1 dari 1

Beckhoff EP3174-0092 EtherCAT Box 4-channel Analog Input Module

Beckhoff EP3174-0092 EtherCAT Box 4-channel Analog Input Module

Hanya 10 item tersisa di stok
  • Produsen: BECKHOFF

  • Nomor Produk: EP3174-0092

  • Negara asal:Jerman

  • Jenis Produk: EtherCAT I/O Modules

  • Pembayaran: T/T, Western Union

  • Berat: 500g

  • Dimensi: 150 x 40 x 40 mm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

Engineered for direct field installation without an electrical enclosure, the Beckhoff EP3174-0092 EtherCAT Box provides four high-precision, individually parameterizable differential analog inputs. This IP67-rated module processes signals in the ranges of -10/0 to +10 V or 0/4 to 20 mA per channel, offering 16-bit resolution with integrated Distributed Clocks for precise temporal synchronization. Its robust, fully-sealed design makes it ideal for harsh industrial environments where decentralized signal acquisition is required.

Key Features

  • Four Differential Inputs: Individually parameterizable for voltage or current signals.
  • 16-Bit Resolution: High-precision digitization (including sign) for demanding measurement tasks.
  • High-Speed Processing: 100 us conversion time with a 5 kHz input filter limit frequency.
  • Distributed Clocks: Supports ultra-precise, synchronized time-stamped data acquisition across the EtherCAT network.
  • Rugged Build: IP65/66/67 protection rating for moisture, dust, and washdown protection.
  • Standardized Connectors: M12 x 1 analog interface combined with M8 EtherCAT and power interfaces.

Applications

  • Decentralized process measurement in machine building and plant engineering.
  • Heavy-duty automated material handling and conveyor installations.
  • On-machine mounting in wet or high-vibration manufacturing environments.
  • Distributed sensor integration requiring rapid loop update times.

Technical Specifications

Manufacturer Beckhoff Automation GmbH & Co. KG
Model Number EP3174-0092
Protocol EtherCAT
Number of Inputs 4 (Differential)
Signal Types -10/0...+10 V | 0/4...20 mA (Configurable per channel)
Resolution 16-bit (including sign)
Conversion Time approx. 100 us
Internal Resistance > 200 kOhm (Voltage) | typ. 85 Ohm + diode voltage (Current)
Common-Mode Voltage (U_CM) max. 35 V
Measurement Error < +/-0.3% (relative to full scale value)
Nominal Supply Voltage 24 V DC (-15% / +20%)
Current Consumption (from U_S) 120 mA
Electrical Isolation 500 V
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Protection Rating IP65/66/67 (conforms to EN 60529)
Approvals CE, UL
Country of Origin Germany
Shipping Weight (Calculated) 0.5 kg (Net Unit Weight: 165 g)
Package Dimensions (Calculated) 150 x 40 x 40 mm

Connections and Interfaces

Connector / Port Interface & Pin Assignment
Input Channels (1 to 4) M12 x 1 female socket, 5-pin, A-coded (Pin 1: +24V Sensor supply; Pin 2: Input +; Pin 3: GND; Pin 4: Input -; Pin 5: Shield)
EtherCAT Bus 2 x M8 socket, 4-pin, shielded, screw type (Input and downstream Connection)
Power Supply Feed 1 x M8 male socket, 4-pin (Pin 1: +24V US; Pin 2: +24V UP; Pin 3: GND S; Pin 4: GND P)
Power Downstream 1 x M8 female socket, 4-pin (For daisy-chaining supply to next node)

Empirical Engineering Insights

Alternative Models & Compatibility

The EP3174-0092 utilizes standard EtherCAT XML Device Description (ESI) files. In older TwinCAT 2.11 environments, make sure to update the device description repository to correctly resolve the -0092 hardware profile. It acts as a drop-in physical replacement for older IP67 analog input modules, provided the pin assignments for the differential ground connections are respected.

Application Pitfalls & Engineering Notes

When using differential inputs, ensure that the common-mode voltage between any input signal and the module's internal ground does not exceed the maximum rating of 35 V DC. If you are integrating 3-wire sensors or ungrounded signal generators, a high impedance path to the system ground should be provided to prevent signal drift and potential saturation of the differential input stages.

Commissioning & Wiring Tips

Always configure the channel parameter settings (CoE Index 0x8000 to 0x8030) inside the TwinCAT System Manager prior to applying analog loops. Connecting an active 4-20 mA current loop while the channel is still configured for a 10V input range can lead to faulty process readouts, though the internal input stage is electrically protected from nominal overcurrent.

Installation Guidelines

CRITICAL WARNING:

Do not connect or disconnect any M8 or M12 connectors under active electrical load. Always isolate the 24V DC control supply (US) and the load supply (UP) before performing installation, maintenance, or reconfiguration. Failure to do so can cause permanent damage to the contacts and internal communication chipsets.

1 Mount the EP3174-0092 directly onto a flat machine surface or profile rail using two M3 screws through the integrated mounting ears.
2 Ensure the physical earthing path is secure by utilizing a conductive mounting surface or running a separate ground strap to the designated functional earth terminal.
3 Connect the shielded M12 analog input lines, verifying that the cable shields are correctly terminated to the connector sleeves.
4 Attach the M8 EtherCAT communication lines, secure with nominal screw-torque to ensure IP67 sealing, and apply power.
Loading product navigation…

How do I switch the EP3174-0092 channels between voltage and current modes?

Channel configuration is handled via CoE (CANopen over EtherCAT) directory parameters in TwinCAT. You must configure the operational parameters under index 0x8000 for Channel 1 through 0x8030 for Channel 4 to switch between -10/0...+10V and 0/4...20mA ranges.

What is the maximum allowed common-mode voltage for the differential inputs?

The differential inputs support a maximum common-mode voltage (U_CM) of 35 V DC. Exceeding this limit relative to the internal reference will result in measurement errors or potential hardware damage.

Can the sensor supply on the M12 ports be switched or protected?

The sensor supply is derived directly from the load voltage UP. It is short-circuit proof and distributed to the M12 connection sockets, but it is not individually software-switchable per channel.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...