The 990-10-50-01-05 is a two-wire, loop-powered vibration transmitter designed to provide a simple 4 to 20 mA proportional vibration signal directly to a machinery control system. This 990 Vibration Transmitter integrates a Proximitor Sensor into a single unit, accepting input from a 3300 NSv proximity probe and its matching extension cable. It conditions the transducer signal into appropriate peak-to-peak vibration amplitude engineering units, enabling cost-effective machinery protection alarming, logic, and overall vibration trending without requiring an external proximity sensor unit.
Features
Integrated Proximitor Sensor eliminates the need for an external housing or separate signal conditioner.
Non-isolated PROX OUT and COM terminals alongside a coaxial connector provide dynamic vibration and gap voltage signal output for diagnostics.
Non-interacting zero and span potentiometers beneath the transmitter label allow easy loop adjustment.
Dedicated Test Input pin enables swift verification of the loop signal output via an external function generator.
Built-in Not OK/Signal Defeat circuit prevents false alarms or high loop outputs caused by loose connections or a faulty proximity probe.
Dual mounting flexibility with standard options for either 35 mm DIN-rail clips or bulkhead mounting screws.
Potted construction ensures dependable performance in high-humidity environments up to 100% condensing.
Applications
Centrifugal air compressors
Small industrial pumps
Electric motors
Industrial cooling fans
Ordering Information
990: Vibration Transmitter
10: 0-10 mils pp (0-250 um pp) Full-scale Option
50: 5.0 meters (16.4 feet) System Length Option
01: 35 mm DIN rail clips Mounting Option
05: CSA Division 2, ATEX Zone 0, ATEX Zone 2 and includes ABS maritime approval Agency Approval Option
Technical Specifications
Parameter
Specification
Manufacturer
Bently Nevada
Model
990-10-50-01-05
Input Signal
Accepts 1 non-contacting 3300 NSv Proximity Probe and extension cable
Power Requirements
+12 to +35 Vdc input at the transmitter terminal (28 Vdc for Hazardous locations)
Signal Output
4 to 20 mAdc over specified full-scale range in 2-wire configuration
Loop Accuracy
Within +-1.5% over specified full-scale range across a 250 Ohm loop resistance
Maximum Loop Resistance
1,000 Ohm including cable at 35 Vdc
Current Limiting
23 mA typical
Probe Gap Requirement
0.5 to 1.75 mm (20 to 55 mils) from target to ensure full scale range
Prox Out Linear Range
1.4 mm (55 mils), starting at approx 0.25 mm (10 mils) from target surface
Prox Out Scale Factor
7.87 mV/um (200 mV/mil) +-6.5% typical; worst case +-10%
Frequency Response
5 Hz to 6,000 Hz +0, -3 dB
Not OK / Signal Defeat
Output drops to less than 3.6 mA within 100 us of fault; restores in 2-3 seconds
Power-up Inhibit
Output held at less than 3.6 mA for 2 to 3 seconds after power application
Prox Out Impedance
10 kOhm output impedance calibrated for a 10 MOhm load
Typical Noise Level
50 mV pp
Minimum Target Size
9.5 mm (0.375 in) diameter AISI 4140 steel
Maximum Leadwire Length
3 meters (10 feet) for Proximitor Sensor Output (BNC connector)
Non-isolated dynamic vibration and gap voltage signal (BNC/Terminals)
COM
Common reference terminal for loop power and diagnostics
+
Positive loop power input (+12 to +35 Vdc)
-
Negative loop power return / 4-20 mA current output
TEST
Test Input pin for external function generator signal verification
Coaxial Jack
Direct connection to the 3300 NSv matching extension cable
Installation Guidelines
Probe Gap Adjustment
The proximity probe must be mechanically gapped between 0.5 and 1.75 mm (20 and 55 mils) from the target surface during installation. This ensures that the probe operates entirely within its linear range and allows the transmitter to accurately generate the full-scale 4 to 20 mA output.
Thread Engagement Limits
When installing the probe into a threaded mounting hole, do not exceed the industry-standard maximum thread engagement length of 1.5 times the nominal thread diameter. For a 1/4-28 thread, maximum engagement is 0.375 in; for M8x1, it is 12 mm. Exceeding these limits can cause mechanical binding and voids the warranty. For 1/4-28 probes, a #3 or larger tap drill is recommended.
Signal Isolation and Diagnostics
The PROX OUT coaxial connector provides a dynamic transducer signal for diagnostics but is not isolated from the 4 to 20 mA loop. While it can connect directly to isolated, battery-powered test equipment, using an external test adapter (such as the 990/991 Test Adapter) is strongly recommended when connecting to AC-powered equipment like oscilloscopes. This preserves loop isolation and prevents false alarms or loop degradation.
Moisture Protection
The transmitter features a potted construction rated for up to 100% condensing humidity. However, the coaxial connectors on the probe and extension cable must be physically protected against fluid ingress to maintain calibration and signal integrity.
Compliance and Certifications
CSA: Class I, Division 2
ATEX: Zone 0, Zone 2
Marine: ABS maritime approval
FAQ
Can the 4 to 20 mA loop output be used to analyze vibration phase or establish gap alarms?
No. The 4 to 20 mA loop output provides only overall peak-to-peak vibration amplitude data. It cannot capture vibration phase or support advanced monitoring features such as gap alarms, phase alarms, Danger Bypass, or Trip Multiply.
What happens to the loop output if the proximity probe cable is disconnected or cut?
The transmitter features a Not OK/Signal Defeat circuit. If a fault or loose connection occurs, the loop signal drops to less than 3.6 mA within 100 microseconds to prevent high outputs or false machinery alarms. It restores within 2 to 3 seconds once the fault condition is resolved.
Is an external Proximitor sensor needed when ordering this transmitter?
No. The unit features a fully integrated Proximitor sensor inside the transmitter housing. It connects directly to the 3300 NSv probe extension cable without needing an intermediary signal conditioner.
Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...
From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...
Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...
This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...
This tutorial explores the commissioning of a single-axis servo motion system using a CMZ SBD drive, covering hardware setup, axis scaling, homing configuration, and safe motion verification for...
This tutorial explains how Mitsubishi FX PLCs integrate with FR-D700 VFDs and HMI panels for forward/reverse motor control. It covers wiring logic, parameter configuration, ladder programming, and...
Choosing a selection results in a full page refresh.