Decentralized field automation requirements are directly addressed by the IP5009-B528, a high-performance DeviceNet fieldbus box engineered by Beckhoff for direct mounting in demanding industrial environments. This station connects digital and analog peripheral signals directly to DeviceNet networks without requiring a protective control cabinet. By utilizing integrated M12 tee-connector ports and M8 power feed-through interfaces, this module enables efficient line-topology wiring directly on the machinery.

The module supports configuration flexibility through either the Beckhoff KS2000 software suite or directly via the master controller using explicit messaging. The integrated electronics dynamically adapt to network transfer rates up to 500 kbaud. Electrical isolation of 500 V between the control voltage and the fieldbus line provides robust protection against transient noise and grounding loops, securing reliable I/O data transmission across varying plant distances.

Features

  • DeviceNet Integration: Full compatibility with DeviceNet physical layer and protocol specifications.
  • Automatic Baud Rate Detection: Automatically syncs with the master station at transmission speeds up to 500 kbaud.
  • Integrated Tee-Connector: Built-in 1 x M12 plug (5-pin) and 1 x M12 socket (5-pin) interfaces eliminate the need for external T-pieces.
  • Flexible I/O Mapping: Handles digital and analog peripheral signals based on the specific module extension and I/O layout.
  • Power Daisy-Chaining: Features an M8 male input and M8 female downstream power connection to feed control and load voltages.
  • Robust Environmental Housing: Rated up to IP67 for dust and water ingress protection, allowing direct machinery mounting without enclosures.

Applications

  • Automotive assembly lines and robotic welding cells
  • Packaging machinery and material handling conveyor networks
  • Water and wastewater processing systems with decentralized control nodes
  • General factory automation requiring IP67 distributed field I/O

Technical Specifications

ManufacturerPart Number / ModelFieldbus ProtocolData Transfer RatesBus InterfaceData Transfer MediumControl Voltage SupplyLoad Voltage SupplyPower Supply ConnectionBox Supply CurrentElectrical IsolationI/O Communication TypesOperating TemperatureStorage TemperatureVibration/Shock ResistanceEMC Immunity/EmissionProtection ClassInstallation PositionShipping Weight
BECKHOFF
IP5009-B528
DeviceNet
Automatic detection up to 500 kbaud
1 x M12 plug (5-pin), 1 x M12 socket (5-pin) (tee-connector integrated)
Shielded copper cable, with power supply, typ. 2 x 2 x 0.25 mm²
24 V DC (-15 % / +20 %)
According to connected I/O type
Feed: 1 x M8 male socket (4-pin); Downstream: 1 x M8 female socket (4-pin)
45 mA + current consumption of sensors (max. 0.5 A)
Control voltage/fieldbus: 500 V; Control voltage/I/O: according to I/O type
Bit strobe, polling, cyclic, change of state (COS)
0 to +55 degC
-25 to +85 degC
Conforms to EN 60068-2-6 / EN 60068-2-27
Conforms to EN 61000-6-2 / EN 61000-6-4
IP65/66/67 (conforms to EN 60529)
Variable
2.0 kg

Connections and Interfaces

Connection Interface Connector Type Function
Bus Input M12 Plug, 5-pin DeviceNet upstream fieldbus network connection
Bus Output M12 Socket, 5-pin DeviceNet downstream connection (integrated T-connector)
Power Input M8 Male Socket, 4-pin Feed control voltage (24 V DC) and sensor/actuator power
Power Output M8 Female Socket, 4-pin Downstream control and load voltage loop-through

Installation Guidelines

  • Mounting: Secure the unit to a flat, rigid machine surface using the integrated mounting flanges. Avoid mounting orientations that expose the connection points to continuous fluid pooling.
  • Grounding: Ensure a low-impedance connection to the machine ground. Use the provided mounting holes or local functional earth contacts.
  • Cabling and Torquing: All unused M12 and M8 ports must be sealed with appropriate protective caps to maintain the IP65/66/67 rating. Tighten mating connectors to the manufacturer-specified torque limits.
  • Cable Routing: Route fieldbus communication cables away from high-noise power lines, motor cables, and variable frequency drives to prevent electromagnetic interference.

Compliance and Certifications

  • CE
  • UL
Loading product navigation…

What fieldbus protocol does the Beckhoff IP5009-B528 utilize?

The IP5009-B528 utilizes the DeviceNet fieldbus protocol, supporting automatic baud rate detection up to 500 kbaud.

How is the IP5009-B528 fieldbus box configured?

The module can be configured using the Beckhoff KS2000 configuration software or directly via the main controller using explicit messaging.

Does this module require an external junction or T-connector for network wiring?

No, the IP5009-B528 features an integrated tee-connector with 1 x M12 plug (5-pin) and 1 x M12 socket (5-pin) for direct network line routing.

What are the environmental ratings for this device?

The device features an IP65, IP66, and IP67 ingress protection rating, making it suitable for cabinet-free installation directly on machinery.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...