ABB

ABB PSTX840-600-70 1SFA898119R7000 Softstarter

SKU 1SFA898119R7000

Stokta
  • 12-month warranty
  • Free returns within 30 days
  • Üretici: ABB

  • Ürün No.: 1SFA898119R7000

  • Menşei ülke:İsveç

  • Ürün Türü: Three-Phase Softstarter

  • Ödeme: T/T, Western Union

  • Ağırlık: 46500g

  • Boyutlar: 435 mm x 493 mm x 369 mm

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Description

The ABB PSTX840-600-70 (product ID 1SFA898119R7000 / 1SFA 8981 19 R7000) is a three-phase PSTX series softstarter engineered for controlled starting, stopping, and protection of medium- to large-sized three-phase AC induction motors. Operating across a main circuit voltage range of 208 to 600 V AC at 50/60 Hz with a 100 to 250 V AC control supply, the unit delivers a rated operational current of 840 A in an in-line connection (250 kW at 230 V, 450 kW at 400 V, and 600 kW at 500 V) or 1455 A in an inside-delta connection (450 kW at 230 V, 800 kW at 400 V, and 1000 kW at 500 V).

Equipped with three-phase voltage-ramp and torque-control algorithms, the PSTX840-600-70 integrates a built-in bypass contactor to minimize power losses during continuous running and simplify panel wiring. Operators interact via a detachable full-graphic display rated IP66 and UL Type 4X for outdoor panel mounting, while system integration is supported through hardwired Start/Stop/Reset inputs, three programmable digital inputs, four signaling relays, an analog output (0 to 10 V, 0 to 20 mA, or 4 to 20 mA), built-in Modbus RTU, and optional Anybus communication modules.

Features

  • Three-phase motor control supporting soft start and soft stop via voltage ramp or torque control
  • Built-in bypass for reduced heat dissipation, energy savings, and simplified cabinet installation
  • High current capacity rated at 840 A in-line and 1455 A inside-delta with a starting capacity of 4 x Ie for 10 seconds
  • Detachable full-graphic HMI display with IP66 and UL Type 4X outdoor environmental rating
  • Built-in electronic overload protection (EOL) with dual overload curves for start and run phases
  • Advanced motor control modes including kickstart, forward/reverse slow-speed jog, dynamic braking, standstill brake, pump cleaning, motor heating, sequence start, emergency/fire pump mode, and two-phase limp mode
  • Comprehensive electrical and thermal protection covering phase reversal, current/voltage imbalance, underload, locked rotor, ground fault, thyristor overload, and PTC/PT-100 temperature inputs
  • Built-in Modbus RTU communication plus support for optional Anybus modules (Profinet, Profibus, Modbus TCP, EtherNet/IP, EtherCAT, DeviceNet, CANopen, BACnet-IP, and BACnet-MSTP)
  • Four integrated status signaling relays (Run, By-pass/TOR, Fault, Overload) and configurable analog output (0 to 10 V, 0 to 20 mA, 4 to 20 mA)

Applications

  • Centrifugal and positive-displacement pumps, including municipal water systems and emergency/fire pump installations
  • Industrial ventilation fans, exhaust blowers, and HVAC air handling units
  • Rotary screw, reciprocating, and centrifugal air and gas compressors
  • Heavy-duty belt conveyors, crushers, and bulk material handling systems
  • High-inertia three-phase industrial machinery operating on 208 to 600 V AC mains

