1 از 1

Omron E5CC-RX2ADM-800 E5CC Series Digital Temperature Controller

Omron E5CC-RX2ADM-800 E5CC Series Digital Temperature Controller

فقط 7 قلم کالا در انبار باقی مانده است
  • تولیدکننده: Omron

  • شماره محصول: E5CC-RX2ADM-800

  • کشور سازنده:ژاپن

  • نوع محصول: Digital Temperature Controllers

  • پرداخت: حواله بانکی (T/T)، وسترن یونیون

  • وزن: 130g

  • ابعاد: 110 mm x 65 mm x 65 mm

  • بندر حمل و نقل: شیامن

  • گارانتی: ۱۲ ماه

تعداد
مشاهده جزئیات کامل

Description

Designed for highly precise thermal process regulation, the Omron E5CC-RX2ADM-800 digital temperature controller delivers advanced PID control within a compact 48x48 mm (1/16 DIN) form factor. This instrument features a high-contrast white LCD display with 15.2 mm character heights, ensuring maximum legibility in high-density control panels. Operating on a 24 VAC/VDC auxiliary power supply, the unit integrates 2-PID control logic with automatic tuning to minimize overshoot and stabilize temperature fluctuations in demanding thermal systems. Built with a relay control output and dual auxiliary outputs, this hardware is engineered for direct integration into industrial machines, packaging lines, and environmental chambers.

Features

  • Universal Sensor Input: Direct support for multi-range thermocouples, platinum resistance thermometers (RTDs), and analog current/voltage inputs.
  • Dual Auxiliary Relays: Two independent auxiliary relay outputs for alarms, limit controls, or system interlocks.
  • Advanced Control Algorithms: High-speed sampling loop of 50 ms combined with 2-PID control and auto-tuning (AT) capabilities.
  • Enhanced Visibility: Large, easy-to-read white PV display segment contrasted against a dark background.
  • Compact Depth: Only 60 mm depth behind the panel, minimizing enclosure footprint and maximizing wiring space.

Applications

  • Plastic Extrusion & Molding: Accurate barrel zone heating control and die temperature stabilization.
  • Packaging Machinery: Precise sealing bar temperature management to ensure consistent package integrity.
  • Industrial Ovens & Furnaces: High-reliability thermal profiling and multi-stage heating curve regulation.
  • Food & Beverage Processing: Sanitation-compliant temperature monitoring and pasteurization loop control.

Technical Specifications Table

Parameter Specification Value
Manufacturer Omron
Model Code E5CC-RX2ADM-800
Supply Voltage 24 VAC (50/60 Hz) / 24 VDC
Operating Voltage Range 85% to 110% of rated supply voltage
Power Consumption Max 4.1 VA (24 VAC) / Max 2.3 W (24 VDC)
Control Output 1 Relay output (SPST-NO, 250 VAC, 3 A resistive load)
Auxiliary Outputs 2 Relay outputs (SPST-NO, 250 VAC, 3 A resistive load)
Control Method ON/OFF control or 2-PID control (with auto-tuning)
Sampling Period 50 ms
Terminal Connection Type Screw terminal block (M3)
Front Panel Dimensions 48 x 48 mm
Operating Ambient Temp -10 to 55 degC (with no condensation or icing)
Shipping Weight (Calculated) 0.35 kg
Package Dimensions (Calculated) 110 mm x 65 mm x 65 mm

Empirical Engineering Insights

Alternative Models & Compatibility

The E5CC-RX2ADM-800 serves as a direct functional replacement for legacy models such as the E5CN-R2MD-500 series. However, when migrating to the E5CC platform, verify the wiring terminations: the E5CC uses a different physical pin layout relative to older generations. If your application relies on voltage pulse output for solid-state relays (SSRs), do not use the RX model; select the E5CC-QX2ADM-800 instead to prevent damage to the relay mechanism caused by high-frequency switching.

Application Pitfalls & Engineering Notes

Because this model is rated for 24 VAC/VDC power, it is highly sensitive to voltage drops along long DC distribution lines in control panels. Ensure that the power supply is situated close to the instrument and is isolated from heavy inductive switching devices. Running auxiliary outputs with high-current AC loads near their 3 A limit without RC snubbers will significantly shorten the electrical lifespan of the internal output relays due to contact arcing.

Commissioning & Wiring Tips

To configure parameters prior to cabinet powering, use the Omron CX-Thermo software paired with the front-panel setup port interface. This approach allows parameter configuration over a USB bus power connection, completely eliminating the need to connect 24V field power during the engineering phase. Ensure that you ground the analog shield wire of the sensor close to the panel entry point rather than routing it alongside high-voltage AC cables.

