Product Overview
The IC200ALG264 (IC200-ALG-264) is a high-density, 15-channel analog input module from the GE VersaMax series, specifically designed for precision monitoring of current signals. It is engineered to accept unipolar current inputs ranging from 0 to 20 mA or 4 to 20 mA, making it a critical component for processing feedback from transmitters in chemical plants, water treatment facilities, and HVAC systems. By offering 15 channels in a single compact footprint, the IC200ALG264 maximizes panel space efficiency while providing 12-bit resolution for accurate data acquisition. Its seamless integration with VersaMax CPUs and Network Interface Units (NIUs) ensures high-speed data throughput and robust performance in distributed I/O architectures.
Technical Configuration
The module features a high-density architecture where 15 channels share a common return, optimized for space-constrained installations. It utilizes a 12-bit A/D converter, providing 4,000 counts over the signal range. The module is "Hot-Swappable" when used with appropriate VersaMax terminal bases, allowing for maintenance without system shutdown. Built-in diagnostics include "Open Wire" detection for 4-20 mA mode and monitoring of the user-supplied 24 VDC power, with front-facing LED indicators for "OK" and "User Power" status to simplify field troubleshooting.
Technical Specifications
| Attribute |
Specification |
| Model |
IC200ALG264 |
| Brand |
GE Fanuc / Emerson |
| Series |
VersaMax Analog I/O |
| Input Type |
Current (Unipolar) |
| Number of Channels |
15 (Single-ended) |
| Input Range |
0 to 20 mA / 4 to 20 mA |
| Resolution |
12-bit (4,000 counts) |
| Accuracy |
+/- 0.25% of full scale (at 25 deg C) |
| Input Impedance |
250 Ohms |
| Update Rate |
13 ms for all 15 channels |
| External Power Supply |
24 VDC (+/- 15%) |
| Weight |
Approx. 0.13 kg |
Technical FAQs
Does this module require external 24 VDC to function?
Yes. The IC200ALG264 requires an external 24 VDC power supply to power the analog-to-digital conversion circuitry. This power is connected via the terminal base. If the "User Power" LED is not illuminated, the module will report zero or under-range values to the CPU.
How does the 15-channel "Common Return" affect wiring?
Unlike 8-channel isolated modules, all 15 channels on the IC200ALG264 share a single common return path. This means all field transmitters must be compatible with a shared ground system. For loops requiring full galvanic isolation between channels, a different module or external signal isolators should be used.
What happens if a 4-20 mA wire is broken?
In 4-20 mA mode, the module provides a low-range diagnostic. If the current drops below approximately 3.5 mA, the PLC will typically report a "Low Alarm" or "Open Wire" fault for that specific channel, allowing for immediate maintenance.
Engineering & Installation Guide
-
Terminal Base Selection: This high-density module must be paired with a compatible terminal base, such as the IC200TBT002 (Barrier style) or IC200TBP002 (Spring style). Ensure the base is keyed correctly to prevent accidental insertion of digital modules into the analog slot.
-
Shielding for High-Density I/O: With 15 analog signals in close proximity, crosstalk and EMI are potential risks. Use high-quality shielded twisted-pair cabling and ensure the shields are terminated at the PLC end to a dedicated earth ground bar.
-
Loop Power Considerations: If the field transmitters are "2-wire" types (loop-powered), ensure your external 24 VDC power supply has sufficient amperage to power all 15 loops simultaneously, plus the module's own power requirement (approx. 50 mA).