1 de 4

Yokogawa AAT141-S00 CENTUM VP TC/mV Input Module (16-channel, Isolated)

Yokogawa AAT141-S00 CENTUM VP TC/mV Input Module (16-channel, Isolated)

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: Yokogawa

  • Nº do Produto: AAT141-S00

  • País de origem:Japão

  • Tipo de Produto: TC/mV Input Modules

  • Pagamento: T/T, Western Union

  • Peso: 200g

  • Dimensões: 32.8 x 130 x 125.5 mm (W x H x D)

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

The Yokogawa AAT141-S00 is a 16-channel isolated thermocouple and millivolt input module designed for FIO systems within CENTUM VP field control stations. It functions as a signal converter by inputting field temperature and voltage signals into internal data for the Field Control Station (FCS). The AAT141-S00 module receives signals from thermocouple types J, K, E, B, R, S, T, and N, as well as mV voltage spans ranging from -100 to 150 mV and -20 to 80 mV. It supports dual-redundant configuration and connects externally via a pressure clamp terminal block.

Features

  • 16 isolated input channels for thermocouple and mV signals.
  • Software-selectable TC/mV input types individually configured for CH1 to CH16.
  • Dual-redundant configuration capability.
  • Dedicated pressure clamp terminal external connection interface.
  • Software-configurable burnout detection (UP/DOWN/Not available) for all channels.

Applications

  • Process temperature monitoring using thermocouples.
  • Millivolt analog input signal interfacing in CENTUM VP FIO DCS environments.
  • High-reliability industrial control systems requiring isolated I/O modules.

Ordering Information

Model Suffix Codes Option Codes Description
AAT141     TC/mV Input Module (16-channel, Isolated)
Suffix -S   Standard type
  0   With no explosion protection
  0   Basic type

Technical Specifications

Category Item Specification
Basic Specifications Manufacturer Yokogawa
  Model AAT141-S00
  Number of Input Channels 16, isolated
Input Specifications Input Signal

TC: JIS C1602:1995, IEC584:1995 Type J, K, E, B, R, S, T, N


 

mV: -100 to 150 mV, -20 to 80 mV

  Switching Input Signals TC/mV can be set individually for CH1 to CH16
  Allowable Input Voltage +/-5 V
  Input Resistance (Power ON/OFF) 2 MOhm or larger
Performance Accuracy

+/-30 uV (TC)


 

+/-80 uV for span (-100 to 150 mV)


 

+/-30 uV for span (-20 to 80 mV)

  Reference Junction Compensation Accuracy Within +/-1 degC (varies depending on installation and ambient temperature)
  Allowable Total Resistance 1000 Ohm or less (signal source plus wiring)
  Effect of Signal Source Resistance +/-20 uV per 1000 Ohm (+/-40 uV in dual-redundant configuration)
  Temperature Drift

+/-80 uV/10 degC (-100 to 150 mV input)


 

+/-30 uV/10 degC (TC/-20 to 80 mV input)

  Data Update Period 1 s
  Burn-out Detection All channels can be set together (Not available/available UP/DOWN), Detection time: 60 s
Electrical & Insulation Withstanding Voltage Between input and system: 1500 V AC, for 1 minute
  Maximum Current Consumption 450 mA (5 V DC)
Physical Specifications Weight 0.2 kg
  External Connection Pressure clamp terminal

Installation Guidelines

  • Use a non-ground type thermocouple (TC) because the device is an isolated type module; using ground type TC on multiple channels causes temperature errors due to multi-point ground.
  • Ensure proper installation onto supported ESB, Optical ESB, or ER bus node units.
  • Maintain matching wiring resistance for signal cables to ensure measurement accuracy.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Yokogawa AAT141-S00 CENTUM VP TC/mV Input Module (16-channel, Isolated)

What input signal types are supported by the module?

The module supports thermocouple types J, K, E, B, R, S, T, and N, as well as mV voltage inputs ranging from -100 to 150 mV and -20 to 80 mV.

Why must non-ground type thermocouples be used with this module?

Because the module is an isolated type, using a ground type thermocouple across multiple channels causes temperature measurement errors due to multi-point grounding.

What is the maximum current consumption for the device?

The maximum current consumption is 450 mA at 5 V DC.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendemos mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Aceitamos devoluções de produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso site oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Japão

Produtos Visualizados Recentemente

Conhecimento técnico

Modernização das IHMs Bailey INFI 90 Symphony executadas no OpenVMS Alpha

Um guia prático para substituir estações de operação Bailey Symphony antigas que rodam no OpenVMS Alpha. Ele compara a emulação de Alpha, a migração para OpenVMS x86, a reimplantação em OPC e a...

Por que os dados de manutenção são essenciais para a confiabilidade industrial

Os dados de manutenção conectam ordens de serviço, sinais de sensores, histórico de ativos, custos e conhecimento dos técnicos. Quando bem utilizados, melhoram o planejamento, a confiabilidade, a...

Atuadores elétricos projetados para substituir sistemas de energia fluida: um guia prático de automação industrial

Este artigo explica como atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações matemáticas usando o OpenPLC para aplicações de automação industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas fundamentais, como adição, subtração, multiplicação, divisão, módulo e exponenciação, na automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação de CLPs em FBD: Aplicações Industriais Práticas além da Lógica Básica

O artigo explica várias funções avançadas de lógica booleana usadas na programação de CLPs, além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas-verdade,...

Lógica booleana na programação de CLPs: entendendo as portas lógicas em FBD

A lógica booleana é a base de todo programa de CLP. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem às...