Description

Functioning as an ultra-precise sensor interface, the Beckhoff ELM3104-0000 delivers 4-channel analog current measurements directly to EtherCAT-enabled industrial control environments. This high-speed measurement terminal operates in the +/-20 mA range with an exceptional 24-bit resolution, satisfying the rigorous demands of dynamic processes and high-accuracy laboratory test benches. Housed in a robust zinc die-cast enclosure, it features advanced digital processing functions including oversampling up to 10 ksps per channel, TrueRMS calculations, and customizable digital filters to eliminate high-frequency field noise.

Features

  • 4 simultaneous differential current measurement channels supporting +/-20 mA signals.
  • High-speed delta-sigma A/D converters delivering up to 100 microseconds (10 ksps) sampling rates per channel.
  • Flexible oversampling capability (factor n = 1 to 100) for high-resolution waveform acquisition.
  • Integrated signal conditioning tools: TrueRMS calculation, integrator/differentiator, PeakHold, and non-linear scaling.
  • Precision Distributed Clocks (DC) synchronization providing jitter accuracy far below 1 microsecond.
  • Rugged zinc die-cast housing designed for optimal thermal dissipation and superior mechanical protection.
  • Push-in service plugs for convenient, tool-free field wiring and swift module swap-outs.

Applications

  • High-speed industrial test benches and dynamometers.
  • Vibration monitoring and structural health tracking systems.
  • Precision loop monitoring in chemical processing plants.
  • Acoustic analysis and rapid transient signal logging.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff
Model Number ELM3104-0000
Product Type EtherCAT Measurement Terminal
Number of Channels 4 (differential)
Signal Range +/-20 mA
Resolution 24-bit (including sign)
Sampling Rate Max. 100 microseconds / 10 ksps per channel, simultaneous
Oversampling Factor n = 1 to 100 selectable
Internal Input Resistance 150 Ohms
Measurement Error typ. < +/-100 ppm (+/-0.01 percent) relative to full scale
Temperature Coefficient typ. < 10 ppm/K
E-bus Current Consumption typ. 490 mA
Electrical Isolation 707 V DC channel/bus, 707 V DC channel/SGND
Thermal Dissipation typ. 3 W
Connection Cross-Section Solid/Stranded: 0.2 to 1.5 mm2 (AWG 24 to 14)
Housing Material Zinc die-cast
Dimensions (W x H x D) 30 mm x 100 mm x 95 mm
Operating Temperature -25 to +60 degC
Shipping Weight 2.0 kg

Connections and Interfaces

Terminal / Pin Function / Circuit Assignment
Channel 1 (Pin 1 / Pin 2) Current Input Ch1 (+) / Signal Ground Ch1 (-)
Channel 2 (Pin 1 / Pin 2) Current Input Ch2 (+) / Signal Ground Ch2 (-)
Channel 3 (Pin 1 / Pin 2) Current Input Ch3 (+) / Signal Ground Ch3 (-)
Channel 4 (Pin 1 / Pin 2) Current Input Ch4 (+) / Signal Ground Ch4 (-)

Alternative Models & Compatibility

While standard EL3xxx series modules address general-purpose current tracking, the ELM3104-0000 high-precision measurement module requires TwinCAT 3 runtime integration to support advanced oversampling algorithms and full 24-bit resolution processing. This module is fully backward compatible with standard EtherCAT networks but necessitates a dedicated system bus layout capable of supplying its typical 490 mA E-bus power requirement.

Application Pitfalls & Engineering Notes

To maintain the 100 ppm accuracy specification, ensure that all current loops use shielded twisted-pair (STP) cabling. Electromagnetic interference in proximity to heavy frequency drives can induce noise, reducing the module's effective number of bits (ENOB). The zinc die-cast chassis must be mounted onto a well-grounded, oxidation-free 35 mm steel DIN rail to maintain optimal shield pathing and thermal dissipation under full 3 W load conditions.

Commissioning & Wiring Tips

Utilize the integrated 2-pin push-in service plugs for high-vibration applications. This feature allows rapid module replacement without individual wire extraction, minimizing wiring errors. When commissioning in TwinCAT, verify that Distributed Clocks (DC) are enabled for the terminal to align historical process inputs with sub-microsecond precision across multiple nodes.

Installation Guidelines

CRITICAL WARNING: De-energize all power distribution blocks, control cabinets, and auxiliary supply circuits prior to mounting or dismounting the terminal. Failure to isolate the power supply can lead to unexpected system bus damage, electrical shocks, or critical degradation of the internal delta-sigma analog circuitry.
1

Mount the ELM3104-0000 directly onto a clean, grounded 35 mm DIN rail (conforming to EN 60715).

2

Engage the double slot and key connection on the side of the terminal block to securely latch into the adjacent EtherCAT modules.

3

Strip the analog signal wires to a precise length of 8 to 9 mm. Insert solid conductors or stranded wires with ferrules directly into the push-in terminal plug.

4

Power on the system and scan the EtherCAT network topology in the TwinCAT System Manager to configure filters and sample rates.

Loading product navigation…

What is the maximum oversampling rate for the ELM3104-0000?

The terminal supports an oversampling factor of n = 1 to 100, allowing it to achieve a sampling rate up to 10 ksps (10,000 samples per second) simultaneously across all 4 channels.

How is the ELM3104-0000 different from standard EL3xxx modules?

The ELM series offers a higher 24-bit resolution, strict +/-100 ppm accuracy, and a zinc die-cast housing designed for structural shielding and thermal management in high-precision measurement tasks.

What software is required to configure the integrated digital filters?

Configuration of digital filters, TrueRMS calculations, and scaling parameters must be performed via TwinCAT 3 during the system engineering and commissioning process.

What is the E-bus current consumption of this terminal?

The ELM3104-0000 typically draws 490 mA from the E-bus. System designers must ensure the power supply terminal upstream provides sufficient current headroom.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...