Description

Serving as the hardware foundation of the modular control architecture, the Omron CS1W-BC053 provides the necessary physical mounting and high-speed electrical backplane bus for CS1-series programmable logic controller systems. This 5-slot CPU backplane enables reliable communication and regulated power distribution between the central processing unit, the system power supply module, and up to five local I/O or specialized application units.

Constructed to withstand harsh industrial environments, the Omron CS1W-BC053 ensures signal integrity across all processing channels. Its integrated expansion bus connector facilitates straightforward linkage to expansion backplanes, allowing the control system to scale effectively without compromising bus speed or data throughput.

Key Features

  • Five Dedicated I/O Slots: Accommodates up to 5 standard I/O, special I/O, or CPU bus units.
  • Dedicated CPU and Power Slots: Integrated slot positioning optimized for CS1G/CS1H CPUs and companion power supply modules.
  • Expansion Bus Interface: Built-in port for direct connection to CS1W-BI series expansion racks via standard expansion cables.
  • Rigid Mechanical Construction: Heavy-gauge chassis designed to resist torsional stress and vibration in control panels.
  • High-Speed Communication Bus: Low-latency parallel bus architecture ensures fast update cycles for dense I/O configurations.

Applications

  • Centralized Factory Automation: Houses process control systems for automotive assembly, material handling, and packaging machinery.
  • Water and Wastewater Processing: Serves as the robust central rack for localized telemetry, pumps, and treatment controllers.
  • Power Plant Auxiliary Controls: Reliable platform for non-safety-critical balance of plant (BOP) monitoring and sequencing systems.
  • HVAC and Environmental Control: Direct management of large-scale industrial chilling, heating, and air filtration plants.

Technical Specifications

Parameter Specification
Manufacturer Omron
Model Number CS1W-BC053
Product Series CS1 Series (CS1G / CS1H)
Backplane Type CPU Backplane
Number of I/O Slots 5 slots (excluding CPU and Power Supply slots)
Power Supply Slot 1 (Requires CS1 Series Power Supply Module)
CPU Slot Compatibility CS1G-CPU, CS1H-CPU
Expansion Capability Supported (via standard CS1W expansion bus connector)
Mounting Method M4 screws (panel mounting) or DIN rail via optional mounting brackets
Operating Temperature 0 to 55 degC
Net Dimensions (W x H x D) 294 mm x 130 mm x 80 mm
Shipping Weight (Calculated) 1.0 kg
Package Dimensions (Calculated) 320 mm x 160 mm x 110 mm

Empirical Engineering Insights

Alternative Models & Compatibility

While the CS1W-BC053 is the standard 5-slot CPU backplane, environments requiring more spatial flexibility can scale to the 8-slot (CS1W-BC083) or 10-slot (CS1W-BC103) variants. Note that standard CS1W-BC backplanes are built for simplex systems; they cannot be substituted for CS1D-BC duplex backplanes when configuring hot-standby redundant CPU systems.

Application Pitfalls & Engineering Notes

Engineers must calculate the total current consumption of all proposed modules (CPU, special I/O, communication cards, and standard I/O) against the output power limits of the mounted power supply module. Ensure that both the 5V DC and 26V DC limits are not breached, particularly when utilizing high-density analog modules or network communication cards on the 5-slot bus.

Commissioning & Wiring Tips

To mitigate electrical noise, ensure that the functional ground (FG) and protective ground (GR) terminals of the mounted power supply module are wired directly to a low-resistance earth ground point using heavy-gauge wire (minimum 2 mm squared). Failure to ground the system adequately can result in communication dropouts or transient bus faults across the backplane slots.

Installation Guidelines

CRITICAL WARNING

Disconnect all primary and auxiliary AC/DC power sources feeding the control panel prior to mounting, removing, or wiring any modules onto the CS1W-BC053 backplane. Failure to completely de-energize the system can result in severe electric shock, permanent damage to the CPU backplane contacts, or processor fault states.

1
Mechanical Mounting: Securely bolt the backplane to the control panel backplate using M4 screws in the designated mounting holes. Ensure the mounting plate is clean, flat, and free of paint at the ground contact points to ensure optimal grounding.
2
Power Supply Assembly: Insert the Omron power supply module into the leftmost designated power slot and secure it with its integrated locking mechanisms and terminal screws.
3
CPU and Module Allocation: Slide the CS1 CPU module into the slot adjacent to the power supply. Install subsequent I/O and communication modules into slots 0 through 4, making sure that each module clicks firmly into position and its locking levers are fully engaged.
4
Bus Expansion Configuration: If expanding to secondary racks, remove the protective cover from the expansion connector on the right side of the backplane and firmly seat the CS1W-CN expansion cable, tightening the securing screws.
Loading product navigation…

Can I use standard C200H series I/O modules on the CS1W-BC053 backplane?

Yes. The CS1W-BC053 backplane is designed to accept both CS1-specific modules and standard C200H / C200HW I/O and Special I/O units, allowing for easy legacy system integration.

How do I address the slots on the CS1W-BC053 CPU backplane?

The slots are addressed sequentially from left to right, starting at slot 0 (immediately adjacent to the CPU module) through slot 4. Power supply and CPU slots do not count as assignable I/O slots.

What happens if I exceed the power consumption limits of the backplane bus?

Exceeding the power limits will cause the power supply module to enter overcurrent protection mode, resulting in system shutdown, intermittent CPU watchdog faults, or communication errors on the I/O bus.

Is a terminator required for the expansion port if no expansion rack is connected?

No. The expansion connector on the CS1W-BC053 does not require a physical terminator if it is running as a standalone single-rack system.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Japão

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Fluidos: Tutorial Prático

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...