1 จาก 1

Beckhoff EL3443-0011 EtherCAT Terminal 3-channel Analog Input Power Measurement Terminal

Beckhoff EL3443-0011 EtherCAT Terminal 3-channel Analog Input Power Measurement Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL3443-0011

  • Country of origin:เยอรมนี

  • Product Type: EtherCAT Terminals

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 120 mm x 80 mm x 25 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

ปริมาณ
ดูรายละเอียดทั้งหมด

Designed for precise 3-phase AC/DC grid analysis, the Beckhoff EL3443-0011 functions as a high-performance power measurement terminal within the EtherCAT I/O system. This module enables direct measurement of current and voltage in supply networks, calculating key electrical parameters with high resolution and transmitting them directly to the controller via the high-speed EtherCAT bus.

Key Features

  • 3-channel voltage and 3-channel current measurement for comprehensive 3-phase power analysis.
  • High-resolution 24-bit analog-to-digital conversion for precise grid diagnostics.
  • Comprehensive parameter calculation including active, reactive, and apparent power, energy, cos phi, frequency, and harmonic analysis up to the 40th harmonic.
  • Mains monitoring capabilities with precise zero-voltage crossing detection.
  • Supports optional single-phase operation for versatile system integration.

Applications

  • Industrial power monitoring and energy management systems (EMS).
  • Grid quality analysis in manufacturing plants and substations.
  • Machine-level consumption tracking and predictive maintenance.
  • Integration with wind turbines, solar inverters, and generator sets.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff
Model EL3443-0011
Number of Inputs 3 x current, 3 x voltage
Technology 3-phase power measurement
Measuring Voltage max. 480 V AC 3-phase (ULX-N: max. 277 V AC / 240 V DC)
Measuring Current 100 mA (AC/DC), via measuring transformers x A / 100 mA
Resolution 24 bit
Measuring Error 0.3% relative to full scale value (U/I), 0.6% calculated value
Update Interval One mains period (20 ms at 50 Hz)
Update Time Net-synchronous
Electrical Isolation 2500 V
Current Consumption E-bus typ. 120 mA
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95 %, non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
Material Polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Shipping Weight 2.0 kg
Package Dimensions (Calculated) 120 mm x 80 mm x 25 mm

Connection Specifications

Conductor Type Cross-Section Range Stripping Length
Solid Conductor (s) 0.08 to 2.5 mm2 (AWG 28 to 14) 8 to 9 mm
Stranded Conductor (st) 0.08 to 2.5 mm2 (AWG 28 to 14) 8 to 9 mm
Flexible Conductor with Ferrule (f) 0.14 to 1.5 mm2 (AWG 26 to 16) 8 to 9 mm

Empirical Engineering Insights

Alternative Models & Compatibility

The EL3443-0011 is specifically calibrated for 100 mA current transformer (CT) secondary outputs. It must not be confused with the standard EL3443-0000 (which supports 1 A or 5 A CTs). Attempting to connect a 1 A/5 A CT directly to the EL3443-0011 will saturate the inputs and can permanently damage the internal shunt resistors.

Application Pitfalls & Engineering Notes

When measuring highly distorted grids, ensure that the harmonic analysis (up to the 40th harmonic) does not exceed the processing bandwidth of your TwinCAT cycle time. If cycle times are set too low, high-frequency CoE uploads of harmonic data can cause E-bus communication timeouts.

Commissioning & Wiring Tips

Always ensure that the current transformer polarity (K-L / P1-P2) matches the voltage phase allocation. Incorrect polarity or mismatched phases will result in negative active power readings and incorrect power factor (cos phi) calculations in the TwinCAT System Manager.

Installation Guidelines

CRITICAL WARNING: Risk of fatal electrical shock and equipment destruction. Always de-energize all voltage measurement lines and current transformer primary circuits before installing, removing, or wiring the terminal. Never open the secondary circuit of an active current transformer, as dangerously high open-circuit voltages will occur. Ensure the E-bus power contacts are completely isolated before mounting.
1
Mount the EL3443-0011 onto a standard 35 mm DIN rail (conforming to EN 60715) by sliding it until the lock mechanism engages securely.
2
Connect the voltage measurement lines to the designated terminals, ensuring correct phase assignment (L1, L2, L3, N).
3
Connect the 100 mA secondary outputs of your current transformers to the current inputs, observing correct polarity.
4
Power up the E-bus and configure the terminal parameters in TwinCAT System Manager, setting the correct transformer ratios.

What is the maximum voltage rating for the EL3443-0011?

The terminal supports a maximum measuring voltage of 480 V AC 3-phase. For UL applications, the maximum phase-to-neutral voltage is 277 V AC and 240 V DC.

Can I use standard 1 A or 5 A current transformers with this module?

No, this model is designed specifically for 100 mA AC/DC secondary current inputs. Connecting 1 A or 5 A transformers directly will damage the internal shunt circuitry.

What parameters are calculated by the internal processor?

It calculates active, reactive, and apparent power/energy, power factor (cos phi), frequency, total harmonic distortion (THD), and individual harmonics up to the 40th harmonic.

