1 de 1

BECKHOFF KS4004 KS Series Bus Terminal

BECKHOFF KS4004 KS Series Bus Terminal

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: KS4004

  • País de origem:Alemanha

  • Tipo de Produto: Bus Terminals

  • Pagamento: T/T, Western Union

  • Peso: 85g

  • Dimensões: 6.8 cm x 1.2 cm x 10.0 cm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

The KS4004 analog output terminal is designed to generate highly accurate analog signals within the range of 0 to 10 V. Engineered as part of the Beckhoff KS series, this 4-channel module features a pluggable wiring level that permits swift replacement during maintenance without disconnecting active field wiring. The terminal processes electrical signals with a resolution of 12 bits and transfers them, electrically isolated, to the process level. The power required to operate the module is drawn directly from the K-bus, eliminating the need for separate external power contacts.

This single-ended output terminal is optimized for compact control cabinets where high-density analog output signals and quick-disassembly capabilities are critical. With built-in short-circuit protection and an exceptionally low output error margin, the KS4004 guarantees stable command signal delivery to actuator drives, control valves, and other analog-driven field devices in complex process environments.

Features

  • Four analog output channels with a 0 to 10 V signal range.
  • Pluggable connection level for easy installation and tool-free module swap-outs.
  • Internal power supply driven directly via the Beckhoff K-bus interface.
  • Short-circuit proof outputs designed to handle loads greater than 5 kOhm.
  • High-accuracy performance with a relative output error of less than +/-0.1 % of the full-scale value.
  • No address or hardware configuration required prior to deployment.

Applications

  • Industrial positioning systems and actuator control loops.
  • Variable frequency drive (VFD) speed reference signaling.
  • HVAC dampers and climate control system modulation.
  • Standard machine building and process plant automation.

Technical Specifications

ManufacturerPart Number / ModelTechnologyNumber of OutputsPower SupplySignal VoltageLoadOutput ErrorResolutionConversion TimeElectrical IsolationCurrent Consumption K-BusCurrent Consumption Power ContactsBit Width in Process ImageOperating TemperatureStorage TemperatureRelative HumidityVibration and Shock ResistanceEMC Immunity and EmissionProtection RatingDesignMaterialInstallationDimensions (L x W x H)Weight
BECKHOFF
KS4004
Single-ended
4
Via the K-bus
0 to 10 V
> 5 kOhm (short-circuit proof)
< +/-0.1 % (relative to end value)
12 bit
Approx. 2 ms
500 V (K-bus/signal voltage)
Typ. 85 mA
None (no power contacts)
Output: 4 x 16 bit data (optional 4 x 8 bit control/status)
0 to +55 degC
-25 to +85 degC
95 %, no condensation
Conforms to EN 60068-2-6 / EN 60068-2-27
Conforms to EN 61000-6-2 / EN 61000-6-4
IP20 (variable installation position)
Terminal housing with pluggable wiring level
Polycarbonate
35 mm DIN rail (conforming to EN 60715) with lock
6.8 cm x 1.2 cm x 10.0 cm
0.085 kg

Connections and Interfaces

Wiring MethodSolid Wire Cross-SectionStranded Wire Cross-SectionFine-Wire Cross-SectionStripping Length
Connection Property Specification
Spring actuation by screwdriver
0.08 to 1.5 mm² (AWG 28 to 16)
0.08 to 1.5 mm² (AWG 28 to 16)
0.14 to 1.5 mm² (AWG 26 to 16)
9 to 10 mm

Installation Guidelines

  • Mount the module vertically or horizontally on a standard 35 mm DIN rail conforming to EN 60715. Ensure the locking slide mechanism snaps securely into place.
  • To prevent electromagnetic interference on sensitive 0-10 V analog lines, use shielded cables and connect the shield to a low-resistance ground terminal near the entry point of the control panel.
  • Ensure that no field wiring is connected when plugging or unplugging the terminal wiring level to avoid transient electrical spikes.

Compliance and Certifications

  • CE
  • UL
  • ATEX: II 3 G Ex nA IIC T4 Gc
Loading product navigation…

What is the primary difference between Beckhoff KS and KL series terminals?

The KS series terminals (such as the KS4004) feature a pluggable connection level that can be detached from the housing. This allows the terminal electronics to be replaced without disconnecting the pre-wired terminal blocks.

Does the KS4004 require an external power supply connection?

No, the KS4004 does not use external power contacts. It is powered internally via the standard Beckhoff K-bus, consuming typically 85 mA.

What is the output voltage and channel capability of the KS4004?

The KS4004 provides 4 analog output channels, each capable of outputting a 0 to 10 V signal with 12-bit resolution.

Is the analog output protected against short circuits?

Yes, the analog outputs on the KS4004 are short-circuit proof for loads greater than 5 kOhm.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reabastecimento e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...