Facilitating high-precision analog signal generation directly in decentralized environments, the Beckhoff EPP4174-0002 EtherCAT P Box integrates four individually parameterizable analog outputs within a ruggedized IP67 housing. This module eliminates the need for protective control cabinets by allowing users to transmit both EtherCAT telemetry and dual 24 V DC power supplies (US for system/sensor power and UP for peripheral/actuator power) through a single, P-coded M8 cable interface. Designed for demanding field use, each channel on the EPP4174-0002 can be independently configured to output standard control signals, ensuring direct compatibility with a wide array of field actuators, positioning valves, and variable speed drives.

Key Features

  • Flexible Signal Configuration: Individually parameterize each of the 4 channels to support -10/+10 V voltage loops or 0/4...20 mA current loops.
  • EtherCAT P Cabling Solution: Uses standard M8 P-coded industrial connectors to combine high-speed communication and power distribution on a single connection.
  • Industrial Durability: Complete IP65, IP66, and IP67 protection class housing, allowing direct machine mounting in environments with moisture, dust, and vibration.
  • High-Resolution DAC: Embedded 16-bit digital-to-analog converter with a highly responsive conversion time of approximately 40 microseconds.
  • Integrated Actuator Supply: Actuator field power is distributed directly from the auxiliary voltage UP channel, simplifying external wiring configurations.

Industrial Applications

  • Decentralized control valve positioning and pneumatic actuator modulation in process lines.
  • Speed and torque setpoint generation for distributed variable frequency motor drives.
  • Remote analog instrumentation interfacing in harsh manufacturing and maritime environments.
  • Direct machinery integration for distributed material handling and packaging systems.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Reference EPP4174-0002
Interface Protocol EtherCAT P
Number of Channels 4 analog outputs
Signal Formats -10 to +10 V | 0 to 20 mA | 4 to 20 mA (Configurable per channel)
Resolution 16 bit
Conversion Time Approx. 40 microseconds
Voltage Mode Load > 5 kOhm
Current Mode Load < 500 Ohm
Accuracy Deviation < 0.1% (Relative to full scale limit value)
Power Feed Nominal 24 V DC (-15% / +20%)
Current Usage (US) Typ. 100 mA
Electrical Isolation 500 V RMS
Environmental Limits Operating: -25 to +60 Celsius | Storage: -40 to +85 Celsius
Enclosure Rating IP65 / IP66 / IP67 (Conforms to EN 60529)
Country of Origin Germany
Shipping Weight (Calculated) 0.50 kg (with protective system packaging)
Package Dimensions (Calculated) 150 x 50 x 40 mm

Connections and Interfaces

M12 Output Pin Function / Assignment
Pin 1 +24 V DC Actuator Supply (UP)
Pin 2 Analog Output + (Voltage/Current Signal)
Pin 3 GND (UP) (Actuator Reference)
Pin 4 Analog Output - (Signal Ground Reference)
Pin 5 Functional Earth (FE Shield Connection)

Empirical Engineering Insights

Alternative Models & Compatibility

The EPP4174-0002 operates strictly within EtherCAT P environments. It is physically key-coded with a P-coded M8 connector scheme to prevent accidental insertion of standard EtherCAT cables. If replacing or interfacing with traditional standard EtherCAT segments (EP series), you must deploy an intermediate hub or coupler (such as the EP9224 or EK1300) to safely transition and inject the combined US and UP power lines.

Application Pitfalls & Engineering Notes

When driving long analog cables in high electromagnetic interference (EMI) environments, ensure the shielded M12 connectors are grounded to functional earth via the FE pin. Avoid running analog lines adjacent to high-power motor lines. If a current loop channel encounters open-circuit status, the 16-bit DAC register values in TwinCAT will saturate and reflect a diagnostic fault code; ensure error handling algorithms are standard practice within the PLC task cycles.

Commissioning & Wiring Tips

Always complete your configuration within TwinCAT System Manager under the CoE (CanOpen over EtherCAT) directory before supplying active load connections. Do not swap configurations from current to voltage online while an active actuator is connected, as short-circuits or excess drive current may occur. Make sure the total current draw sourced from the auxiliary voltage UP does not exceed the continuous rating of the distribution block.

Installation Guidelines

CRITICAL WARNING:

Disconnect and isolate all power sources (US and UP) before connecting or disconnecting the M8 EtherCAT P or M12 analog cabling. Hot-plugging industrial connectors in wet or hazardous conditions can compromise the internal electrical isolation limits and potentially cause damage to the integrated D/A hardware.

1

Mount the EPP4174-0002 unit using the integrated screw points directly onto flat, vibration-resistant machinery structures or mounting brackets.

2

Connect the incoming EtherCAT P lines using shielded M8 P-coded screw-type connectors, tightening to the recommended OEM torque specification.

3

Configure the analog output parameters (current / voltage profiles) in the TwinCAT System Manager software, ensuring signal ranges match downstream actuator requirements.

Loading product navigation…

Can the EPP4174-0002 module be connected to a standard EtherCAT network?

No. The module features P-coded M8 interfaces designed for unified EtherCAT P lines containing integrated system and peripheral power loops. It requires an EtherCAT P junction or master interface to link into traditional EtherCAT systems.

How is the signal output range configured for each individual channel?

Each analog output channel is parameterized independently. Signal settings (-10/+10 V, 0-20 mA, or 4-20 mA) must be set via the CANopen over EtherCAT (CoE) online directory inside TwinCAT software.

What is the maximum allowable load for current output mode on this module?

The output load for channels configured for current signals must remain below 500 Ohms. Exceeding this boundary causes DAC signal clipping and registers a saturation error in the process image.

How are connected field actuators powered by this module?

Actuators receive direct supply current from the distributed UP auxiliary power line. This is routed through the M12 connector's Pin 1, avoiding additional power drops.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...