1 de 3

General Electric IS200ESELH1AAA Mark VI Exciter Collector Board

General Electric IS200ESELH1AAA Mark VI Exciter Collector Board

Apenas 3 item(ns) restante(s) em estoque
  • Fabricante: General Electric

  • Nº do Produto: IS200ESELH1A

  • País de origem:Estados Unidos

  • Tipo de Produto: Exciter Collector Board

  • Código de barras: 8537101190

  • Pagamento: T/T, Western Union

  • Peso: 850g

  • Dimensões: 25 mm x 330 mm x 178 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

The IS200ESELH1AAA serves as an exciter collector board developed for the Mark VI Speedtronic control platform. This electronic assembly functions primarily within turbine control systems to handle continuous management parameters for steam and gas turbines. Operating within either a Simplex infrastructure or a Triple Modular Redundant (TMR) structural setup, the IS200ESELH1AAA receives logic-level gate pulses directly from a linked VME-based EMIO input/output management card. The module interfaces with up to six distinct gate pulse signals, routing these outputs onward to an external EGPA exciter gate pulse amplifier board positioned inside a separate enclosure cabinet. Built with integrated voltage suppression and circuit limitation components spanning over 200 resistors, diodes, transistors, and integrated circuits, this conformal-coated printed circuit board ensures clean data execution pathways across dual multi-pin backplane connectors.

Features

  • Receives up to six distinct logic-level gate pulse signals directly from a host VME-style EMIO management unit.
  • Routes processed gating information to a separate cabinet-mounted EGPA exciter gate pulse amplifier module.
  • Deploys integrated voltage suppression architecture using a network of over 200 resistors, capacitors, transistors, and diodes.
  • Features a slim physical faceplate equipped with three status LEDs designated for Power, Active, and Gating monitoring.
  • Adapts dynamically to simple system configurations using one unit, or TMR setups utilizing two boards driven by M1 and M2 links.
  • Features specialized industrial conformal PCB insulation coating across the active surface layer for hardware durability.

Applications

  • Mark VI Speedtronic Systems: Directing gate pulse synchronization tasks for utility-scale gas and steam turbine controls.
  • Excitation Controls: Interfacing interface logic maps between primary input/output blocks and external gate pulse amplifiers.
  • TMR Redundant Operations: Functioning as an isolated pulse capture node driven concurrently by distinct controller processors.

Technical Specifications

Parameter Value
Manufacturer General Electric
Functional Code / Part Number IS200ESELH1AAA
Functional Abbreviation ESEL
Series Mark VI Speedtronic
Product Type Exciter Collector Board
Assembly Style Normal Assembly
Total Product Revisions 3 Revisions
Backwards Compatibility First two revisions compatible
PCB Coating Treatment Conformal Coated
Input Signal Capability Up to 6 gate pulse inputs
Interface Hardware 2 x Backplane Connectors
Status Indicators 3 x Faceplate LEDs (Power, Active, Gating)
Weight 0.85 KG
Dimensions (W x H x D) 25 mm x 330 mm x 178 mm

 

Connections/Interfaces

Connector Type Function
Backplane Connectors (Dual) Provides bus interface paths and power links within the rack enclosure

 

Installation Guidelines

  • Turn off all main power paths going to the Mark VI turbine control chassis before inserting the module.
  • Slide the board evenly along the designated rack tracks until the dual backplane connectors link fully into the receiver frame.
  • Fasten the top and bottom mounting clips securely over the enclosure frame to prevent loose contact faults.
  • Verify correct tracking behaviors across the faceplate panel by evaluating the Power, Active, and Gating LEDs during system initialization.
Loading product navigation…

Are all three A-rated hardware revisions of the module completely identical?

No. Only the first two A-rated product revisions share identical revision styles to maintain backwards compatibility within the system series.

What functional components drive the module in a triple modular redundant setup?

In a TMR infrastructure, a pair of these units is required, where one board is driven directly by the M1 link and the other board interfaces with the M2 link.

What do the three integrated faceplate indicators monitor?

The three top-mounted LEDs provide clear, local status monitoring for system power, active board status, and active signal gating loops.

From which internal hardware card does the device receive its gate inputs?

The board receives up to six logic-level gate pulse inputs from a connected VME-based EMIO interface module.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Color pattern
Verde
Country of origin
Estados Unidos
Power source
Energia CC

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...