The AI845 with product ID 3BSE023675R1 is an 8-channel analog input module designed for the S800 I/O distributed system architecture. This hardware unit interfaces standard 0 to 20 mA or 4 to 20 mA current signals from field transmitters directly to the central processing controller. It incorporates dedicated HART routing capabilities per channel, enabling bi-directional communication with smart instruments over existing analog loops without altering regular process variable transmission. It provides dual-channel hardware redundancy options when paired with appropriate terminal units, maintaining active signal paths and system availability during single module exceptions.

Features

  • Provides 8 single-ended current tracking input channels supporting 0 to 20 mA or 4 to 20 mA signals.
  • Integrates channel-by-channel HART pass-through communication for asset management systems.
  • Supports hot-swapping and fully redundant configurations for uninterrupted process data acquisition.
  • Features integrated diagnostic routines to supervise open-circuit monitoring and out-of-range signal states.
  • Utilizes compact electrical termination setups using standard S800 Module Termination Units.

Applications

  • High-availability process loop telemetry inside petrochemical refining and power generation units.
  • Dual-fault tolerant interface links interfacing safety parameters with distributed control systems.
  • Asset management integration utilizing remote HART diagnostic mapping protocols.

Technical Specifications

Parameter Value
Manufacturer ABB
Model AI845
Product ID 3BSE023675R1
Series S800 I/O
Product Type Analog Input Module
Number of Channels 8 single-ended channels (redundancy supported)
Input Range 0 to 20 mA / 4 to 20 mA
Input Impedance 250 ohms
Resolution 12-bit A/D conversion
HART Protocol Support Yes, pass-through per channel
Power Requirements 24 V DC internal consumption
Degree of Protection IP20
Operating Temperature 0 to +55 degC
Storage Temperature -40 to +70 degC
Country of Origin Sweden (SE)
Weight 0.25 kg

Connections/Interfaces

Terminal Pin Function
1 Channel 1 Signal Input (+)
2 Channel 2 Signal Input (+)
3 Channel 3 Signal Input (+)
4 Channel 4 Signal Input (+)
5 Channel 5 Signal Input (+)
6 Channel 6 Signal Input (+)
7 Channel 7 Signal Input (+)
8 Channel 8 Signal Input (+)
9 to 16 Channel Signal Return / Common Ground (0V)

Installation Guidelines

  • Baseplate Insertion: Verify that the Module Termination Unit (such as TU844 or TU845) is secured onto the DIN rail before engaging the module body. Disconnect primary electrical feeds, align the plastic guide tabs, and apply uniform vertical force until the side retention latches click home.
  • Shielding Protocol: Terminate the outer metal mesh of twisted-pair instrument wires using the ground bars situated on the enclosure entry frame. Maintain single-point earth terminations at the control cabinet wall to eliminate low-frequency ground-loop feedback.
  • Redundant Configuration: To execute redundant module deployments, both units must reside in an identical, paired-slot termination cluster. Map the master/backup hierarchy inside the control programming software to handle hot-standby functions.
  • Cable Separation Routing: Route low-current operational signals in separate wiring ducts isolated from variable speed drives, bulk contactor control blocks, and heavy three-phase power buses by a minimal clear air threshold of 30 cm.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Entrée analogique S/R HART 8 canaux ABB 3BSE023675R1 AI845

Does this module supply transmitter loop power directly to 2-wire instruments?

This module acts as a current-sinking input device. Loop voltage for 2-wire transmitters must be supplied through an external 24 V DC distribution block or specialized module termination units containing integrated auxiliary distribution.

What happens to the process variable measurement if one module in a redundant pair fails?

The backplane interface switches the active signal processing path to the standby partner within milliseconds without interrupting the data stream or generating process value spikes.

Can standard 0 to 5 V or 0 to 10 V voltage inputs connect to this card?

No. This module is exclusively designed to evaluate current loop paths within the 0 to 20 mA or 4 to 20 mA operational signal ranges.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d’origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître les conditions d’éligibilité complètes, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Color pattern
Blanc
Country of origin
Suède
Power source
Alimentation DC

Produits récemment consultés

Connaissances techniques

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l'intégration IDS/IPS...

Guide des préhenseurs robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés du gecko et des pinces souples de qualité alimentaire aux outils d'entrepôt...

Retour en arrière : comment les premiers moteurs électriques ont transformé l'exploitation minière souterraine

Des compresseurs à courant continu entraînés par corde aux wagonnets de mine alimentés par batterie, les premières opérations minières ont marqué un tournant dans l’électrification industrielle. Cet...

Factory I/O : un outil moderne de simulation PLC pour la formation à l'automatisation industrielle

Factory I/O révolutionne l'enseignement des automates programmables industriels (API) en proposant des simulations industrielles 3D immersives pour les étudiants, les ingénieurs et les équipes de...