for positive current and Module 2 for negative current. Control logic must ensure only one module outputs current at a given time.
Compliance and Certifications
Standard / Certification
Detail
TÜV
Approved for safety-related applications
CE
CE Compliance
Requirement Class
AK 1 ... 6
IS
Intrinsic Safety Certified
FAQ
How must unused analog channels be wired on the module to prevent diagnostic error indications?
Unused channels require termination jumpers between terminal b6 and b8 for channel 1, or terminals b22 and b24 for channel 2. This jumper prevents internal diagnostics from flagging open-circuit fault conditions.
What source voltage and maximum load resistance are supported when operating channels in sink mode?
The module requires a source voltage between 10 and 30 V DC. Maximum burden resistance in sink mode is calculated using the formula (UQ - 10 V) divided by 21.2 mA, incorporating external line resistance.
What internal automatic test routines are conducted on the converter module during continuous system operation?
The module automatically performs continuous self-testing during operation. Primary test routines verify the linearity of the 12-bit D/A converter, monitor cross-talk between output channels, and check the functionality of the integrated safety shutdown circuit.
A field replacement guide for GE Fanuc IC200MDL650 covering revision-dependent negative logic, four common groups, 24 VDC thresholds, input filtering, carrier checks and commissioning records.
A field-focused IC697CPX935 replacement guide covering fast memory, firmware-dependent serial behavior, rack power, cooling, I/O architecture and backup records.
A field-focused IC693DSM324 replacement guide covering Series 90-30 host checks, FSSB servo-chain records, 5 V power budget, firmware limits, follower control and commissioning.
A practical replacement guide for the GE Fanuc IC693CPU313, covering its embedded five-slot architecture, memory backup, firmware-dependent capacity and why it cannot use Series 90-30 expansion racks.
Choosing a selection results in a full page refresh.