BECKHOFF KS3444 Bus Terminal 4-Channel Analog Input Module

BECKHOFF KS3444 Bus Terminal 4-Channel Analog Input Module

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: KS3444

  • País de origem:Alemanha

  • Tipo de Produto: Bus Terminals

  • Pagamento: T/T, Western Union

  • Peso: 55g

  • Dimensões: 12 mm x 100 mm x 68 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Industrial processing systems utilize the BECKHOFF KS3444 analog input bus terminal to interface standard 0 to 20 mA signals directly from the field level to the higher-level automation controller. This four-channel module features single-ended inputs and provides a highly space-efficient design with a pluggable wiring level, enabling fast, tool-free installation and maintenance. By operating directly through the standard K-bus, the unit transmits digitized process values back to the coupler or controller with a 12-bit resolution. Integrated electrical isolation of 500 V between the K-bus and the signal channels guarantees high noise immunity and signal integrity in demanding electrical environments.

Features

  • Four single-ended analog inputs handling standard 0 to 20 mA current loops.
  • Pluggable connection level (KS-series design) allowing pre-wiring and rapid terminal replacement.
  • Compact 12 mm housing width to optimize control cabinet and DIN rail space.
  • K-bus powered with a typical current consumption of 85 mA.
  • Reliable performance across a broad operating temperature range of 0 to +55 degC.
  • Sturdy design complying with EN 60068-2-6 and EN 60068-2-27 for vibration and shock resistance.

Applications

  • Chemical and petrochemical processing plants.
  • Water and wastewater treatment facilities.
  • Machinery manufacturing and factory automation.
  • HVAC and building automation controls.

Technical Specifications

CategoryTechnical ParameterValue
Manufacturer BECKHOFF KS3444
Product Type Bus Terminal (Pluggable wiring level) 4
Signal Current 0 to 20 mA Single-ended
Internal Resistance < 85 Ohm 12 bit
Conversion Time approx. 2 ms < ±0.3 % (relative to full scale value)
Surge Voltage Resistance 30 V DC 500 V (K-bus/signal voltage)
Current Consumption K-Bus typ. 85 mA Input: 4 x 16 bit data (4 x 8 bit control/status optional)
Housing Material Polycarbonate IP20 / variable
Operating Temperature 0 to +55 degC -25 to +85 degC
Relative Humidity 95 %, non-condensing Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4 35 mm DIN rail (EN 60715) with lock
Connection Cross-section Solid/Stranded: 0.08 to 1.5 mm²; Fine-wire: 0.14 to 1.5 mm² AWG 28 to 16 (Solid/Stranded); AWG 26 to 16 (Fine-wire)
Stripping Length 9 to 10 mm 12 mm x 100 mm x 68 mm
Weight 0.055 kg II 3 G Ex nA IIC T4 Gc

Connections and Interfaces

Connection Point Signal Assignment
Terminal 1 Input 1 (+)
Terminal 2 Input 2 (+)
Terminal 3 Input 3 (+)
Terminal 4 Input 4 (+)
Terminal 5 Input 1 (0 V)
Terminal 6 Input 2 (0 V)
Terminal 7 Input 3 (0 V)
Terminal 8 Input 4 (0 V)

Installation Guidelines

  • Mount the terminal on a standard 35 mm DIN rail conforming to EN 60715. Ensure the locking mechanism is securely engaged.
  • To wire the pluggable KS terminal, use a flat-bladed screwdriver to actuate the integrated tension clamp mechanism.
  • Ensure the system power supply is deactivated before plugging or unplugging the terminal wiring block to prevent damage to the K-bus connections.
  • Observe regional grounding and shielding guidelines for analog signal cables to minimize electromagnetic interference.

Compliance and Certifications

  • CE
  • UL
  • ATEX (II 3 G Ex nA IIC T4 Gc)
  • DNVGL
Loading product navigation…

What is the primary difference between the Beckhoff KL3444 and the KS3444?

The KS3444 features a pluggable wiring level, allowing the terminal block connector to be detached from the main housing without disconnecting individual field wires. The KL3444 has a fixed wiring level.

Does the KS3444 require an external power supply for K-bus communication?

No, the KS3444 is powered directly via the K-bus backplane from the bus coupler or controller, drawing a typical current of 85 mA.

Is the Beckhoff KS3444 suitable for hazardous locations?

Yes, the KS3444 is ATEX certified with Ex marking II 3 G Ex nA IIC T4 Gc, making it suitable for Zone 2 hazardous areas when installed in an appropriate enclosure.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...