1 de 4

Yokogawa AAT141-S00 CENTUM VP TC/mV Input Module (16-channel, Isolated)

Yokogawa AAT141-S00 CENTUM VP TC/mV Input Module (16-channel, Isolated)

Il ne reste que 10 article(s) en stock
  • Fabricant : Yokogawa

  • N° de produit : AAT141-S00

  • Pays d'origine :Japon

  • Type de produit : TC/mV Input Modules

  • Paiement : Virement bancaire, Western Union

  • Poids : 200g

  • Dimensions : 32.8 x 130 x 125.5 mm (W x H x D)

  • Port d'expédition : Xiamen

  • Garantie : 12 mois

Quantité
Voir les détails complets

Description

The Yokogawa AAT141-S00 is a 16-channel isolated thermocouple and millivolt input module designed for FIO systems within CENTUM VP field control stations. It functions as a signal converter by inputting field temperature and voltage signals into internal data for the Field Control Station (FCS). The AAT141-S00 module receives signals from thermocouple types J, K, E, B, R, S, T, and N, as well as mV voltage spans ranging from -100 to 150 mV and -20 to 80 mV. It supports dual-redundant configuration and connects externally via a pressure clamp terminal block.

Features

  • 16 isolated input channels for thermocouple and mV signals.
  • Software-selectable TC/mV input types individually configured for CH1 to CH16.
  • Dual-redundant configuration capability.
  • Dedicated pressure clamp terminal external connection interface.
  • Software-configurable burnout detection (UP/DOWN/Not available) for all channels.

Applications

  • Process temperature monitoring using thermocouples.
  • Millivolt analog input signal interfacing in CENTUM VP FIO DCS environments.
  • High-reliability industrial control systems requiring isolated I/O modules.

Ordering Information

Model Suffix Codes Option Codes Description
AAT141     TC/mV Input Module (16-channel, Isolated)
Suffix -S   Standard type
  0   With no explosion protection
  0   Basic type

Technical Specifications

Category Item Specification
Basic Specifications Manufacturer Yokogawa
  Model AAT141-S00
  Number of Input Channels 16, isolated
Input Specifications Input Signal

TC: JIS C1602:1995, IEC584:1995 Type J, K, E, B, R, S, T, N


 

mV: -100 to 150 mV, -20 to 80 mV

  Switching Input Signals TC/mV can be set individually for CH1 to CH16
  Allowable Input Voltage +/-5 V
  Input Resistance (Power ON/OFF) 2 MOhm or larger
Performance Accuracy

+/-30 uV (TC)


 

+/-80 uV for span (-100 to 150 mV)


 

+/-30 uV for span (-20 to 80 mV)

  Reference Junction Compensation Accuracy Within +/-1 degC (varies depending on installation and ambient temperature)
  Allowable Total Resistance 1000 Ohm or less (signal source plus wiring)
  Effect of Signal Source Resistance +/-20 uV per 1000 Ohm (+/-40 uV in dual-redundant configuration)
  Temperature Drift

+/-80 uV/10 degC (-100 to 150 mV input)


 

+/-30 uV/10 degC (TC/-20 to 80 mV input)

  Data Update Period 1 s
  Burn-out Detection All channels can be set together (Not available/available UP/DOWN), Detection time: 60 s
Electrical & Insulation Withstanding Voltage Between input and system: 1500 V AC, for 1 minute
  Maximum Current Consumption 450 mA (5 V DC)
Physical Specifications Weight 0.2 kg
  External Connection Pressure clamp terminal

Installation Guidelines

  • Use a non-ground type thermocouple (TC) because the device is an isolated type module; using ground type TC on multiple channels causes temperature errors due to multi-point ground.
  • Ensure proper installation onto supported ESB, Optical ESB, or ER bus node units.
  • Maintain matching wiring resistance for signal cables to ensure measurement accuracy.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Yokogawa AAT141-S00 CENTUM VP TC/mV Input Module (16-channel, Isolated)

What input signal types are supported by the module?

The module supports thermocouple types J, K, E, B, R, S, T, and N, as well as mV voltage inputs ranging from -100 to 150 mV and -20 to 80 mV.

Why must non-ground type thermocouples be used with this module?

Because the module is an isolated type, using a ground type thermocouple across multiple channels causes temperature measurement errors due to multi-point grounding.

What is the maximum current consumption for the device?

The maximum current consumption is 450 mA at 5 V DC.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats Arabes Unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
Japon

Produits récemment consultés

Connaissances techniques

Modernisation des IHM Bailey INFI 90 Symphony fonctionnant sous OpenVMS Alpha

Un guide pratique pour remplacer les postes opérateur vieillissants Bailey Symphony fonctionnant sous OpenVMS Alpha. Il compare l’émulation Alpha, la migration vers OpenVMS x86, la refonte basée sur...

Pourquoi les données de maintenance sont essentielles à la fiabilité industrielle

Les données de maintenance relient les ordres de travail, les signaux des capteurs, l’historique des actifs, les coûts et les connaissances des techniciens. Lorsqu’elles sont bien exploitées, elles...

Actionneurs électriques conçus pour remplacer les systèmes de puissance fluidique : guide pratique de l’automatisation industrielle

Cet article explique comment les actionneurs électriques intégrés, tels que la série e-Actuator de SMC, transforment le contrôle des mouvements industriels en remplaçant les systèmes pneumatiques et...

Opérations mathématiques avec OpenPLC pour des applications d’automatisation industrielle

Cet article explique comment les systèmes API réalisent des opérations mathématiques essentielles telles que l’addition, la soustraction, la multiplication, la division, le modulo et l’exponentiation...

Logique booléenne avancée avec la programmation d’API en FBD : applications industrielles pratiques au-delà de la logique de base

L’article explique plusieurs fonctions avancées de logique booléenne utilisées en programmation d’automates au-delà des opérations élémentaires ET, OU et NON. Il présente l’utilisation d’outils tels...

Logique booléenne en programmation d’API : comprendre les portes logiques du langage FBD

La logique booléenne est le fondement de tout programme d’API. Des commandes simples de machines aux systèmes complexes d’automatisation industrielle, les portes logiques déterminent la manière dont...