การจัดส่งด่วนทั่วโลก

  • การจัดส่งมาตรฐาน: 4-6 วันทำการ ผ่าน DHL, FedEx และ UPS
  • จัดส่งด่วน: จัดส่งในวันเดียวกันสำหรับคำสั่งซื้อที่มีในสต็อกและสั่งก่อนเวลา 14:00 น. (GMT+8)
  • ครอบคลุมทั่วโลก: ให้บริการมากกว่า 150 ประเทศ รวมถึงการจัดส่งด่วนไปยังซาอุดีอาระเบียและสหรัฐอาหรับเอมิเรตส์

การคืนสินค้าและการรับประกัน

  • การรับประกัน 30 วัน: รับคืนสินค้าที่มีในสต็อกในบรรจุภัณฑ์เดิมที่ปิดผนึกจากโรงงาน
  • การรับประกัน 12 เดือน: อะไหล่อุตสาหกรรมทุกชิ้นได้รับการรับประกันทางเทคนิคจากผู้เชี่ยวชาญของเรา

คำสั่งซื้อจะถูกดำเนินการและจัดส่งในวันจันทร์ถึงวันศุกร์ (ไม่รวมวันหยุดราชการ)


สำหรับคุณสมบัติครบถ้วน ค่าธรรมเนียมการเติมสินค้าใหม่ และรายละเอียดการคืนสินค้าระหว่างประเทศ กรุณาดูที่เว็บไซต์อย่างเป็นทางการของเรา นโยบายการคืนเงินและการคืนสินค้า .

TECHNICAL SPECIFICATIONS

Country of origin
เยอรมนี

สินค้าที่ดูล่าสุด

ความรู้ทางเทคนิค

ตัวกระตุ้นไฟฟ้าที่ออกแบบมาเพื่อทดแทนระบบพลังงานของเหลว: คู่มือการทำงานอัตโนมัติในอุตสาหกรรมอย่างเป็นประโยชน์

บทความนี้อธิบายถึงวิธีที่แอคชูเอเตอร์ไฟฟ้าแบบบูรณาการ เช่น ซีรีส์ e-Actuator ของ SMC กำลังเปลี่ยนแปลงการควบคุมการเคลื่อนที่ในอุตสาหกรรมโดยการทดแทนระบบนิวเมติกและไฮดรอลิกแบบดั้งเดิม...

การดำเนินการทางคณิตศาสตร์โดยใช้ OpenPLC สำหรับแอปพลิเคชันระบบอัตโนมัติในอุตสาหกรรม

บทความนี้อธิบายวิธีที่ระบบ PLC ดำเนินการคำนวณทางคณิตศาสตร์พื้นฐาน เช่น การบวก การลบ การคูณ การหาร โมดูลัส และการยกกำลังในระบบอัตโนมัติอุตสาหกรรม...

ตรรกะบูลีนขั้นสูงด้วยการเขียนโปรแกรม FBD PLC: การประยุกต์ใช้งานในอุตสาหกรรมที่เกินกว่าตรรกะพื้นฐาน

บทความนี้อธิบายฟังก์ชันตรรกะบูลีนขั้นสูงหลายอย่างที่ใช้ในการเขียนโปรแกรม PLC นอกเหนือจากการดำเนินการพื้นฐานอย่าง AND, OR และ NOT โดยครอบคลุมถึงการใช้เครื่องมือต่างๆ เช่น ตารางความจริง มัลติเพล็กเซอร์...

ตรรกะบูลีนในการเขียนโปรแกรม PLC: ทำความเข้าใจเกตตรรกะ FBD

ตรรกะบูลีนเป็นพื้นฐานของโปรแกรม PLC ทุกโปรแกรม ตั้งแต่การควบคุมเครื่องจักรง่ายๆ ไปจนถึงระบบอัตโนมัติในอุตสาหกรรมที่ซับซ้อน...

คู่มือเชิงลึกเกี่ยวกับไฟร์วอลล์อุตสาหกรรมและการแบ่งส่วนเครือข่าย OT

ไฟร์วอลล์อุตสาหกรรมมีบทบาทสำคัญในความปลอดภัยไซเบอร์ของ OT โดยปกป้องเครือข่าย PLC, DCS และ SCADA ผ่านการแบ่งส่วน การควบคุมการเข้า/ออก และการผสานรวม IDS/IPS ที่สอดคล้องกับหลักการ IEC 62443

คู่มือการใช้งานกริปเปอร์หุ่นยนต์: ตั้งแต่การจับที่ละเอียดอ่อนจนถึงระบบอัตโนมัติสำหรับงานหนัก

กริปเปอร์หุ่นยนต์สมัยใหม่กำลังพัฒนาก้าวข้ามกรามกลไกแบบดั้งเดิม ตั้งแต่ระบบกาวที่ได้แรงบันดาลใจจากจิ้งจกและกริปเปอร์นุ่มที่ใช้ในอาหาร ไปจนถึงเครื่องมือคลังสินค้าที่ขับเคลื่อนด้วย AI...