| z2 |
UB+ (+24V, redundant supply input) |
| b2 |
U- (0V/Common supply) |
| d2 |
UN+ (+24V supply input) |
| z4 |
B (RS 485 bus line) |
| b4 |
GND (BP, Common, RS 485) |
| d4 |
A (RS 485 bus line) |
| z6 |
Supply1+ (sensor supply channel 1) |
| b6 |
Supply1- (sensor supply channel 1) |
| d6 |
Supply2+ (sensor supply channel 2) |
| z8 |
AIN1- (Input channel 1, SENS1-A-) |
| b8 |
Supply2- (sensor supply channel 2) |
| d8 |
AIN2- (Input channel 2, SENS2-A-) |
| z10 |
AIN1+ (Input channel 1, SENS1-B+) |
| b10 |
GND (Common) |
| d10 |
AIN2+ (Input channel 2, SENS2-B+) |
| z12 |
Test1 (internal test value activation channel 1) |
| b12 |
GND |
| d12 |
PU1 (24V pull-up pulse1) |
| z14 |
Pulse1-TTL (processed pulse output 1) |
| b14 |
Pulse1-E (emitter pulse 1) |
| d14 |
Pulse1-C (collector pulse 1) |
| z16 |
Pulse2-TTL (processed pulse output 2) |
| b16 |
Pulse2-E (emitter pulse 2) |
| d16 |
Pulse2-C (collector pulse 2) |
| z18 |
I1+ (current output CH1) |
| b18 |
I1- (current output CH1 common) |
| d18 |
PU2 (24V pull-up pulse2) |
| z20 |
I2+ (current output CH2) |
| b20 |
I2- (current output CH2 common) |
| d20 |
Reset peak value 1 |
| z22 |
ES (external lock input) |
| b22 |
GND |
| d22 |
Test2 (internal test value activation channel 2) |
| z24 |
SC-D (operating principle GW1 / Out 2-1 inversion) |
| b24 |
GND |
| d24 |
SC-A (operating principle GW2 / Out 1-1 inversion) |
| z26 |
CC1-C (channel clear 1 collector) |
| b26 |
GW1-A-C (alert 1 collector / Out 1-2 collector) |
| d26 |
GW1-D-C (danger 1 collector / Out 1-1 collector) |
| z28 |
CC1-E (channel clear 1 emitter) |
| b28 |
GW1-A-E (alert 1 emitter / Out 1-2 emitter) |
| d28 |
GW1-D-E (danger 1 emitter / Out 1-1 emitter) |
| z30 |
CC2-C (channel clear 2 collector) |
| b30 |
GW2-A-C (alert 2 collector / Out 2-2 collector) |
| d30 |
GW2-D-C (danger 2 collector / Out 2-1 collector) |
| z32 |
CC2-E (channel clear 2 emitter) |
| b32 |
GW2-A-E (alert 2 emitter / Out 2-2 emitter) |
| d32 |
GW2-D-E (danger 2 emitter / Out 2-1 emitter) |