Honeywell

Honeywell 900G02-0202 HC900 Digital Input 24VDC 16-Channel Module

SKU 900G02-0202

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: 900G02-0202

  • Country of origin:United States

  • Product Type: Digital Input Modules

  • Payment: T/T, Western Union

  • Weight: 3000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

Designed for seamless integration with the HC900 controller platform, the 900G02-0202 facilitates the precise acquisition of discrete binary states from field-level sensors, switches, and contacts. This digital input module accommodates 16 independent input channels operating at a nominal 24 VDC threshold. It processes raw ON/OFF signals from limit switches, proximity sensors, pushbuttons, and auxiliary relays directly into the control processor database, ensuring dependable status updates for interlocking, safety monitoring, and sequencing logic.

The module features exceptional galvanic isolation to shield internal logic circuits from field-side electrical disturbances, surges, and common-mode noise. Status LEDs on the front panel provide real-time visual feedback for diagnostic verification. Engineered for high-density environments, this module minimizes cabinet footprint while maintaining superior thermal dissipation profile across standard operating ranges.

Features

  • 16 high-density digital input channels configured for 24 VDC sinking or sourcing inputs.
  • Individual channel LED indicators on the faceplate for rapid loop diagnostics and status verification.
  • Robust optical isolation protecting backplane control circuitry from field-side electrical transients.
  • Hot-swappable architecture allows safe module insertion and removal without disrupting active controller backplane operations.
  • Configurable software input filters to eliminate contact bounce and high-frequency noise.

Applications

  • Burner management systems (BMS) and industrial combustion control loops.
  • Water and wastewater treatment plant monitoring.
  • Boiler system safety interlocks and auxiliary equipment tracking.
  • Chemical processing and refinery auxiliary sequence control.

Technical Specifications

Manufacturer Honeywell
Part Number / Model 900G02-0202
Series HC900 Control System
Module Type Digital Input (DI)
Number of Channels 16 Channels
Nominal Input Voltage 24 VDC
Operating Input Range 15 VDC to 30 VDC (Logic High), 0 VDC to 5 VDC (Logic Low)
Galvanic Isolation 1500 VAC Channel-to-Backplane
Power Requirements Backplane draw: 150 mA at 5 VDC
Operating Temperature 0 to 60 degC
Storage Temperature -40 to 85 degC
Relative Humidity 5% to 95% non-condensing

Connections and Interfaces

Terminal Pin Function Assignment
1 to 16 Digital Input Channels 1 through 16
17, 18 24 VDC Common Return (COM)
19, 20 Chassis Ground / Shield Termination

Installation Guidelines

  • Align the module carefully with the card guide rails of the HC900 rack chassis and slide firmly inward until the backplane connector is fully seated.
  • Secure the upper and lower retaining screws to protect the module from vibrational displacement.
  • Avoid routing 24 VDC digital input field wiring in parallel close to high-voltage AC power lines to prevent electromagnetic coupling.
  • Utilize the designated terminal blocks designed for the HC900 system to ensure correct wiring pinout and strain relief.

Compliance and Certifications

  • CE Compliant
  • UL Listed (US and Canada)
  • FM Approved, Class I, Division 2, Groups A, B, C, D
  • ATEX Zone 2 Certified

FAQ

What is the primary function of the Honeywell 900G02-0202?

The Honeywell 900G02-0202 is a 16-channel digital input module designed to interface 24 VDC field signals (switches, buttons, contacts) with the HC900 process controller.

Does the 900G02-0202 support hot-swapping during active operation?

Yes, this module supports hot-swapping, allowing maintenance personnel to replace modules on the HC900 backplane without shutting down control power.

What is the acceptable voltage range for logic high and logic low states?

Logic High is active between 15 VDC and 30 VDC, while Logic Low is detected in the range of 0 VDC to 5 VDC.

What electrical certifications does this module hold?

The 900G02-0202 is CE compliant, UL listed for US and Canada, FM Approved for Class I, Division 2 (Groups A, B, C, D), and ATEX Zone 2 compliant.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 2 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

Designing Power and Communication Redundancy

Design control-system redundancy by mapping shared dependencies, separating power and network paths, defining failover behavior, exposing degraded operation, and proof-testing every tolerated fault.

Troubleshooting Industrial Control Cabinets Systematically

A structured control-cabinet troubleshooting method covering safe work, drawings, power paths, branch protection, DC supplies, return circuits, PLC outputs, fault records and repair verification.

Measuring Voltage in Industrial Control Circuits

A practical voltage-testing guide for industrial control panels, covering reference points, meter selection, live-dead-live checks, voltage drop, ghost voltage, stored energy and intermittent faults.

Building a Verifiable Lockout Tagout Procedure

A practical lockout tagout guide covering hazardous-energy identification, isolation, stored-energy control, verification, group work, temporary testing, restoration, inspections and audits.

Designing Compressed-Air Preparation at the Machine

A field guide to point-of-use compressed-air preparation covering filters, regulators, drains, dryers, lubrication, pressure loss, isolation, monitoring, commissioning and leak testing.

Selecting Pneumatic Valve Actuation and Safe States

A practical guide to manual, pilot and solenoid pneumatic valves, covering port functions, monostable and bistable behavior, PLC outputs, safe states, commissioning and fault diagnosis.