1 dari 1

Beckhoff EL3621-0020 EtherCAT Terminal 1-channel Analog Input Module

Beckhoff EL3621-0020 EtherCAT Terminal 1-channel Analog Input Module

Hanya 10 item tersisa di stok
  • Produsen: BECKHOFF

  • Nomor Produk: EL3621-0020

  • Negara asal:Jerman

  • Jenis Produk: EtherCAT Terminals

  • Pembayaran: T/T, Western Union

  • Berat: 2000g

  • Dimensi: 12 mm x 100 mm x 68 mm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

Processing high-accuracy current measurements in industrial environments is executed with precision using the Beckhoff EL3621-0020 EtherCAT Terminal. This single-channel differential analog input module handles signal levels from 4 to 20 mA with a highly detailed 24-bit resolution. Each terminal is factory-calibrated, offering an exceptional measuring error margin of less than +/-0.01 % at 25 degC. Operating directly on the EtherCAT I/O system, it bridges the gap between field sensors and centralized controllers with reliable E-bus communication.

Features

  • High-Resolution Analog Digitization: Utilizes 24-bit digital signal conversion (including sign) for highly detailed process values.
  • Factory Calibrated: Supplied with an official analog calibration certificate to ensure traceable measurement accuracy.
  • Integrated Low-Pass Filtering: Hardware features an input filter limit frequency of 3 kHz, coupled with configurable conversion times from 1 ms to 400 ms.
  • Differential Measurement Architecture: Features high common-mode voltage rejection up to a maximum of 10 V.
  • Compact DIN-Rail Housing: Ultra-slim 12 mm form factor minimizes control cabinet footprint.

Applications

  • Process technology loop-monitoring (flow, level, pressure, and temperature transmitters).
  • High-precision test rigs and calibration benches requiring traceable laboratory-grade field metrics.
  • Automated environmental logging stations and chemical dosing systems.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff
Model Number EL3621-0020
Number of Inputs 1 (Differential)
Input Signal Current 4 to 20 mA
Resolution 24-bit (including sign)
Internal Resistance typ. 85 Ohm + diode voltage
Input Filter Limit Frequency 3 kHz
Common-Mode Voltage (Ucm) max. 10 V DC
Conversion Time 1 to 400 ms (configurable)
Measurement Error (at 25 degC) < ±0.01 % (relative to full scale, 50 Hz filter)
Electrical Isolation 500 V (E-bus / signal voltage)
E-Bus Current Consumption typ. 190 mA
Crosstalk Attenuation > 60 dB
Housing Material Polycarbonate
Protection Rating IP20
Operating Temperature 0 to 50 degC
Storage Temperature -25 to 85 degC
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Net Weight approx. 60 g
Shipping Weight (Calculated) 2.0 kg (including secure export packaging)

Connections and Interfaces

Connection Parameter Specification Limits
Wiring Technology Spring actuation via screwdriver
Solid Conductor (e) 0.08 to 2.5 mm² (AWG 28 to 14)
Flexible Conductor (f) 0.08 to 2.5 mm² (AWG 28 to 14)
Conductor with Ferrule (a) 0.14 to 1.5 mm² (AWG 26 to 16)
Stripping Length 8 to 9 mm

Empirical Engineering Insights

Alternative Models & Compatibility

The module provides a factory-calibrated alternative to standard analog inputs where sub-0.01 % accuracy is imperative. Please note that this terminal relies exclusively on the E-bus for power. It does not possess feed-through power contacts, so it must be factored into the overall E-bus current budget calculations when replacing standard, lower-consumption modules.

Application Pitfalls & Engineering Notes

Due to the 190 mA E-bus current consumption of this terminal, installing multiple high-precision modules side-by-side can quickly deplete the couplers feed capacity. Use an intermediate power supply terminal (such as the EL9410) if the total bus consumption exceeds the coupler rating. Avoid placing high-power switching relays immediately adjacent to this card to prevent EMI-induced drift in the 24-bit AD converter.

Commissioning & Wiring Tips

To achieve the factory-calibrated accuracy of less than 0.01 %, use shielded twisted-pair (STP) cabling for the 4 to 20 mA analog signal path. Ensure the cable shield is grounded at the entry point of the control panel. In TwinCAT 3, adjust the conversion filter settings to match the grid frequency (50 Hz or 60 Hz) to optimize common-mode noise rejection.

Installation Guidelines

CRITICAL WARNING: Hazardous electrical voltage can cause electrical shock and equipment damage. Disconnect and lock out all power sources feeding the terminal segment and associated field devices before inserting, removing, or wiring any EtherCAT terminal modules. Ensure the system is completely de-energized.
1
DIN-Rail Mounting: Place the module onto the 35 mm DIN rail (conforming to EN 60715) and push down until the locking mechanism clicks securely into place.
2
Side-by-Side Interlocking: Align the side slots with the adjacent EtherCAT Terminal, ensuring the double slot and key connections are fully seated to establish robust E-bus contact.
3
Wire Termination: Strip the signal wire outer jacket by 8 to 9 mm. Insert a flathead screwdriver into the spring release slot, insert the wire, and release the tension to secure.
Loading product navigation…

Does this terminal require an external power supply for operation?

The module derives its internal processing power entirely from the 5V E-bus on the EtherCAT segment. Ensure that your EtherCAT coupler or bus power supply has sufficient E-bus capacity to cover the typical 190 mA draw.

Can this analog input module measure 0 to 20 mA signals?

This specific high-precision version is optimized and factory-calibrated exclusively for 4 to 20 mA current loops. It is not designed to support 0 to 20 mA ranges.

What is the purpose of the integrated factory calibration?

The factory calibration certificate guarantees an extremely low measuring error of less than +/-0.01 % at 25 degC, which is ideal for systems requiring traceable high-precision measurements without field calibration.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Elektrik yang Dirancang untuk Menggantikan Cairan: Tutorial Praktis

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...