Technical Specifications

Attribute Specification
Manufacturer ABB
Model / Type Designation PSTX840-600-70
Product ID / Order Code 1SFA898119R7000 / 1SFA 8981 19 R7000
EAN 7320500510421
Product Series PSTX Softstarters (PSTX840)
Product Type Three-Phase Softstarter
Rated Operational Voltage 208 to 600 V AC
Rated Frequency 50/60 Hz (Main Circuit)
Rated Control Supply Voltage (Us) 100 to 250 V AC, 50/60 Hz
Rated Control Circuit Voltage (Uc) 24 V DC
Rated Operational Current - In-Line (Ie) 840 A
Rated Operational Power - In-Line (Pe) 250 kW (at 230 V); 450 kW (at 400 V); 600 kW (at 500 V)
Rated Operational Current - Inside Delta 1455 A
Rated Operational Power - Inside Delta 450 kW (at 230 V); 800 kW (at 400 V); 1000 kW (at 500 V)
UL/CSA Horsepower Rating (Three-Phase) 300 Hp (200 to 208 V AC); 350 Hp (220 to 240 V AC); 700 Hp (440 to 480 V AC); 800 Hp (550 to 600 V AC)
Maximum Operating Voltage (UL/CSA) 600 V (Main Circuit)
Service Factor 100%
Starting Capacity at Maximum Rated Current (Ie) 4 x Ie for 10 s
Ramp Time 1 to 120 s
Initial Voltage During Start 10 to 99 V
Step Down Voltage Special Ramp 100 to 10%
Current Limit Function 1.5 to 7.5 x Ie
Built-in Bypass Yes (with Inside Delta connection switch)
Overload Protection Built-in electronic overload protection (EOL), dual overload (start and run)
Signal Relays Run Signal Relay, By-pass (TOR) Signal Relay, Fault Signal Relay, Overload Signal Relay (NO contacts)
Analog Outputs 0 to 10 V, 0 to 20 mA, 4 to 20 mA
LED Status Indicators Ready to Start/Standby ON (Green), Running R (Green), Protection (Yellow), Fault (Red)
Communication Protocols Modbus-RTU (built-in); Modbus-TCP, EtherNet/IP, EtherCAT, DeviceNet, CANopen, Profibus, Profinet, BACnet-IP, BACnet-MSTP (via Anybus / Fieldbus plug)
HMI Display Detachable full-graphic display (IP66 and UL Type 4X outdoor rating)
Main Circuit Terminal Type Busbars (Bars)
Tightening Torque (Main Circuit) 45 N-m (398.3 lb-in UL/CSA)
Connecting Capacity (Control & Supply Circuits) Rigid 1 x 2.5 mm2
Degree of Protection Main Terminals: IP00 (IEC 60529, IEC 60947-1, EN 60529); Graphic Display: IP66 / Type 4X
Ambient Operating Temperature -25 to +60 degC
Ambient Storage Temperature -40 to +70 degC
Dimensions (W x H x D) 435 mm x 493 mm x 369 mm
Net Weight 46.5 kg
Shipping Package Dimensions & Gross Weight 600 mm (W) x 616 mm (D) x 800 mm (H); 58.5 kg gross weight
Customs Tariff Number 85371091

Connections/Interfaces

Connector Pin Function
Main Power Busbars Three-phase line and motor load busbar connections rated up to 840 A in-line (1455 A inside-delta), tightened to 45 N-m
Control Supply Terminals (Us) 100 to 250 V AC (50/60 Hz) auxiliary control power input accepting rigid 1 x 2.5 mm2 conductors
Control Circuit & Digital Inputs (Uc) 24 V DC control circuit with hardwired Start, Stop, Fault Reset, and three programmable digital inputs (rigid 1 x 2.5 mm2)
Signal Output Relays Normally Open (NO) relay outputs for Run, By-pass / Top of Ramp (TOR), Fault, and Overload status indication
Analog Output Terminals Configurable analog feedback output supporting 0 to 10 V, 0 to 20 mA, or 4 to 20 mA signals
Temperature Sensor Inputs Dedicated motor thermal protection inputs supporting PTC and PT-100 sensors
Built-in Fieldbus Interface Integrated Modbus RTU serial communication interface and external Fieldbus plug adaptor support (PS-FBPA)
Anybus & HMI Expansion Ports Front expansion slot for optional Anybus industrial Ethernet/fieldbus modules and port for the detachable IP66 graphic display or PSCA-1 USB cable

Installation Guidelines

  • Enclosure Protection: Because the main power terminals carry an IP00 protection rating, install the softstarter inside a suitable industrial control enclosure; optionally fit terminal shrouds (LT750-AC / LT750-AL) and terminal enlargements (LW750) or CuAl cable lug kits (1SDA013956R1 / 1SDA023380R1) for finger protection and conductor termination.
  • Busbar & Control Wiring Torque: Tighten main circuit busbar connections to 45 N-m (398.3 lb-in per UL/CSA specifications) and terminate control/supply wiring using rigid 1 x 2.5 mm2 conductors.
  • Connection Configuration: Select between standard in-line connection (up to 840 A) and inside-delta connection (up to 1455 A) using the integrated inside-delta configuration switch prior to commissioning.
  • Remote HMI Mounting: Detach the IP66 / Type 4X rated graphic display from the softstarter body and mount it on the cabinet door for external operator access and diagnostics without opening the enclosure.
  • Thermal Clearance & Operating Environment: Maintain ambient air temperatures within -25 to +60 degC inside the panel during operation.