Installation Guidelines

CRITICAL WARNING: Prior to attempting physical installation, mounting, or terminal wiring, ensure that the primary electrical power source to the control cabinet is completely de-energized. Confirm the absence of residual AC/DC voltages using a calibrated digital multimeter. Failure to isolate power may cause electrical shock, physical hazard, or permanent failure of the internal logic circuits.
1
Insert the controller housing through the prepared 45x45 mm panel cutout from the front, ensuring the protective rubber gasket is correctly seated to maintain the IP66 water-resistant seal.
2
Slide the plastic mounting adapter from the rear of the panel along the controller body until the adapter clicks firmly against the panel backplate. Tighten the securing screws evenly to prevent frame distortion.
3
Terminate the universal input lines (thermocouple or RTD) using high-quality insulated crimp lugs to avoid signal noise. Route power and control output wires along dedicated low-voltage wireways separated from motor drive leads.
Loading product navigation…

Can the E5CC-RX2ADM-800 model be powered directly by standard 120 VAC or 240 VAC mains voltage?

No. The RX2ADM suffix indicates the unit is strictly designed for 24 VAC or 24 VDC auxiliary power. Connecting line voltage (100 to 240 VAC) directly to the power terminals will permanently destroy the internal electronic components.

Does this temperature controller support Pt100 RTD sensor inputs, or is it thermocouple-only?

This controller features a universal input. By configuring the input type parameter, you can configure it for multiple thermocouple types (K, J, T, E, etc.), platinum resistance thermometers (Pt100, JPt100), and analog current or voltage signals.

What is the contact rating of the primary control relay on the E5CC-RX2ADM-800?

The primary control output (Output 1) is a single-pole, single-throw, normally open (SPST-NO) relay rated for 250 VAC at 3 A under a purely resistive load.

ارسال سریع جهانی

  • تحویل استاندارد: ۴-۶ روز کاری از طریق DHL، FedEx و UPS.
  • ارسال فوری: ارسال همان روز برای سفارش‌های موجود در انبار که قبل از ساعت ۲:۰۰ بعدازظهر (GMT+8) ثبت شده‌اند.
  • پوشش جهانی: خدمات به بیش از ۱۵۰ کشور، شامل تحویل سریع به عربستان سعودی و امارات.

بازگشت کالا و گارانتی

  • ضمانت ۳۰ روزه: بازگشت کالا برای محصولات موجود در انبار با بسته‌بندی اصلی و مهر کارخانه پذیرفته می‌شود.
  • گارانتی ۱۲ ماهه: هر قطعه صنعتی با گارانتی فنی حرفه‌ای ما پشتیبانی می‌شود.

سفارش‌ها از دوشنبه تا جمعه پردازش و تحویل داده می‌شوند (به جز تعطیلات رسمی).


برای شرایط کامل واجد شرایط بودن، هزینه‌های بازگردانی و جزئیات بازگشت بین‌المللی، لطفاً سیاست رسمی ما را مشاهده کنید سیاست بازپرداخت و بازگشت کالا .

TECHNICAL SPECIFICATIONS

Country of origin
ژاپن

محصولات مشاهده‌شده اخیر

دانش فنی

عملگرهای الکتریکی طراحی شده برای جایگزینی سیالات: آموزش عملی

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

عملیات ریاضی با استفاده از OpenPLC برای کاربردهای اتوماسیون صنعتی

این مقاله توضیح می‌دهد که چگونه سیستم‌های PLC عملیات ریاضی اصلی مانند جمع، تفریق، ضرب، تقسیم، مدول و توان را در اتوماسیون صنعتی انجام می‌دهند. نشان می‌دهد که چگونه این بلوک‌های عملکردی سیگنال‌های خام...

منطق بولی پیشرفته با برنامه‌نویسی FBD PLC: کاربردهای عملی صنعتی فراتر از منطق پایه

این مقاله چندین تابع پیشرفته منطق بولی را که در برنامه‌نویسی PLC فراتر از عملیات پایه AND، OR و NOT استفاده می‌شوند، توضیح می‌دهد. همچنین نحوه استفاده از ابزارهایی مانند جداول صحت، مالتی‌پلکسرها،...

منطق بولی در برنامه‌نویسی PLC: درک گیت‌های منطقی FBD

منطق بولی پایه و اساس هر برنامه PLC است. از کنترل‌های ساده ماشین تا سیستم‌های پیچیده اتوماسیون صنعتی، دروازه‌های منطقی تعیین می‌کنند که کنترل‌کننده‌ها چگونه به ورودی‌ها و شرایط عملیاتی متغیر پاسخ...

راهنمای جامع فایروال‌های صنعتی و تقسیم‌بندی شبکه OT

فایروال‌های صنعتی نقش حیاتی در امنیت سایبری OT ایفا می‌کنند و با استفاده از تقسیم‌بندی، کنترل ورودی/خروجی و ادغام IDS/IPS مطابق با اصول IEC 62443، از شبکه‌های PLC، DCS و SCADA محافظت می‌کنند.

راهنمای گیره‌های رباتیک: از جابجایی ظریف تا اتوماسیون سنگین

گیره‌های رباتیک مدرن فراتر از فک‌های مکانیکی سنتی در حال پیشرفت هستند. از سیستم‌های چسبنده الهام‌گرفته از گکوی، گیره‌های نرم با درجه‌بندی غذایی تا ابزارهای انبار مجهز به هوش مصنوعی، فناوری‌های...