Honeywell FC-SAO-0220m CCV1.0 Safety Manager Safe Analog Output Module

SKU FC-SAO-0220m CCV1.0

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: FC-SAO-0220m CCV1.0

  • Country of origin:United States

  • Product Type: Analog Output Modules

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 130 x 20 x 262 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell FC-SAO-0220m is a Safe Analog Output Module featuring two 0(4)–20 mA output channels engineered for high-integrity safety control applications within the Honeywell Safety Manager system. Operating as a critical output interface, the module converts internal digital system logic commands into precise analog current loops to regulate modulating final control elements, valves, and positioners in safety-critical loops.

Designed with internal safety architecture, each channel contains a 12-bit D/A converter for output signal generation and an integrated A/D converter that continuously reads back the actual output value. Within a configured Diagnostic Test Interval, the module automatically tests output channels for output value accuracy (within ±5%), de-energization capability, and cross-talk between outputs. Each channel features a secondary means of de-energizing (SMOD), enabling the watchdog and processor to de-energize the output independently of the application command value.

The Honeywell FC-SAO-0220m features conformal coating on all internal electronic assemblies (designated by the FC- prefix) to protect against airborne contaminants, dust, and aggressive industrial environments. The output channels are galvanically isolated from both the 24 Vdc internal power supply and the 5 Vdc logic supply.

Features

  • Provides two 0(4)–20 mA safe analog output channels configurable as active or passive loops.
  • Conformally coated PCB construction (FC- prefix) for reliable environmental protection.
  • Dual-converter architecture utilizes a 12-bit D/A converter for driving current and an internal A/D converter for continuous signal read-back and self-testing.
  • Incorporates continuous self-diagnostics verifying output current accuracy within ±5%, de-energization ability, and channel cross-talk.
  • Secondary Means of De-energizing (SMOD) allows the watchdog or main processor to force channels to a de-energized state.
  • Galvanically isolated outputs from the 5 Vdc and 24 Vdc supply buses.
  • Supports both non-redundant and redundant Safety Manager I/O configurations starting as of Safety Builder release 120.

Applications

  • Safety Instrumented Systems (SIS): Converts safety shutdown logic into precise 4–20 mA positioning signals for emergency isolation and modulating control valves.
  • Burner Management Systems (BMS): Manages fuel-to-air ratio valves and flue gas damper actuators requiring safety-certified continuous signal conditioning.
  • Fire & Gas (F&G) Mitigation Systems: Controls variable output speed drives and proportional deluge valves.
  • Hazardous Location Control: Interfaces with non-incendive field circuits in Class I, Division 2 environments via approved terminal assemblies.

Technical Specifications

General

Parameter Specification
Manufacturer Honeywell
Model Number FC-SAO-0220m
Module Version CCV1.0
Product Type Safe Analog Output Module (0(4)–20 mA)
System Platform Honeywell Safety Manager
Coating Conformal Coated (FC-Type)
Form Factor 4 TE, 3 HE (4 HP, 3U)

Electrical & Power Ratings

Parameter Specification
Logic Power Requirements 5 Vdc, 30 mA
Internal Supply Voltage 24 Vdc, 65 mA + 30 mA per active output
WDG Input Current 0.5 mA
Isolation Galvanically isolated from 24 Vdc and 5 Vdc
Common Pins 0 V 1 (d14) and 0 V 2 (d20) interconnected on module

Output Channels & Performance

Parameter Specification
Number of Output Channels 2
Output Signal Range Active or Passive, 0–20 mA / 4–20 mA
D/A Converter Resolution 12-bit
Off-State Current < 0.05 mA
Active Loop Resistance Maximum 600 Ω
Active Maximum Output Voltage 30 Vdc
Passive External Voltage Maximum 40 Vdc
Passive Minimum Voltage Drop ≤ 7.5 V
Diagnostic Voltage Accuracy Current value ± 5%
Allowed Load Types Resistive or capacitive only (inductive loads report module fault)

Mechanical Keying

Parameter Specification
Module Keying Holes Holes A9, C5
Chassis Keying Pins Large pins A9, C5

Connections / Interfaces

Connector Pin Function
d2 Watchdog (WDG)
b2 Ground (GND)
z2 Logic Power (+5 Vdc VCC)
d8 Internal Supply 24 Vdc
z8 Supply 0 Vdc
d14 0 V 1
d16 mA 1 (Channel 1 Current Output)
z16 Loop 1
d20 0 V 2
d22 mA 2 (Channel 2 Current Output)
z22 Loop 2

Installation Guidelines

  1. Confirm that the Honeywell FC-SAO-0220m module version (CCV1.0) matches system software project requirements.
  2. Inspect the rear connector pins and keying hole locations (A9, C5) to ensure compatibility with the card guide positioning pins.
  3. Ensure power to the target chassis section is safely disconnected before inserting the card, or verify hot-swap suitability in redundant configurations.
  4. Align the card edge with the 4 TE chassis guide rails and push firmly into the backplane until properly seated.
  5. Connect the 24 Vdc internal supply to prevent fault detection during automatic self-test procedures.
  6. Short-circuit any unused output channels (link terminal 2 with 3 for channel 1, or terminal 6 with 7 for channel 2 on the TSAO-0220m FTA) to prevent fault reporting during self-diagnostic execution.
  7. Do not connect inductive loads directly to the outputs; the module is designed exclusively for resistive or capacitive loads.

Maintenance & Replacement Recommendations

  • Redundant Output Consideration: When replacing a module in redundant analog output configurations, note that a detected fault during self-testing may cause a minor current dip on the output before the Safety Manager switches control to the healthy redundant channel.
  • Fault Inspection: If a channel fault LED lights up, verify that inductive loads have not been connected to the outputs and ensure that all unused channels are properly jumpered.

Compliance and Certifications

  • CE Marked
  • TÜV Certified
  • UL Listed
  • CSA Certified
  • Factory Mutual (FM): FM 3611 Approved for Class I, Division 2, Groups ABCD and Class II, Division 2, Groups FG non-incendive field circuits in hazardous locations.

FAQ

What is the primary function of the Honeywell FC-SAO-0220m module?

The Honeywell FC-SAO-0220m is a 2-channel safe analog output module (0(4)–20 mA) for Safety Manager systems that converts safety logic commands into analog current loops to control modulating safety devices.

What type of loads can be connected to the Honeywell FC-SAO-0220m module?

The Honeywell FC-SAO-0220m supports resistive or capacitive loads only. Connecting inductive loads will cause the module to report a channel fault.

How should unused channels on the Honeywell FC-SAO-0220m be wired?

Unused output channels on the Honeywell FC-SAO-0220m must be shorted (e.g., linking terminals 2 with 3 for Channel 1 on the TSAO-0220m FTA) to prevent fault detection during automatic self-test cycles.

What hazardous area certifications does the Honeywell FC-SAO-0220m carry?

The Honeywell FC-SAO-0220m is FM approved to FM 3611 for Class I, Division 2, Groups ABCD and Class II, Division 2, Groups FG non-incendive field circuits.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell FC-SAO-0220m CCV1.0 Safety Manager Safe Analog Output Module

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 4 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Dots
Country of origin
United States
Power source
DC Power

Technical knowledge

Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap

Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.