Compliance and Certifications

  • CE: Compliant with European Union directives (Declaration of Conformity 2CMT005209)
  • UL / cULus: Rated for UL/CSA three-phase motor control up to 600 V AC and 800 Hp
  • CCC and CQC: Certified under China Compulsory Certification (2020980304001095 / 2020980304001491) and CQC (CQC2015010304830300 / CQC2015010304830295)
  • DNV: Marine and offshore type approval certificate TAE000087N
  • RoHS and REACH: Compliant with EU RoHS Directive 2011/65/EU and Amendment 2015/863 (2CMT2022-006500), EU REACH (2CMT2022-006481), and US TSCA (2CMT2023-006524)
  • Environmental & Data Compliance: ABB EcoSolutions validated with 81.9% recyclability per EN 45555, WEEE Category 5 B2B compliance, and EU Data Act compliance (1SFC132498M0201)

FAQ

What are the current and power ratings for the ABB PSTX840-600-70 softstarter?

The ABB PSTX840-600-70 (1SFA898119R7000) is rated for 840 A in an in-line connection (250 kW at 230 V, 450 kW at 400 V, 600 kW at 500 V) and up to 1455 A in an inside-delta connection (450 kW at 230 V, 800 kW at 400 V, 1000 kW at 500 V).

Does the PSTX840-600-70 include a built-in bypass and electronic overload protection?

Yes, the softstarter features an integrated bypass contactor to reduce running energy losses along with built-in dual electronic overload protection (EOL) for both start and run phases.

What communication protocols and control voltages are supported by 1SFA898119R7000?

It operates on a 100 to 250 V AC (50/60 Hz) control supply with a 24 V DC control circuit, includes built-in Modbus RTU, and supports Anybus modules for Profinet, Profibus, Modbus TCP, EtherNet/IP, EtherCAT, DeviceNet, CANopen, and BACnet.

Can the graphic display on the PSTX840-600-70 be mounted on a panel door?

Yes, the softstarter includes a detachable full-graphic display rated IP66 and UL Type 4X for outdoor and cabinet door mounting.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

ABB PSTX840-600-70 1SFA898119R7000 Softstarter

Miktar
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 -ın, -in, -un, -ün (bağlama göre değişir) 2
Stokta sadece 20 adet kaldı
Miktar
Tüm detayları görüntüle
Loading product navigation…

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenir.

Siparişler Pazartesi-Cuma (resmi tatiller hariç) işlenir ve teslim edilir.


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

Teknik bilgi

1746-A7 Şasi Değişimi Kontrolleri: Yuvalar, Güç ve Ara Bağlantılar

Allen-Bradley 1746-A7’yi değiştirmek için bir mühendislik kontrol listesi: şasi serisini, arka düzlem yükünü, yuva planını, bağlantı kablolarını, montajı, topraklamayı ve teslim alınma durumunu...

IC200MDL650 Yedek Kontrolleri: Mantık Polaritesi, Filtreler ve Ortak Hatlar

Revizyona bağlı negatif mantığı, dört yaygın grubu, 24 VDC eşik değerlerini, giriş filtrelemesini, taşıyıcı kontrollerini ve devreye alma kayıtlarını kapsayan GE Fanuc IC200MDL650 için saha...

IC697CPX935 Değişim Kontrolleri: Bellek, Bağlantı Noktaları ve Raf Gücü

Hızlı belleği, ürün yazılımına bağlı seri iletişim davranışını, raf gücünü, soğutmayı, G/Ç mimarisini ve yedekleme kayıtlarını kapsayan, sahaya yönelik bir IC697CPX935 değiştirme kılavuzu.

IC693DSM324 Değişim Kontrolleri: FSSB, Ürün Yazılımı ve Takipçi Kontrolü

Seri 90-30 ana bilgisayar kontrollerini, FSSB servo zinciri kayıtlarını, 5 V güç bütçesini, firmware sınırlarını, takipçi kontrolünü ve devreye almayı kapsayan, saha odaklı IC693DSM324 değiştirme...

HIMA F3430 Yedek Kontrolleri: Kontak Değerleri ve Güvenlik Sınırları

Röle kontak değerleri, DC yük değer düşürme, sigortalama, F3330/F3331 farkları, güvenlik kısıtlamaları ve devreye alma kayıtlarını kapsayan, sahada kullanıma yönelik HIMA F3430 değiştirme kılavuzu.

IC697PWR710 Değiştirme Kontrolleri: Yük Bütçesi ve Çift Raf Sınırları

5 V yük hesaplamalarını, çift raf sınırlarını, uzatma kablolarını, giriş kontrollerini, koruma davranışını ve donanım revizyonu risklerini kapsayan, saha odaklı bir IC697PWR710 değiştirme kılavuzu.