1 of 1

Unité d'entrée analogique Omron NX-AD2208 série NX

Unité d'entrée analogique Omron NX-AD2208 série NX

Il ne reste que 8 article(s) en stock
  • Fabricant : Omron

  • N° de produit : NX-AD2208ÿ

  • Pays d'origine :Japon

  • Type de produit : Unités d'entrée analogique

  • Paiement : Virement bancaire, Western Union

  • Poids : 70g

  • Dimensions : 12 mm x 100 mm x 71 mm

  • Port d'expédition : Xiamen

  • Garantie : 12 mois

Quantité
Voir les détails complets

Description

Precision data acquisition in modern machine control requires reliable, high-speed interfaces like the Omron NX-AD2208. This high-performance analog input unit is designed for the Omron NX Series platform, offering two differential channels dedicated to standard 4 to 20 mA analog current loops. Utilizing a high-resolution conversion of 1/30,000 and an ultra-fast conversion time of 10 us per point, it ensures rapid signal processing for demanding real-time industrial applications. The unit features flexible timing with support for both synchronous I/O refreshing and Free-Run refreshing, adapting perfectly to different system architectures via EtherCAT couplers or direct CPU connection.

Features

  • Two differential analog input channels dedicated to 4 to 20 mA signals.
  • Ultra-fast signal processing with a conversion time of 10 us per point.
  • High-resolution performance at 1/30,000 for precise process measurements.
  • Supports switching between synchronous I/O refreshing and Free-Run refreshing.
  • Screwless clamping terminal block with 8 terminals simplifies field wiring and resists vibration.
  • Integrated TS status indicator for immediate diagnostics.
  • Galvanic isolation between the input channels and the NX bus using a power transformer and digital isolator.

Applications

  • Continuous process monitoring (flow, pressure, and level transmitters).
  • High-speed industrial closed-loop feedback systems.
  • Water treatment facilities and chemical dosage monitoring.
  • OEM machinery integration with Sysmac NJ/NX controller networks.

Technical Specifications

ManufacturerModel / Part NumberProduct TypeNumber of InputsInput RangeInput TypeResolutionConversion TimeInput Conversion RangeAbsolute Maximum RatingInput ImpedanceOverall Accuracy (at 25 degC)Overall Accuracy (0 to 55 degC)Refreshing MethodIsolation MethodInsulation ResistanceDielectric StrengthPower Consumption (CPU connected)Power Consumption (Coupler connected)I/O Power Supply MethodExternal TerminalsDimensions (W x H x D)Weight
Omron
NX-AD2208
Analog Input Unit (Current)
2 points
4 to 20 mA
Differential
1/30000
10 us/point
-5% to 105% (full scale)
+/-30 mA
250 Ohms
+/-0.1% (full scale)
+/-0.2% (full scale)
Switching synchronous I/O refreshing and Free-Run refreshing
Between input and NX bus: Power = Transformer, Signal = Digital isolator (no isolation between individual input channels)
20 M Ohm min. between isolated circuits (at 100 VDC)
510 VAC between isolated circuits for 1 minute (leakage current 5 mA max.)
1.25 W max.
0.90 W max.
No supply required through terminals
Screwless clamping terminal block (8 terminals)
12 mm x 100 mm x 71 mm
0.07 kg

Installation Guidelines

  • Mounting: Mount the unit directly onto a standard 35 mm DIN rail. Ensure the interlocking side-connector blocks securely lock into adjacent NX modules.
  • Wiring: Use solid wires or stranded wires with ferrules. Push directly into the screwless clamping terminal block without using tools. To release, use a small flat-blade screwdriver on the release button.
  • Shielding: Connect the shielded outer conductor of the analog input cables to a functional ground bar to reduce electro-magnetic noise.
  • Environmental Maintenance: Maintain proper panel ventilation to ensure the operating environment remains within 0 to 55 degC.
Loading product navigation…

What is the primary input type for the Omron NX-AD2208?

The NX-AD2208 is an analog input unit configured for 2 differential current input channels supporting 4 to 20 mA signals.

What are the resolution and conversion speed specs for this module?

It features a high resolution of 1/30,000 and a high-speed conversion rate of 10 us per point.

Does the NX-AD2208 require an external I/O power supply?

No, it does not require an external I/O power supply terminal, drawing its operating power directly from the NX bus.

What refreshing methods does this analog unit support?

It supports both switching synchronous I/O refreshing and Free-Run refreshing to match controller cycle configurations.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats arabes unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
Japon

Produits récemment consultés

Connaissances techniques

Actionneurs électriques conçus pour remplacer les systèmes à fluide : un guide pratique d'automatisation industrielle

Cet article explique comment les actionneurs électriques intégrés, tels que la série e-Actuator de SMC, transforment le contrôle du mouvement industriel en remplaçant les systèmes pneumatiques et...

Opérations mathématiques avec OpenPLC pour les applications d'automatisation industrielle

Cet article explique comment les systèmes PLC réalisent des opérations mathématiques de base telles que l'addition, la soustraction, la multiplication, la division, le modulo et l'exponentiation dans...

Logique booléenne avancée avec la programmation FBD PLC : applications industrielles pratiques au-delà de la logique de base

L'article explique plusieurs fonctions avancées de la logique booléenne utilisées en programmation d'automates programmables industriels (API) au-delà des opérations de base ET, OU et NON. Il aborde...

Logique booléenne en programmation PLC : comprendre les portes logiques FBD

La logique booléenne est la base de tout programme PLC. Des commandes machines simples aux systèmes d'automatisation industrielle complexes, les portes logiques déterminent comment les contrôleurs...

Guide approfondi sur les pare-feux industriels et la segmentation des réseaux OT

Les pare-feux industriels jouent un rôle crucial dans la cybersécurité OT, protégeant les réseaux PLC, DCS et SCADA grâce à la segmentation, au contrôle des entrées/sorties et à l’intégration IDS/IPS...

Guide des pinces robotiques : de la manipulation délicate à l'automatisation lourde

Les pinces robotiques modernes évoluent au-delà des mâchoires mécaniques traditionnelles. Des systèmes adhésifs inspirés des geckos aux pinces souples de qualité alimentaire, en passant par des...