1 de 1

BECKHOFF EP3162-0002 EtherCAT Box 2-Channel Analog Input Module

BECKHOFF EP3162-0002 EtherCAT Box 2-Channel Analog Input Module

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: EP3162-0002

  • País de origem:Alemanha

  • Tipo de Produto: Analog Input Modules

  • Pagamento: T/T, Western Union

  • Peso: 165g

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Processing analog signals directly in harsh field environments is simplified with the EP3162-0002 EtherCAT Box. This IP67-rated decentralized module features two highly flexible, galvanically isolated analog inputs that are software-parameterizable for either voltage (-10/0 to +10 V) or current (-20/0/4 to +20 mA) signals on a per-channel basis. By executing analog-to-digital conversion directly at the sensor location, this module minimizes signal degradation over long wire runs, enabling clean 16-bit measurement resolution across distributed fieldbus networks.

The device features dual-channel isolation to eliminate ground loop issues, making it highly reliable in electrically noisy industrial applications. Connectivity is facilitated through robust, industry-standard M12 connectors for the sensor lines and M8 connectors for the EtherCAT fieldbus and power supply daisy-chaining. With integrated Distributed Clocks (DC) support, the module guarantees precise, synchronized data acquisition across large-scale industrial machinery.

Features

  • Two single-ended, individually parameterizable analog input channels.
  • Supports standard industrial signal ranges: -10 to +10 V, 0 to 10 V, -20 to +20 mA, 0 to 20 mA, and 4 to 20 mA.
  • Complete galvanic isolation between individual input channels for high signal integrity.
  • Fast analog-to-digital conversion time of approximately 100 microseconds per channel.
  • High-precision 16-bit digital resolution (including sign).
  • Distributed Clocks (DC) support for high-fidelity clock synchronization in time-critical tasks.
  • Rugged IP65/66/67 physical housing for direct mounting outside of control cabinets.

Applications

  • Decentralized process instrumentation and sensor monitoring in heavy industrial plants.
  • Hydraulics and pneumatic system pressure, flow, and temperature tracking.
  • Machine-mount data acquisition systems in automotive assembly and packaging lines.
  • Test bench environments requiring high-speed, synchronized analog measurements.

Technical Specifications

Manufacturer Beckhoff Automation
Part Number / Model EP3162-0002
Product Type EtherCAT Box (Analog Input)
Number of Inputs 2 single-ended (galvanically isolated channels)
Signal Type (Voltage) -10/0...+10 V (parameterizable per channel)
Signal Type (Current) -20/0/4...+20 mA (parameterizable per channel)
Resolution 16 bit (including sign)
Internal Resistance > 200 kOhm (voltage) | typ. 85 Ohm + diode voltage (current)
Measurement Error < ±0.3% (relative to full scale value)
Conversion Time ~ 100 microseconds
Input Filter Limit Frequency 5 kHz
Bus Interface Connection 2 x M8 socket, shielded, screw-type
Input Connection Method M12 x 1, 5-pin, A-coded
Nominal Supply Voltage 24 V DC (-15% / +20%)
Power Connection Feed: 1 x M8 male (4-pin); Downstream: 1 x M8 female (4-pin)
Current Consumption (Us) 120 mA
Sensor Supply Us derived from auxiliary voltage, electrically isolated
Electrical Isolation 500 V (fieldbus to signal), 300 V (signal to signal)
Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Weight approx. 165 g
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27

Connections and Interfaces

M12 Pin Connection Signal Assignment
Pin 1 +24 V DC Sensor Supply (Us)
Pin 2 Analog Input + (Voltage / Current)
Pin 3 GND Sensor Supply (Us)
Pin 4 Analog Input -
Pin 5 Shield / Functional Earth

Installation Guidelines

  • Mounting: Screw the module directly onto flat machine surfaces using the integrated mounting holes. Ensure the mounting plane is grounded.
  • Shielding: Use fully shielded M12 sensor cables and shielded M8 EtherCAT cabling to preserve signal integrity and prevent electromagnetic interference (EMI).
  • Power Daisy Chaining: When utilizing the downstream M8 power output, verify that the total current draw of downstream modules does not exceed the maximum power bus capacity.
  • Sealing: Unused M12 and M8 ports must be sealed with appropriate IP67 protection caps to maintain environmental integrity.

Compliance and Certifications

  • CE
  • UL
Loading product navigation…

Can the EP3162-0002 measure both voltage and current on different channels simultaneously?

Yes, each of the two analog input channels on the EP3162-0002 can be independently parameterized via TwinCAT software. One channel can be set for voltage measurements (e.g., -10 to +10 V) while the other handles current loops (e.g., 4 to 20 mA).

What is the level of electrical isolation provided between the two input channels?

The EP3162-0002 features galvanic isolation up to 300 V between the individual input channels, as well as 500 V isolation to the EtherCAT fieldbus, minimizing the risk of ground loops.

Does this module require a control cabinet for installation?

No, with its IP65/66/67-rated enclosure, the EP3162-0002 is designed for direct machine mounting in wet, dusty, or harsh environments without needing an electrical enclosure.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...