Directing high-precision analog measurements in hazardous environments, the ELX3152-0090 is an intrinsically safe analog input terminal designed for the direct integration of field devices from Zone 0/20 explosion-hazard areas. This 2-channel single-ended interface processes standard 0/4 to 20 mA current signals with 16-bit resolution. Integrated with TwinSAFE SC (Single Channel) technology, the terminal enables safety-supporting signals to be analyzed and utilized within standard industrial control systems, expanding diagnostic depth and process safety across complex control architectures.

Features

  • Direct connection of intrinsically safe field devices from Zone 0/20 and Zone 1/21.
  • Two independent single-ended analog input channels supporting 0 to 20 mA and 4 to 20 mA signals.
  • TwinSAFE SC capability for integrating safety-assisting monitoring functions.
  • High-resolution 16-bit representation for highly accurate field instrument monitoring.
  • Supports Distributed Clocks (DC) for highly synchronized and precise EtherCAT process data acquisition.
  • Advanced internal processing options including activatable digital FIR/IIR filters.
  • Diagnostic compliance with NE43 NAMUR sensor limit specifications.

Applications

  • Oil and gas extraction, processing, and refining facilities.
  • Chemical and petrochemical process plants requiring intrinsic safety (Ex i).
  • Industrial wastewater treatment facilities with explosive gas atmospheres.
  • Pharmaceutical processing lines managing volatile substances.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model ELX3152-0090
Product Type EtherCAT Terminal (Ex i, TwinSAFE SC)
Number of Inputs 2 (single-ended)
Signal Current Range 0/4...20 mA
Connection Technology 2- or 3-wire (default: 3-wire)
Resolution 16 bit (including sign)
Measuring Error < +/-0.3% (relative to full scale value)
Internal Measuring Resistance typ. 100 Ohm
Input Filter Limit Frequency 5 kHz
Conversion Time typ. 1 ms
Electronics Supply Voltage 24 V DC (via power contacts, powered by ELX9560)
Current Consumption (Power Contacts) typ. 10 mA + load
Current Consumption (E-bus) typ. 85 mA
Distributed Clocks (DC) Yes
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95%, non-condensing
Weight approx. 60 g
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Housing Material Polycarbonate

Connections and Interfaces

Connection Property Specification / Wire Size
Wiring Type Solid wire, stranded wire, or wire with ferrule (spring-actuated)
Solid Conductor (s) 0.08 to 2.5 mm² (AWG 28...14)
Stranded Conductor (st) 0.08 to 2.5 mm² (AWG 28...14)
Flexible Conductor with Ferrule (f) 0.14 to 1.5 mm² (AWG 26...16)
Stripping Length 8 to 9 mm
Power Contacts 2 blade/spring contacts

Installation Guidelines

  • Mount securely on a standard 35 mm DIN rail conforming to EN 60715 using the locking mechanism.
  • Ensure adjacent terminal modules are locked using the integrated double-slot and key housing connections.
  • Power the terminal exclusively through a certified ELX9560 power supply module to satisfy all intrinsically safe electrical isolation standards.
  • Ensure appropriate spacing and ventilation within the terminal cluster as defined by the hazardous zone class regulations.

Compliance and Certifications

  • CE, UL
  • ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
  • IECEx: Ex ec [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I
  • cFMus: AIS Class I, II, III, Division 1, Groups A-G; Class I, Division 2, Groups A-D; Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc
Loading product navigation…

What is the primary function of the Beckhoff ELX3152-0090?

The Beckhoff ELX3152-0090 is a 2-channel analog input EtherCAT Terminal that allows direct measurement of 0/4 to 20 mA current loops from intrinsically safe (Ex i) sensors located in Zone 0/20 and Zone 1/21 hazardous areas.

What is TwinSAFE SC technology and how is it used in this module?

TwinSAFE SC (Single Channel) technology allows analog process values from standard terminals like the ELX3152-0090 to be made available to safety-related networks (TwinSAFE) for auxiliary safety functions, without requiring dedicated, certified safety-only hardware.

What power supply is required for the ELX3152-0090 terminal?

The terminal requires 24 V DC power delivered via the power contacts from an ELX9560 power supply terminal. This ensures compliance with intrinsically safe barrier regulations and appropriate signal isolation.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...