Product Overview
The FC-101P22KT4E20 (FC101P22KT4E20) is a high-efficiency VLT HVAC Basic Drive specifically engineered to optimize fan and pump performance in modern building automation systems. Delivering a robust 22.0 kW (30.0 hp) shaft output, this drive is a cornerstone for HVAC infrastructure in commercial complexes, hospitals, and data centers. By implementing intelligent variable speed control, the FC-101 series significantly reduces energy consumption and mechanical stress on ventilation systems. Its design prioritizes ease of integration and long-term reliability, ensuring that critical climate control processes remain operational while achieving a best-case efficiency of 96.8%.
Technical Configuration
The hardware architecture of the FC-101P22KT4E20 is tailored for high-density power management within an IP20 (H7 enclosure) footprint.
-
Power Profile: Engineered for 22.0 kW applications, supporting a continuous output current of 88.0 A at 40 deg C ambient temperatures, ensuring stable operation under full-load HVAC cycles.
-
Thermal Intelligence: The drive features advanced thermal management, maintaining a continuous output of 79.2 A even at elevated ambient temperatures of 50 deg C, making it suitable for mechanical rooms with limited ventilation.
-
Efficient Energy Conversion: With a typical power loss of only 804 W and an efficiency rating of 96.8%, the drive minimizes heat dissipation within the control cabinet, reducing the requirement for auxiliary cooling.
-
Wiring Versatility: The power terminals are designed to accommodate large-gauge cables up to 50 mm2 (1 AWG), allowing for secure, low-resistance connections essential for high-current industrial power distribution.
Technical Specifications
| Feature |
Specification |
| Model |
FC-101P22KT4E20 |
| Brand |
Danfoss |
| Shaft Output (kW) |
22.0 kW |
| Shaft Output (hp) |
30.0 hp |
| Enclosure Rating |
IP20 / H7 |
| Input Voltage |
3-Phase (380-480 VAC) |
| Continuous Current (40 deg C) |
88.0 A |
| Continuous Current (50 deg C) |
79.2 A |
| Max Cable Size |
50 mm2 (1 AWG) |
| Typical Efficiency |
96.8% |
| Net Weight |
36.0 kg |
| Shipping Weight |
38.0 kg |
Technical FAQs
How does the FC-101 drive handle motor cable length?
The FC-101P22KT4E20 supports up to 50 meters of shielded motor cable or 75 meters of unshielded cable. If your HVAC installation requires longer runs, an output sine-wave filter or dU/dt filter should be installed to prevent voltage spikes from reaching the motor windings.
Is the 22.0 kW rating affected by high ambient temperatures?
Yes. While the drive is rated for 88.0 A at 40 deg C, the continuous output drops to 79.2 A at 50 deg C. If the drive is installed in a high-temperature environment, ensure the motor's full-load current does not exceed the derated value.
What is the "Fire Mode" feature in this HVAC drive?
Fire Mode is a critical safety feature that allows the drive to ignore most internal protection alarms during an emergency, keeping smoke extraction fans running as long as possible to clear escape routes, regardless of damage to the drive itself.
Engineering & Installation Guide
-
Cable Termination: When connecting the 50 mm2 power cables, ensure the terminals are tightened to the manufacturer's specified torque. Loose connections at these high current levels (up to 88.0 A) will result in localized overheating and potential terminal block failure.
-
Harmonic Compliance: In large-scale HVAC projects, the cumulative effect of non-linear loads can distort the power grid. Utilize the drive’s built-in DC chokes to reduce harmonic interference (THDi), protecting sensitive electronics like PLC controllers and building management sensors on the same branch.
-
Cabinet Airflow: Given the typical power loss of 804 W, the enclosure must have adequate forced ventilation. Position the drive vertically with at least 200 mm of free space above and below the H7 enclosure to facilitate natural convection and forced cooling airflow.