1 de 1

Mitsubishi Electric GT2710-VTWA GOT2000 Series Graphic Operation Terminal

Mitsubishi Electric GT2710-VTWA GOT2000 Series Graphic Operation Terminal

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: Mitsubishi Electric

  • Nº do Produto: GT2710-VTWA

  • País de origem:Estados Unidos

  • Tipo de Produto: HMI Operator Panels

  • Pagamento: T/T, Western Union

  • Peso: 8g

  • Dimensões: 303 mm x 218 mm x 52 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver informações completas

Description

Engineered to deliver high-performance human-machine interface functionality in demanding industrial environments, the Mitsubishi Electric GT2710-VTWA acts as an advanced control panel node within the GOT2000 Series platform. This high-specification graphic operation terminal is equipped with intuitive multi-touch gesture functions, enabling operators to swipe, pinch, and zoom for precise visualization and machine control. Featuring a 10.4-inch TFT color display, a clean white frame bezel, and wide-range AC power compatibility, this terminal ensures optimal system monitoring, alarm diagnostics, and data logging capabilities direct from the control enclosure.

Key Features

  • Multi-Touch Gesture Control: Supports intuitive multi-finger operations to prevent accidental triggers and improve operational efficiency.
  • VGA TFT Display: Crisp 640 x 480 resolution display with a high-contrast backlight for visual clarity in poorly lit control rooms.
  • Flexible Installation Layouts: Engineered to support both horizontal and vertical mounting alignments with automatic temperature de-rating.
  • Robust Environmental Tolerance: Designed to meet stringent industrial standards for vibration, shock, and noise immunity.
  • Broad Communication Port Folio: Integrated Ethernet, RS-232, RS-422/485, USB host/device, and SD card interfaces for streamlined system connectivity.

Applications

  • Automotive Assembly Plants: Serving as the primary interface for body-in-white and conveyor control architectures.
  • Food & Beverage Processing: Cleanroom and washdown environments requiring high-visibility monitors with clean white frame profiles.
  • Packaging and Material Handling: Real-time monitoring of complex multi-axis motion and high-speed sorting systems.
  • Water and Wastewater Treatment: Decentralized monitoring stations utilizing robust Ethernet-based fieldbus topologies.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number GT2710-VTWA
Series GOT2000 Series (GT27)
Display Type TFT Color LCD
Screen Size 10.4 inches
Resolution 640 x 480 Pixels (VGA)
Frame Color White
Input Power Supply Voltage 100 to 240 VAC (+10%, -15%)
Power Consumption (Max) 41 W or less
Inrush Current 60 A or less (2 ms, ambient 25 degC, max load)
Operating Ambient Temperature 0 to 55 degC (horizontal), 0 to 50 degC (vertical)
Operating Ambient Humidity 10 to 90% RH (non-condensing)
Insulation Resistance 10 MOhm or higher (500 VDC)
Applicable Wire Size 0.75 to 2 mm²
Terminal Block Screw M3 (Tightening torque: 0.5 to 0.8 N.m)
External Dimensions (W x H x D) 303 mm x 218 mm x 52 mm
Net Weight (Excl. Brackets) 2.1 kg
Shipping Weight (Calculated) 8.0 kg

Connections and Interfaces

Interface Type Connector / Pin Configuration Function / Protocol Support
Ethernet Port 1x RJ-45 Channel Modbus/TCP, MC Protocol, Host PLC Communications
Serial Interface (CH1) D-Sub 9-pin Male RS-232 serial programming, peripheral connectivity
Serial Interface (CH2) D-Sub 9-pin Female RS-422/485 multi-drop network links
USB Ports Type-A (Host) / Type Mini-B (Device) Data export, firmware transfer, external mouse/keyboard
Storage Slot 1x SD Memory Card Slot OS backup, project storage, and CSV logging parameters

Empirical Engineering Insights

Alternative Models & Compatibility

When migrating legacy systems from the GT16 or GT15 series to the GT2710-VTWA, screen configuration layouts can be upscaled using the GT Works3 software tool. Note that the "W" in the product suffix dictates a specialized white bezel; check chemical compatibility when utilizing this version in food-processing operations where aggressive sanitation agents are in use. For drop-in mechanical sizing, ensure panel cutouts precisely match the standard GOT2000 10.4-inch dimensions.

Application Pitfalls & Engineering Notes

Thermal performance varies based on mounting geometry. When mounted vertically, the internal convective heat flow is restricted; therefore, the maximum safe operating temperature is reduced to 50 degC. Ensure at least 100 mm of clear space is maintained between the rear of the terminal and adjacent circuit components (such as variable frequency drives or high-power contactors) to mitigate induced heat and localized hotspots.

Commissioning & Wiring Tips

To protect the sensitive electronics on the power board, the terminal block must be wired with class-appropriate terminal lugs (RAV1.25-3 or V2-S3.3). Grounding must be completed using a dedicated ground wire with a cross-section of 2 mm² or larger, connected directly to a Class-3 protective ground bus. Avoid routing the terminal's power lines parallel to motor output lines or primary utility feeders to eliminate electromagnetic interference.

Installation Guidelines

CRITICAL WARNING:

Before initiating mounting, physical installation, or wire terminations on the terminal block, isolate all AC mains distribution lines. Confirm with a calibrated digital multimeter that no stray residual charge or live voltage exists at the terminal block. Failure to de-energize can damage internal logic layers and present an immediate risk of electrical shock to commissioning staff.

1
Perform a pre-cutout validation. Verify panel frame thickness is between 2.0 mm and 4.0 mm to guarantee a proper IP67F environmental front seal.
2
Insert the terminal directly into the clean-cut panel window, ensuring the pre-installed dust-gasket does not slip or bind during placement.
3
Tighten all supplied panel mounting brackets in a cross-diagonal sequence to a uniform torque rating of 0.20 to 0.25 N.m. Over-torqueing will distort the front bezel.
4
Attach the M3 ground cable first, and then proceed with the L1 and N power terminations, ensuring the terminal block's screws are locked to 0.5 - 0.8 N.m.
Loading product navigation…

What is the difference between the GT2710-VTWA and standard models?

The GT2710-VTWA features a white front-bezel frame design for clean industrial environments and operates on a standard 100 to 240 VAC power input, unlike DC-powered variants.

Does this operator terminal support multi-touch inputs?

Yes. This HMI features an advanced analog resistive film touch panel that supports simultaneous two-point gestures such as pinch, zoom, and swipe.

How should I compensate for heat in a vertical installation?

For vertical installations, the maximum operational ambient temperature is reduced from 55 degC to 50 degC. Ensure active fan cooling or heat exchangers are used if panel temperatures exceed this limit.

What software program is required to program this terminal?

The GT2710-VTWA must be programmed, updated, and configured using Mitsubishi Electric's GT Works3 software package (part of the IQ Works suite).

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reabastecimento e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Estados Unidos

Produtos Visualizados Recentemente

Conhecimento técnico

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...