BECKHOFF

BECKHOFF EPP3184-0002 EtherCAT P Box

SKU EPP3184-0002

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: EPP3184-0002

  • Country of origin:Germany

  • Product Type: EtherCAT P Boxes

  • Payment: T/T, Western Union

  • Weight: 165g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The BECKHOFF EPP3184-0002 is a high-performance EtherCAT P Box designed for the direct acquisition of analog process signals in industrial environments. Utilizing advanced EtherCAT P technology, this unit integrates both high-speed communication and electrical power supply (system and sensor supply Us, peripheral voltage for actuators Up) into a single, standard cable. This unified architecture simplifies system wiring, minimizes installation footprint, and lowers overall commissioning costs.

Equipped with four single-ended analog inputs, the BECKHOFF EPP3184-0002 offers exceptional flexibility by allowing each channel to be individually parameterized. Field sensors transmitting standard voltage ranges (-10/0 to +10 V) or current signals (0/4 to 20 mA) can be connected directly without requiring hardware-variant changes. With its 16-bit resolution, fast conversion time, and configurable input filters, this EtherCAT P Box delivers precise, synchronized measurement data directly from the machine field level.

Features

  • Four single-ended analog input channels with parameterization per channel for voltage or current signals.
  • EtherCAT P technology integrating data transmission and 24 V DC power supply in one M8 connector.
  • High-precision 16-bit analog-to-digital conversion (including sign).
  • Supports Distributed Clocks (DC) for precise temporal synchronization across the EtherCAT network.
  • Configurable input filters to suppress high-frequency signal noise.
  • Rugged IP65, IP66, and IP67-rated enclosure suitable for wet, dusty, and harsh industrial environments.
  • Diagnostic and status LEDs indicating operating states, bus activity, and channel errors.

Applications

  • Machine-level analog sensor data acquisition without protective control cabinets.
  • Distributed process measurement systems requiring localized signal processing.
  • Factory automation environments utilizing decentralized EtherCAT P topologies.
  • Applications requiring precise multi-channel voltage and current tracking under synchronized Distributed Clocks.

Technical Specifications

Parameter Specification
Manufacturer BECKHOFF
Model Number EPP3184-0002
Product Type EtherCAT P Box (Analog Input)
Number of Inputs 4 single-ended
Signal Type (Parameterizable) -10 to +10 V, 0 to +10 V, 0 to 20 mA, 4 to 20 mA
Resolution 16 bit (including sign)
Measurement Error / Uncertainty Less than +/-0.3% (relative to full-scale value)
Conversion Time Approximately 100 microseconds
Input Filter Limit Frequency 5 kHz
Input Filter Settings Configurable
Internal Resistance (Voltage Input) Greater than 200 kOhm
Internal Resistance (Current Input) Typically 85 Ohm + diode voltage
Common-Mode Voltage (Ucm) Maximum 35 V
Nominal Voltage 24 V DC (-15% / +20%)
Sensor Supply Derived from load supply voltage (Up)
Current Consumption (from Us) Typically 100 mA
Electrical Isolation 500 V
Distributed Clocks (DC) Yes
Bus Interface Connection 2 x M8 socket, shielded, screw type, P-coded
Input Connection Technology M12 x 1, 5-pin, A-coded
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity / Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Approvals and Markings CE, UL
Weight Approximately 165 g

Installation Guidelines

  1. Verify the system architecture and ensure the power source matches the required 24 V DC supply before installation.
  2. De-energize all power supplies feeding the EtherCAT P segment to prevent electrical shock or hardware damage.
  3. Securely mount the EtherCAT P Box to the machine frame or mounting plate in a position that accommodates cabling without strain.
  4. Connect the EtherCAT P bus cables using the shielded M8 screw-type, P-coded sockets. Ensure the connectors are fully tightened to maintain the IP65/66/67 protection rating.
  5. Connect the analog sensors to the A-coded M12 input sockets. Verify correct pin mapping and signal types before starting the system.
  6. Ensure proper grounding and shielding policies are met to protect analog signals from electro-magnetic interference (EMI).
  7. Apply power and configure the module via the TwinCAT System Manager.

Configuration Guidelines

The BECKHOFF EPP3184-0002 must be configured in the TwinCAT engineering software. Scan the EtherCAT P network or manually import the corresponding EtherCAT Software Information (ESI) file. For each individual channel, navigate to the parameterization settings to set the desired input signal type (voltage or current) and configure input filter characteristics as demanded by the application requirements.

FAQ

What is the primary function of the BECKHOFF EPP3184-0002?

The BECKHOFF EPP3184-0002 is a 4-channel analog input EtherCAT P Box designed to acquire voltage (-10/0 to +10 V) or current (0/4 to 20 mA) signals from field sensors and transmit them to the controller over an EtherCAT P network.

Can the analog input channels of the BECKHOFF EPP3184-0002 be configured independently?

Yes, each of the four analog input channels on the BECKHOFF EPP3184-0002 can be individually parameterized in TwinCAT to measure either voltage or current signals.

What connection technology does the BECKHOFF EPP3184-0002 use for field sensors?

The BECKHOFF EPP3184-0002 features M12 x 1, 5-pin, A-coded sockets for robust and secure connection of analog sensor devices.

How is the BECKHOFF EPP3184-0002 powered and connected to the network?

The BECKHOFF EPP3184-0002 utilizes EtherCAT P technology, which combines EtherCAT communication and 24 V DC power supplies (both system and peripheral voltage) in a single M8 P-coded connector.

Does the BECKHOFF EPP3184-0002 support Distributed Clocks?

Yes, the BECKHOFF EPP3184-0002 supports Distributed Clocks (DC), ensuring precise temporal synchronization of the analog input measurements across the EtherCAT system.

Is the BECKHOFF EPP3184-0002 suitable for installation without a control cabinet?

Yes, the BECKHOFF EPP3184-0002 features an IP65/66/67 protection rating, allowing it to be installed directly on machines in harsh environments without an enclosure.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.